O. Reg. 318/17: ENERGY AND WATER EFFICIENCY - APPLIANCES AND PRODUCTS

filed August 1, 2017 under Green Energy Act, 2009, S.O. 2009, c. 12, Sched. A

Skip to content

 

ontario regulation 318/17

made under the

Green Energy Act, 2009

Made: July 26, 2017
Filed: August 1, 2017
Published on e-Laws: August 1, 2017
Printed in The Ontario Gazette: August 19, 2017

Amending O. Reg. 404/12

(ENERGY and water EFFICIENCY - APPLIANCES AND PRODUCTS)

1. Subsection 2 (3) of Ontario Regulation 404/12 is revoked and the following substituted:

(3) Symbols and acronyms used in the Schedules have the following meanings, unless the context requires otherwise:

1. AC: alternating current.

2. AFUE: annual fuel utilization efficiency.

3. AHRI: Air-Conditioning, Heating and Refrigeration Institute.

4. ANSI: American National Standards Institute.

5. BIL: basic impulse insulation level.

6. Btu/h: British thermal units per hour.

7. CGA: Canadian Gas Association.

8. CIE: International Commission on Illumination.

9. COP: coefficient of performance.

10. CSA: Canadian Standards Association.

11. C: degree(s) Celsius.

12. DC: direct current.

13. EER: energy efficiency ratio.

14. Federal Energy Efficiency Regulations (May 4, 2012 version): SOR/94-651 (Energy Efficiency Regulations) made under the Energy Efficiency Act (Canada) as the Regulations read on May 4, 2012.

15. HSPF V: heating season performance factors — region V.

16. Hz: hertz.

17. IEC: International Electrotechnical Commission.

18. IEER: integrated energy efficiency ratio.

19. IES: Illuminating Engineering Society of North America.

20. kV: kilovolts.

21. kVA: kilovolt-amperes.

22. kW: kilowatts.

23. kWh: kilowatt-hours.

24. L: litres.

25. lm/W: lumens per watt.

26. mL/s: millilitres per second.

27. NEMA: National Electrical Manufacturers Association.

28. NFRC: National Fenestration Rating Council.

29. SDHV: small duct high velocity.

30. U.S. DOE: United States Department of Energy.

31. VRF: variable refrigerant flow.

32. W: watts.

33. W/(m²C): watts per meter squared degrees Celsius.

2. Table 1 of the Regulation is revoked.

3. Subparagraph 18 i of section 1 of Schedule 1 to the Regulation is amended by striking out “June 5, 2017” and substituting “January 1, 2020”.

4. (1) Sub-subparagraph 2 i A of section 1 of Schedule 4 to the Regulation is revoked and the following substituted:

A. For an air conditioner or heat pump with at least 19 kW (65,000 Btu/h) of cooling capacity, excluding packaged terminal and single-package vertical air conditioners and heat pumps, the day before the earliest applicable compliance date for the particular air conditioner or heat pump as set out in Column 7 of Table 1 and Column 9 of Tables 2 and 3 to sub-subparagraph 2.1 iv A.  For greater certainty, the particular air conditioner or heat pump is described in Columns 2, 3 and 4, read together, of Tables 1, 2 and 3.

(2) Sub-subparagraph 2.1 i A of section 1 of Schedule 4 to the Regulation is revoked and the following substituted:

A. For an air conditioner or heat pump described in the Tables to sub-subparagraph iv A, from the later applicable compliance date for the particular air conditioner or heat pump as set out in Column 7 of Table 1 and Column 9 of Tables 2 and 3 to December 31, 2017, inclusive. For greater certainty, the particular air conditioner or heat pump is described in Columns 2, 3 and 4, read together, of Tables 1, 2 and 3.

(3) Sub-subparagraph 2.1 iv A of section 1 of Schedule 4 to the Regulation is amended by striking out “Table” and substituting “Tables”.

(4) The Table to sub-subparagraph 2.1 iv A of section 1 of Schedule 4 to the Regulation is revoked and the following substituted:

table 1
Large unitary air conditioners

Column 1

Item

Column 2

Sub-type

Column 3

Heating type

Column 4

Cooling capacity

Column 5

EER

Column 6

IEER

Column 7

Compliance date

1.

Air-cooled

A

≥19 kW and <40 kW

11.2

11.4

January 1, 2013

2.

Air-cooled

A

≥40 kW and <70 kW

11.0

11.2

January 1, 2013

3.

Air-cooled

A

≥70 kW and <223 kW

10.0

10.1

January 1, 2013

4.

Air-cooled

A

≥223 kW

9.7

9.8

January 1, 2013

5.

Air-cooled

B

≥19 kW and <40 kW

11.0

11.2

January 1, 2013

6.

Air-cooled

B

≥40 kW and <70 kW

10.8

11.0

January 1, 2013

7.

Air-cooled

B

≥70 kW and <223 kW

9.8

9.9

January 1, 2013

8.

Air-cooled

B

≥223 kW

9.5

9.6

January 1, 2013

9.

Water-cooled, other than VRF multi-split

A

≥19 kW and <40 kW

12.1

11.7

July 1, 2013

10.

Water-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

11.0

11.2

January 1, 2013

11.

Water-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

12.5

11.2

July 1, 2014

12.

Water-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

11.0

11.1

January 1, 2013

13.

Water-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

12.4

11.1

July 1, 2014

14.

Water-cooled, other than VRF multi-split

A

≥223 kW

11.0

11.1

January 1, 2013

15.

Water-cooled, other than VRF multi-split

B

≥19 kW and <40 kW

11.9

11.5

July 1, 2013

16.

Water-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

11.0

11.0

July 1, 2013

17.

Water-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

12.3

11.0

July 1, 2014

18.

Water-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

10.8

10.9

January 1, 2013

19.

Water-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

12.2

10.9

July 1, 2014

20.

Water-cooled, other than VRF multi-split

B

≥223 kW

10.8

10.9

January 1, 2013

21.

Evaporation-cooled, other than VRF multi-split

A

≥19 kW and <40 kW

12.1

11.7

July 1, 2013

22.

Evaporation-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

11.0

11.2

January 1, 2013

23.

Evaporation-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

12.0

11.2

July 1, 2014

24.

Evaporation-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

11.0

11.1

January 1, 2013

25.

Evaporation-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

11.9

11.1

July 1, 2014

26.

Evaporation-cooled, other than VRF multi-split

A

≥223 kW

11.0

11.1

January 1, 2013

27.

Evaporation-cooled, other than VRF multi-split

B

≥19 kW and <40 kW

11.9

11.5

July 1, 2013

28.

Evaporation-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

11.0

11.0

July 1, 2013

29.

Evaporation-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

11.8

11.0

July 1, 2014

30.

Evaporation-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

10.8

10.9

January 1, 2013

31.

Evaporation-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

11.7

10.9

July 1, 2014

32.

Evaporation-cooled, other than VRF multi-split

B

≥223 kW

10.8

10.9

January 1, 2013

33.

Water- or evaporation-cooled, VRF multi-split

A

≥19 kW and <40 kW

11.5

11.7

January 1, 2013

34.

Water- or evaporation-cooled, VRF multi-split

A

≥40 kW and <70 kW

11.0

11.2

January 1, 2013

35.

Water- or evaporation-cooled, VRF multi-split

A

≥70 kW and <223 kW

11.0

11.1

January 1, 2013

36.

Water- or evaporation-cooled, VRF multi-split

A

≥223 kW

11.0

11.1

January 1, 2013

37.

Water- or evaporation-cooled, VRF multi-split

B

≥19 kW and <40 kW

11.3

11.5

January 1, 2013

38.

Water- or evaporation-cooled, VRF multi-split

B

≥40 kW and <70 kW

10.8

11.0

January 1, 2013

39.

Water- or evaporation-cooled, VRF multi-split

B

≥70 kW and <223 kW

10.8

10.9

January 1, 2013

40.

Water- or evaporation-cooled, VRF multi-split

B

≥223 kW

10.8

10.9

January 1, 2013

* Note:  For the purposes of Column 3, “A” means either no heating section or an electric heating section and “B” means a heating section other than an electric heating section. Variable refrigerant flow multi-split air conditioners or heat pumps with heat recovery fall under the category of “B” unless they also have electric resistance heating, in which case they fall under the category of “A”.

table 2
Large unitary heat pumps

Column 1

Item

Column 2

Sub-type

Column 3

Heating type

Column 4

Cooling capacity

Column 5

EER

Column 6

IEER

Column 7

COP at inlet air at 8.3C

Column 8

COP at inlet air at -8.3C

Column 9

Compliance date

1.

Air-cooled

A

≥19 kW and <40 kW

11.0

11.2

3.30

2.25

January 1, 2013

2.

Air-cooled

A

≥40 kW and <70 kW

10.6

10.7

3.20

2.05

January 1, 2013

3.

Air-cooled

A

≥70 kW and <223 kW

9.5

9.6

3.20

2.05

January 1, 2013

4.

Air-cooled

A

≥223 kW

9.5

9.6

3.20

2.05

January 1, 2013

5.

Air-cooled

B

≥19 kW and <40 kW

10.8

11.0

3.30

2.25

January 1, 2013

6.

Air-cooled

B

≥40 kW and <70 kW

10.4

10.5

3.20

2.05

January 1, 2013

7.

Air-cooled

B

≥70 kW and <223 kW

9.3

9.4

3.20

2.05

January 1, 2013

8.

Air-cooled

B

≥223 kW

9.3

9.4

3.20

2.05

January 1, 2013

9.

Water-cooled, other than VRF multi-split

A

≥19 kW and <40 kW

12.1

11.2

3.30

2.25

July 1, 2013

10.

Water-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

11.0

10.7

3.20

2.05

July 1, 2013

11.

Water-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

12.5

10.7

3.20

2.05

July 1, 2014

12.

Water-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

11.0

9.6

3.20

2.05

July 1, 2013

13.

Water-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

12.4

9.6

3.20

2.05

July 1, 2014

14.

Water-cooled, other than VRF multi-split

A

≥223 kW

9.5

9.6

3.20

2.05

January 1, 2013

15.

Water-cooled, other than VRF multi-split

B

≥19 kW and <40 kW

11.9

11.0

3.30

2.25

July 1, 2013

16.

Water-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

11.0

10.5

3.20

2.05

July 1, 2013

17.

Water-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

12.3

10.5

3.20

2.05

July 1, 2014

18.

Water-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

10.8

9.4

3.20

2.05

July 1, 2013

19.

Water-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

12.2

9.4

3.20

2.05

July 1, 2014

20.

Water-cooled, other than VRF multi-split

B

≥223 kW

9.3

9.4

3.20

2.05

January 1, 2013

21.

Evaporation-cooled, other than VRF multi-split

A

≥19 kW and <40 kW

12.1

11.2

3.30

2.25

July 1, 2013

22.

Evaporation-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

11.0

10.7

3.20

2.05

July 1, 2013

23.

Evaporation-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

12.0

10.7

3.20

2.05

July 1, 2014

24.

Evaporation-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

11.0

9.6

3.20

2.05

July 1, 2013

25.

Evaporation-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

11.9

9.6

3.20

2.05

July 1, 2014

26.

Evaporation-cooled, other than VRF multi-split

A

≥223 kW

9.5

9.6

3.20

2.05

January 1, 2013

27.

Evaporation-cooled, other than VRF multi-split

B

≥19 kW and <40 kW

11.9

11.0

3.30

2.25

July 1, 2013

28.

Evaporation-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

11.0

10.5

3.20

2.05

July 1, 2013

29.

Evaporation-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

11.8

10.5

3.20

2.05

July 1, 2014

30.

Evaporation-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

10.8

9.4

3.20

2.05

July 1, 2013

31.

Evaporation-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

11.7

9.4

3.20

2.05

July 1, 2014

32.

Evaporation-cooled, other than VRF multi-split

B

≥223 kW

9.3

9.4

3.20

2.05

January 1, 2013

33.

Water- or evaporation-cooled, VRF multi-split

A

≥19 kW and <40 kW

12.0

11.2

3.30

2.25

July 1, 2013

34.

Water- or evaporation-cooled, VRF multi-split

A

≥40 kW and <70 kW

10.6

10.7

3.20

2.05

January 1, 2013

35.

Water- or evaporation-cooled, VRF multi-split

A

≥70 kW and <223 kW

9.5

9.6

3.20

2.05

January 1, 2013

36.

Water- or evaporation-cooled, VRF multi-split

A

≥70 kW and <223 kW

10.0

9.6

3.20

2.05

October 29, 2013

37.

Water- or evaporation-cooled, VRF multi-split

A

≥223 kW

9.5

9.6

3.20

2.05

January 1, 2013

38.

Water- or evaporation-cooled, VRF multi-split

B

≥19 kW and <40 kW

12.0

11.0

3.30

2.25

July 1, 2013

39.

Water- or evaporation-cooled, VRF multi-split

B

≥40 kW and <70 kW

10.4

10.5

3.20

2.05

January 1, 2013

40.

Water- or evaporation-cooled, VRF multi-split

B

≥70 kW and <223 kW

9.3

9.4

3.20

2.05

January 1, 2013

41.

Water- or evaporation-cooled, VRF multi-split

B

≥70 kW and <223 kW

9.8

9.4

3.20

2.05

October 29, 2013

42.

Water- or evaporation-cooled, VRF multi-split

B

≥223 kW

9.3

9.4

3.20

2.05

January 1, 2013

43.

Evaporation-cooled, VRF multi-split

A

≥19 kW and <40 kW

11.0

11.2

3.30

2.25

January 1, 2013

44.

Evaporation-cooled, VRF multi-split

A

≥40 kW and <70 kW

10.6

10.7

3.20

2.05

January 1, 2013

45.

Evaporation-cooled, VRF multi-split

A

≥70 kW and <223 kW

9.5

9.6

3.20

2.05

January 1, 2013

46.

Evaporation-cooled, VRF multi-split

A

≥223 kW

9.5

9.6

3.20

2.05

January 1, 2013

47.

Evaporation-cooled, VRF multi-split

B

≥19 kW and <40 kW

10.8

11.0

3.30

2.25

January 1, 2013

48.

Evaporation-cooled, VRF multi-split

B

≥40 kW and <70 kW

10.4

10.5

3.20

2.05

January 1, 2013

49.

Evaporation-cooled, VRF multi-split

B

≥70 kW and <223 kW

9.3

9.4

3.20

2.05

January 1, 2013

50.

Evaporation-cooled, VRF multi-split

B

≥223 kW

9.3

9.4

3.20

2.05

January 1, 2013

* Note:  For the purposes of Column 3, “A” means either no heating section or an electric heating section and “B” means a heating section other than an electric heating section. Variable refrigerant flow multi-split air conditioners or heat pumps with heat recovery fall under the category of “B” unless they also have electric resistance heating, in which case they fall under the category of “A”.

table 3
large condensing units

Column 1

Item

Column 2

Sub-type

Column 3

Heating type

Column 4

Cooling capacity

Column 5

EER

Column 6

IEER

Column 7

COP at inlet air at 8.3C

Column 8

COP at inlet air at -8.3C

Column 9

Compliance date

1.

Air-cooled

A or B

≥19 kW and ≤70 kW

10.1

N/A

N/A

N/A 

January 1, 2013

2.

Water- or evaporation-cooled

A or B

≥19 kW and ≤70 kW

13.1

N/A

N/A

N/A

January 1, 2013

* Note:  For the purposes of Column 3, “A” means either no heating section or an electric heating section and “B” means a heating section other than an electric heating section. Variable refrigerant flow multi-split air conditioners or heat pumps with heat recovery fall under the category of “B” unless they also have electric resistance heating, in which case they fall under the category of “A”.

(5) Sub-subparagraph 2.2 iv C of section 1 of Schedule 4 to the Regulation is amended by striking out “Table” and substituting “Tables”.

(6) The Table to sub-subparagraph 2.2 iv C of section 1 of Schedule 4 to the Regulation is revoked and the following substituted:

table 1
Large unitary air conditioners

Column 1

Item

Column 2

Sub-type

Column 3

Heating type

Column 4

Cooling capacity

Column 5

EER

Column 6

IEER

1.

Air-cooled

A

≥19 kW and <40 kW

11.2

12.9

2.

Air-cooled

A

≥40 kW and <70 kW

11

12.4

3.

Air-cooled

A

≥70 kW and <223 kW

10.0

11.6

4.

Air-cooled

B

≥19 kW and <40 kW

11.0

12.7

5.

Air-cooled

B

≥40 kW and <70 kW

10.8

12.2

6.

Air-cooled

B

≥70 kW and <223 kW

9.8

11.4

7.

Water-cooled, other than VRF multi-split

A

≥19 kW and <40 kW

12.1

11.7

8.

Water-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

12.5

11.2

9.

Water-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

12.4

11.1

10.

Water-cooled, other than VRF multi-split

B

≥19 kW and <40 kW

11.9

11.5

11.

Water-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

12.3

11.0

12.

Water-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

12.2

10.9

13.

Evaporation-cooled, other than VRF multi-split

A

≥19 kW and <40 kW

12.1

11.7

14.

Evaporation-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

12.0

11.2

15.

Evaporation-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

11.9

11.1

16.

Evaporation-cooled, other than VRF multi-split

B

≥19 kW and <40 kW

11.9

11.5

17.

Evaporation-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

11.8

11.0

18.

Evaporation-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

11.7

10.9

19.

Water- or evaporation-cooled VRF multi-split

A

≥19 kW and <40 kW

11.5

11.7

20.

Water- or evaporation-cooled VRF multi-split

A

≥40 kW and <70 kW

11.0

11.2

21.

Water- or evaporation-cooled VRF multi-split

A

≥70 kW and <223 kW

11.0

11.1

22.

Water- or evaporation-cooled VRF multi-split

B

≥19 kW and <40 kW

11.3

11.5

23.

Water- or evaporation-cooled VRF multi-split

B

≥40 kW and <70 kW

10.8

11.0

24.

Water- or evaporation-cooled VRF multi-split

B

≥70 kW and <223 kW

10.8

10.9

* Note:  For the purposes of Column 3, “A” means either no heating section or an electric heating section and “B” means a heating section other than an electric heating section. Variable refrigerant flow multi-split air conditioners or heat pumps with heat recovery fall under the category of “B” unless they also have electric resistance heating, in which case they fall under the category of “A”.

table 2
Large unitary heat pumps

Column 1

Item

Column 2

Sub-type

Column 3

Heating type

Column 4

Cooling capacity

Column 5

EER

Column 6

IEER

Column 7

COP at inlet air at 8.3C

Column 8

COP at inlet air at -8.3C

1.

Air-cooled

A

≥19 kW and <40 kW

11.0

12.2

3.3

2.25

2.

Air-cooled

A

≥40 kW and <70 kW

10.6

11.6

3.2

2.05

3.

Air-cooled

A

≥70 kW and <223 kW

9.5

10.6

3.2

2.05

4.

Air-cooled

B

≥19 kW and <40 kW

10.8

12.0

3.3

2.25

5.

Air-cooled

B

≥40 kW and <70 kW

10.4

11.4

3.2

2.05

6.

Air-cooled

B

≥70 kW and <223 kW

9.3

10.4

3.2

2.05

7.

Water-cooled, other than VRF multi-split

A

≥19 kW and <40 kW

12.1

11.2

3.30

2.25

8.

Water-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

12.5

10.7

3.20

2.05

9.

Water-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

12.4

9.6

3.20

2.05

10.

Water-cooled, other than VRF multi-split

B

≥19 kW and <40 kW

11.9

11.0

3.30

2.25

11.

Water-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

12.3

10.5

3.20

2.05

12.

Water-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

12.2

9.4

3.20

2.05

13.

Evaporation-cooled, other than VRF multi-split

A

≥19 kW and <40 kW

12.1

11.2

3.30

2.25

14.

Evaporation-cooled, other than VRF multi-split

A

≥40 kW and <70 kW

12.0

10.7

3.20

2.05

15.

Evaporation-cooled, other than VRF multi-split

A

≥70 kW and <223 kW

11.9

9.6

3.20

2.05

16.

Evaporation-cooled, other than VRF multi-split

B

≥19 kW and <40 kW

11.9

11.0

3.30

2.25

17.

Evaporation-cooled, other than VRF multi-split

B

≥40 kW and <70 kW

11.8

10.5

3.20

2.05

18.

Evaporation-cooled, other than VRF multi-split

B

≥70 kW and <223 kW

11.7

9.4

3.20

2.05

19.

Water- or evaporation-cooled VRF multi-split

A

≥19 kW and <40 kW

12.0

11.2

3.30

2.25

20.

Water- or evaporation-cooled VRF multi-split

A

≥40 kW and <70 kW

10.6

10.7

3.20

2.05

21.

Water- or evaporation-cooled VRF multi-split

A

≥70 kW and <223 kW

10.0

9.6

3.20

2.05

22.

Water- or evaporation-cooled VRF multi-split

B

≥19 kW and <40 kW

12.0

11.0

3.30

2.25

23.

Water- or evaporation-cooled VRF multi-split

B

≥40 kW and <70 kW

10.4

10.5

3.20

2.05

24.

Water- or evaporation-cooled VRF multi-split

B

≥70 kW and <223 kW

9.8

9.4

3.20

2.05

* Note:  For the purposes of Column 3, “A” means either no heating section or an electric heating section and “B” means a heating section other than an electric heating section. Variable refrigerant flow multi-split air conditioners or heat pumps with heat recovery fall under the category of “B” unless they also have electric resistance heating, in which case they fall under the category of “A”.

5. Subparagraph 5 iv of section 1 of Schedule 6 to the Regulation is revoked and the following substituted:

iv. Prescribed efficiency standard or requirement is that set out in the following Tables:

table 1
dry-type transformer – single phase, voltage class = 1.2 KV

Column 1

Item

Column 2

kVA

Column 3

Efficiency at 0.35 of nameplate load (as percentage)

1.

15

97.70

2.

25

98.00

3.

37.5

98.20

4.

50

98.30

5.

75

98.50

6.

100

98.60

7.

167

98.70

8.

250

98.80

9.

333

98.90

 

table 2
Dry-Type Transformer – Single Phase, Voltage Class > 1.2 kV

Column 1

Item

Column 2

kVA

Column 3

BIL 20-45 kV, Efficiency at 0.5 of nameplate load (as percentage)

Column 4

BIL >45-95 kV, Efficiency at 0.5 of nameplate load (as percentage)

Column 5

BIL >95-199 kV, Efficiency at 0.5 of nameplate load (as percentage)

1.

15

98.1

97.86

97.60

2.

25

98.33

98.12

97.90

3.

37.5

98.49

98.30

98.10

4.

50

98.60

98.42

98.20

5.

75

98.73

98.57

98.53

6.

100

98.82

98.67

98.63

7.

167

98.96

98.83

98.80

8.

250

99.07

98.95

98.91

9.

333

99.14

99.03

98.99

10.

500

99.22

99.12

99.09

11.

667

99.27

99.18

99.15

12.

833

99.31

99.23

99.20

 

table 3
Dry-Type Transformer – Three Phase, Voltage Class = 1.2 kV

Column 1

Item

Column 2

kVA

Column 3

Efficiency at 0.35 of nameplate load (as percentage)

1.

15

97.89

2.

30

98.23

3.

45

98.40

4.

75

98.60

5.

112.5

98.74

6.

150

98.83

7.

225

98.94

8.

300

99.02

9.

500

99.14

10.

750

99.23

11.

1000

99.28

 

TABLE 4
Dry-Type Transformer – Three Phase, Voltage Class > 1.2 kV

Column 1

Item

Column 2

kVA

Column 3

BIL 20-45 kV, Efficiency at 0.5 of nameplate load (as percentage)

Column 4

BIL >45-95 kV, Efficiency at 0.5 of nameplate load (as percentage)

Column 5

BIL >95-199 kV, Efficiency at 0.5 of nameplate load (as percentage)

1.

15

97.50

97.18

96.80

2.

30

97.90

97.63

97.30

3.

45

98.10

97.86

97.60

4.

75

98.33

98.13

97.90

5.

112.5

98.52

98.36

98.10

6.

150

98.65

98.51

98.20

7.

225

98.82

98.69

98.57

8.

300

98.93

98.81

98.69

9.

500

99.09

98.99

98.89

10.

750

99.21

99.12

99.02

11.

1000

99.28

99.20

99.11

12.

1500

99.37

99.30

99.21

13.

2000

99.43

99.36

99.28

14.

2500

99.47

99.41

99.33

15.

3000

99.47

99.41

99.33

16.

3750

99.47

99.41

99.33

17.

5000

99.47

99.41

99.33

18.

7500

99.48

99.41

99.39

6. Subparagraph 7 i of section 1 of Schedule 7 to the Regulation is amended by striking out “June 13, 2018” and substituting “July 1, 2019”.

Commencement

7. This Regulation comes into force on the later of July 1, 2017 and the day it is filed.