Important: This version of the e-Laws website will be upgraded to a new version in the coming weeks.
You can try the beta version of the new e-Laws at ontario.ca/laws-beta.
O. Reg. 332/12: BUILDING CODE
under Building Code Act, 1992, S.O. 1992, c. 23
Skip to contentBuilding Code Act, 1992
Loi de 1992 sur le code du bâtiment
BUILDING CODE
Historical version for the period May 12, 2023 to December 13, 2023.
Last amendment: 89/23.
Legislative History: 151/13, 360/13, 361/13, 368/13, 191/14, 139/17, 462/17, 563/17, 79/18, 388/18, 87/19, 88/19, 209/20, 511/20, 762/20, 867/21, 217/22, 434/22 (as am. by 31/23), 451/22, 30/23, 89/23.
This Regulation is made in English only.
DIVISION A
COMPLIANCE, OBJECTIVES AND FUNCTIONAL STATEMENTs
Part 1
Compliance and General
Section |
1.1. |
Organization and Application |
|
1.1.1. |
Organization of this Code |
|
1.1.2. |
Application of Division B |
|
1.1.3. |
Building Size Determination |
|
|
|
Section |
1.2. |
Compliance |
|
1.2.1. |
Compliance with Division B |
|
1.2.2. |
Materials, Appliances, Systems and Equipment |
|
|
|
Section |
1.3. |
Interpretation |
|
1.3.1. |
Interpretation |
|
|
|
Section |
1.4. |
Terms and Abbreviations |
|
1.4.1. |
Definitions of Words and Phrases |
|
1.4.2. |
Symbols and Other Abbreviations |
|
|
|
Section |
1.5. |
Referenced Documents and Organizations |
|
1.5.1. |
Referenced Documents |
|
1.5.2. |
Organizations |
Section 1.1. Organization and Application
1.1.1. Organization of this Code
1.1.1.1. Scope of Division A
(1) Division A contains compliance and application provisions and the objectives and functional statements of this Code.
1.1.1.2. Scope of Division B
(1) Division B contains the acceptable solutions of this Code.
1.1.1.3. Scope of Division C
(1) Division C contains the administrative provisions of this Code.
1.1.1.4. Internal Cross-references
(1) If a provision of this Code contains a reference to another provision of this Code but no Division is specified, both provisions are in the same Division of this Code.
1.1.2. Application of Division B
1.1.2.1. Application of Parts 1, 7 and 12
(1) Part 1 of Division B applies to all buildings.
(2) Subject to Article 1.1.2.6., Parts 7 and 12 of Division B apply to all buildings.
1.1.2.2. Application of Parts 3, 4, 5 and 6
(1) Subject to Articles 1.1.2.6. and 1.3.1.2., Parts 3, 5 and 6 of Division B apply to all buildings,
(a) used for major occupancies classified as,
(i) Group A, assembly occupancies,
(ii) Group B, care, care and treatment or detention occupancies, or
(iii) Group F, Division 1, high hazard industrial occupancies,
(b) exceeding 600 m2 in building area or exceeding three storeys in building height and used for major occupancies classified as,
(i) Group C, residential occupancies,
(ii) Group D, business and personal services occupancies,
(iii) Group E, mercantile occupancies,
(iv) Group F, Divisions 2 and 3, medium hazard industrial occupancies and low hazard industrial occupancies, or
(c) used for retirement homes.
(2) Subject to Articles 1.1.2.6. and 1.3.1.2., Part 4 of Division B applies to,
(a) post-disaster buildings,
(b) buildings described in Sentence (1),
(c) a retaining wall exceeding 1 000 mm in exposed height adjacent to,
(i) public property,
(ii) access to a building, or
(iii) private property to which the public is admitted,
(d) a pedestrian bridge appurtenant to a building,
(e) a crane runway,
(f) an exterior storage tank and its supporting structure that is not regulated by the Technical Standards and Safety Act, 2000,
(g) signs regulated by Section 3.15. of Division B that are not structurally supported by a building,
(h) a structure that supports a wind turbine generator having a rated output of more than 3 kW,
(i) an outdoor pool that has a water depth greater than 3.5 m at any point, and
(j) a permanent solid nutrient storage facility with supporting walls exceeding 1 000 mm in exposed height.
(3) Section 3.11. of Division B applies to public pools.
(4) Section 3.12. of Division B applies to public spas.
(5) Section 3.15. of Division B applies to signs.
(6) Section 3.16A. of Division B applies to demountable stages and demountable support structures.
1.1.2.3. Application of Part 8
(1) Subject to Article 1.1.2.6., Part 8 of Division B applies to the design, construction, operation and maintenance of all sewage systems and to the construction of buildings in the vicinity of sewage systems.
1.1.2.4. Application of Part 9
(1) Subject to Article 1.1.2.6 Part 9 of Division B applies to all buildings,
(a) of three or fewer storeys in building height,
(b) having a building area not exceeding 600 m2, and
(c) used for major occupancies classified as,
(i) Group C, residential occupancies other than buildings used for retirement homes,
(ii) Group D, business and personal services occupancies,
(iii) Group E, mercantile occupancies, or
(iv) Group F, Divisions 2 and 3, medium hazard industrial occupancies and low hazard industrial occupancies.
1.1.2.5. Application of Part 10
(1) Part 10 of Division B applies to existing buildings requiring a permit under section 10 of the Act.
1.1.2.6. Application of Part 11
(1) Except as provided in Sentence (2), Part 11 of Division B applies to the design and construction of existing buildings, or parts of existing buildings, that have been in existence for at least five years.
(2) If a building has been in existence for at least five years but includes an addition that has been in existence for less than five years, Part 11 of Division B applies to the entire building.
1.1.2.7. Existing Buildings
(1) Except as provided in Section 3.17. of Division B, Section 9.40. of Division B and Part 11 of Division B, if an existing building is extended or is subject to material alteration or repair, this Code applies only to the design and construction of the extensions and those parts of the building that are subject to the material alteration or repair.
(2) If an existing previously occupied building is moved from its original location to be installed elsewhere, or is dismantled at its original location and moved to be reconstituted elsewhere, this Code applies only to changes to the design and construction of the building required as a result of moving the building.
1.1.3. Building Size Determination
1.1.3.1. Building Size Determination of Building Divided by Firewalls
(1) Where a firewall divides a building, each portion of the building that is divided shall be considered as a separate building, except for the purposes of,
(a) a determination of gross area in Section 1.2. of Division C,
(b) a fire alarm and detection system in Sentence 3.2.4.2.(1) of Division B or Article 9.10.18.1. of Division B, and
(c) a plumbing system interconnected through a firewall.
1.1.3.2. Building Size Determination of Building Divided by Vertical Fire Separations
(1) Except as permitted in Sentence (2), if portions of a building are completely separated by a vertical fire separation that has a fire-resistance rating of at least 1 h and that extends through all storeys and service spaces of the separate portions, each separated portion may be considered to be a separate building for the purpose of determining building height if,
(a) each separated portion is not more than three storeys in building height and is used only for residential occupancies other than a retirement home, and
(b) the unobstructed path of travel for a firefighter from the nearest street to one entrance to each separated portion is not more than 45 m.
(2) The vertical fire separation in Sentence (1) may terminate at the floor assembly immediately above a basement if the basement conforms to Article 3.2.1.2. of Division B.
Section 1.2. Compliance
1.2.1. Compliance with Division B
1.2.1.1 Compliance with Division B
(1) Compliance with Division B shall be achieved,
(a) by complying with the applicable acceptable solutions in Division B, or
(b) by using alternative solutions that will achieve the level of performance required by the applicable acceptable solutions in respect of the objectives and functional statements attributed to the applicable acceptable solutions in MMAH Supplementary Standard SA-1, “Objectives and Functional Statements Attributed to the Acceptable Solutions”.
(2) For the purposes of Clause (1)(b), the level of performance in respect of a functional statement refers to the performance of the functional statement as it relates to the objective with which it is associated in MMAH Supplementary Standard SA-1, “Objectives and Functional Statements Attributed to the Acceptable Solutions”.
1.2.2. Materials, Appliances, Systems and Equipment
1.2.2.1. Characteristics of Materials, Appliances, Systems and Equipment
(1) All materials, appliances, systems and equipment installed to meet the requirements of this Code shall possess the necessary characteristics to perform their intended functions when installed in a building.
1.2.2.2. Used Materials, Appliances and Equipment
(1) Unless otherwise specified, recycled materials in building products may be used and used materials, appliances and equipment may be reused when they meet the requirements of this Code for new materials and are satisfactory for their intended use.
Section 1.3. Interpretation
1.3.1. Interpretation
1.3.1.1. Designated Structures
(1) The following structures are designated for the purposes of clause (d) of the definition of building in subsection 1 (1) of the Act:
(a) a retaining wall exceeding 1 000 mm in exposed height adjacent to,
(i) public property,
(ii) access to a building, or
(iii) private property to which the public is admitted,
(b) a pedestrian bridge appurtenant to a building,
(c) a crane runway,
(d) an exterior storage tank and its supporting structure that is not regulated by the Technical Standards and Safety Act, 2000,
(e) signs regulated by Section 3.15. of Division B that are not structurally supported by a building,
(f) a solar collector that is mounted on a building and has a face area equal to or greater than 5 m²,
(g) a structure that supports a wind turbine generator having a rated output of more than 3 kW,
(h) a dish antenna that is mounted on a building and has a face area equal to or greater than 5 m²,
(i) an outdoor pool,
(j) an outdoor public spa,
(k) a permanent solid nutrient storage facility with supporting walls exceeding 1 000 mm in exposed height,
(l) a demountable stage, and
(m) a demountable support structure.
1.3.1.2. Farm Buildings
(1) Except as provided in Sentences (2) to (7), farm buildings shall conform to the requirements in the CCBFC NRCC 38732, “National Farm Building Code of Canada”.
(2) Articles 1.1.1.2. and 3.1.8.1. and Subsections 3.1.4. and 4.1.4. in the CCBFC NRCC 38732, “National Farm Building Code of Canada” do not apply to farm buildings.
(3) In the CCBFC NRCC 38732, “National Farm Building Code of Canada”, references in Articles 1.1.1.3., 2.2.2.1., 2.2.2.2., 2.3.1.1., 2.3.2.1., 3.1.1.1., 3.1.1.2., 3.1.2.1. and 3.1.6.1. to the CCBFC NRCC 38726, “National Building Code of Canada”, are deemed to be references to Ontario Regulation 403/97 (Building Code), as it read on December 30, 2006.
(4) A farm building of low human occupancy having a building area not exceeding 600 m2 and not more than three storeys in building height is deemed to comply with the structural requirements of the CCBFC NRCC 38732, “National Farm Building Code of Canada” if it is designed and constructed in conformance with MMAH Supplementary Standard SB-11, “Construction of Farm Buildings”.
(5) A liquid manure storage tank shall comply with the requirements of Part 4 of Division B of this Code and the requirements of Part 4 of the CCBFC NRCC 38732, “National Farm Building Code of Canada”.
(6) A permanent solid nutrient storage facility shall comply with the requirements of Part 4 of Division B of this Code.
(7) Where a floor area or portion of a floor area within a farm building is intended to contain a hazardous extraction operation involving cannabis, the floor area or portion of the floor area shall be designed and constructed to comply with,
(a) the requirements for locking, latching and other fastening devices for doors set out in Article 2.7.2.2. of Division B of the Fire Code made under the Fire Protection and Prevention Act, 1997,
(b) the ventilation requirements set out in Articles 4.1.7.2. to 4.1.7.6. of Division B of the Fire Code, where the hazardous extraction operation is intended to involve the use of flammable liquids or combustible liquids, and
(c) the ventilation requirements set out in Clauses 5.1.4.2.(1)(a) to (d) and (g) of Division B of the Fire Code, where the hazardous extraction operation is intended to involve the use of flammable gases.
Section 1.4. Terms and Abbreviations
1.4.1. Definitions of Words and Phrases
1.4.1.1. Non-defined Terms
(1) Definitions of words and phrases used in this Code that are not included in the list of definitions in Articles 1.4.1.2., 1.4.1.3. and 1.4.1.4. and are not defined in another provision of this Code shall have the meanings that are commonly assigned to them in the context in which they are used, taking into account the specialized use of terms by the various trades and professions to which the terminology applies.
1.4.1.2. Defined Terms
(1) Each of the words and terms in italics in this Code has,
(a) the same meaning as in subsection 1 (1) of the Act, if not defined in Clause (b) or (c),
(b) the same meaning as in each of the following provisions for the purposes described in the provision:
(i) Sentences 1.4.1.3.(1) and (2) of Division A, and
(ii) Sentences 3.13.1.2.(1), 5.10.4.1.(1), 7.1.3.1.(1), 8.1.1.2.(1) and 11.1.1.2.(1) of Division B, or
(c) the following meaning for the purposes of this Code:
Absorption trench means an excavation in soil, as defined in Part 8 of Division B, or in leaching bed fill, being part of a leaching bed, in which a distribution pipe or leaching chamber is laid that allows infiltration of the effluent into the soil, as defined in Part 8 of Division B, or leaching bed fill.
Acceptable solution means a requirement stated in Parts 3 to 12 of Division B.
Accessible means, when applied to a fixture, connection, plumbing appliance, valve, cleanout or equipment, to be accessible with or without having to first remove an access panel, door or similar obstruction, but a fixture, connection, plumbing appliance, valve, cleanout or equipment is not accessible if access can be gained only by cutting or breaking materials.
Access to exit means that part of a means of egress within a floor area that provides access to an exit serving the floor area.
Adaptable seating means a fixed seat or seats designed to facilitate a side transfer from a wheelchair.
Additional circuit vent means a vent pipe that is installed between a circuit vent and a relief vent to provide additional air circulation.
Adfreezing means the adhesion of soil to a foundation unit resulting from the freezing of soil water.
Air admittance valve means a one-way valve designed to allow air to enter the drainage system when the pressure in the plumbing system is less than the atmospheric pressure.
Air barrier system means an assembly installed to provide a continuous barrier to the movement of air.
Air break means the unobstructed vertical distance between the lowest point of an indirectly connected waste pipe and the flood level rim of the fixture into which it discharges.
Air-conditioning is the process of treating air in a space to control simultaneously its temperature, humidity, cleanliness, and distribution to meet the comfort requirements of the occupants of the space.
Air gap means the unobstructed vertical distance through air between the lowest point of a water supply outlet and the flood level rim of the fixture or device into which the outlet discharges.
Air-supported structure means a structure consisting of a pliable membrane that achieves and maintains its shape and support by internal air pressure.
Alarm signal means an audible signal transmitted throughout one or more zones of a building or throughout a building to advise occupants that a fire emergency exists.
Alert signal means an audible signal to advise designated persons of a fire emergency.
Allowable bearing pressure means the maximum pressure that may be safely applied to a soil or rock by the foundation unit considered in design under expected loading and subsurface conditions.
Allowable load means the maximum load that may be safely applied to a foundation unit considered in design under expected loading and subsurface conditions.
Alternative solution means a substitute for an acceptable solution.
Apparent sound transmission class means a single number rating of the airborne sound attenuation of building assemblies separating two adjoining spaces, taking into account both the direct and flanking sound transmission paths, and “ASTC” has a corresponding meaning.
Appliance means a device to convert fuel into energy and includes all components, controls, wiring and piping required to be part of the device by the applicable standard referred to in this Code.
Architect means the holder of a licence, a certificate of practice or a temporary licence under the Architects Act.
Area affected by a significant drinking water threat means an area described in Clause 1.10.2.3.(2)(b) of Division C.
Artesian groundwater means a confined body of water under pressure in the ground.
As constructed plans means construction plans and specifications that show the building and the location of the building on the property as the building has been constructed.
Assembly occupancy means the occupancy or the use of a building or part of a building by a gathering of persons for civic, political, travel, religious, social, educational, recreational or similar purposes or for the consumption of food or drink.
Attic or roof space means the space between the roof and the ceiling of the top storey or between a dwarf wall and a sloping roof.
Auxiliary water supply means, when applied to premises, any water supply on or available to the premises other than the primary potable water supply for the premises.
Backflow means a flowing back or reversal of the normal direction of the flow.
Backflow preventer means a device or a method that prevents backflow in a water distribution system.
Back-siphonage means backflow caused by a negative pressure in the supply system.
Back-siphonage preventer means a device or a method that prevents back-siphonage in a water distribution system.
Back vent means a pipe that is installed to vent a trap off the horizontal section of a fixture drain or the vertical leg of a water closet or other fixture that has an integral siphonic flushing action and “back vented” has a corresponding meaning.
Backwater valve means a check valve designed for use in a gravity drainage system.
Barrier-free means, when applied to a building and its facilities, that the building and its facilities can be approached, entered and used by persons with physical or sensory disabilities.
Basement means one or more storeys of a building located below the first storey.
Bathroom group means a group of plumbing fixtures installed in the same room, consisting of one domestic-type lavatory, one water closet and either one bathtub, with or without a shower, or one one-headed shower.
Bearing surface means the contact surface between a foundation unit and the soil or rock on which the foundation unit bears.
Boarding, lodging or rooming house means a building,
(a) that has a building height not exceeding three storeys and a building area not exceeding 600 m²,
(b) in which lodging is provided for more than four persons in return for remuneration or for the provision of services or for both, and
(c) in which the lodging rooms do not have both bathrooms and kitchen facilities for the exclusive use of individual occupants.
Boiler means an appliance intended to supply hot water or steam for space heating, processing or power purposes.
Bottle trap means a trap that retains water in a closed chamber and that seals the water by submerging the inlet pipe in the liquids or by a partition submerged in the liquids.
Branch means a soil or waste pipe that is connected at its upstream end to the junction of two or more soil or waste pipes or to a soil or waste stack and that is connected at its downstream end to another branch, a sump, a soil or waste stack or a building drain.
Branch vent means a vent pipe that is connected at its lower end to the junction of two or more vent pipes and that, at its upper end, is connected to another branch vent, a stack vent, a vent stack or a header, or terminates in open air.
Breeching means a flue pipe or chamber for receiving flue gases from one or more flue connections and for discharging these gases through a single flue connection.
Building area means the greatest horizontal area of a building above grade,
(a) within the outside surface of exterior walls, or
(b) within the outside surface of exterior walls and the centre line of firewalls.
Building Code website means the website at www.ontario.ca/buildingcode.
Building control valve means the valve on a water system that controls the flow of potable water from the water service pipe to the water distribution system.
Building drain means the lowest horizontal piping, including any vertical offset, that conducts sewage, clear water waste or storm water by gravity to a building sewer.
Building height means the number of storeys contained between the roof and the floor of the first storey.
Building sewer means a sanitary building sewer or storm building sewer.
Building trap means a trap that is installed in a sanitary building drain or sanitary building sewer to prevent circulation of air between the sanitary drainage system and a public sewer.
Business and personal services occupancy means the occupancy or use of a building or part of a building for the transaction of business or the provision of professional or personal services.
Camp for housing of workers means a camp in which buildings or other structures or premises are used to accommodate five or more employees.
Campground means land or premises used as an overnight camping facility that is not a recreational camp.
Canopy means a roof-like structure projecting more than 300 mm from the exterior face of the building.
Carbon dioxide equivalent means a measure used to compare the impact of various greenhouse gases based on their global warming potential.
Care and treatment occupancy (Group B, Division 2) means an occupancy in which persons receive special care and treatment.
Care occupancy (Group B, Division 3) means an occupancy, other than a retirement home, in which special care is provided by a facility, directly through its staff or indirectly through another provider, to residents of the facility,
(a) who require special care because of cognitive or physical limitations, and
(b) who, as a result of those limitations, would be incapable of evacuating the occupancy, if necessary, without the assistance of another person.
Cavity wall means a construction of masonry units laid with a cavity between the wythes, where the wythes are tied together with metal ties or bonding units and are relied on to act together in resisting lateral loads.
Certificate for the occupancy of a building described in Sentence 1.3.3.4.(3) of Division C means a certificate described in Sentence 3.7.4.3.(6) of Division C.
Certificate for the occupancy of a building described in Sentence 1.3.3.5.(1) of Division C means a certificate described in Sentence 3.7.4.3.(7) of Division C.
Certificate for the occupancy of a building not fully completed means a certificate described in Sentence 3.7.4.3.(5) of Division C.
Chamber means a structure in a shallow buried trench that is constructed with an open bottom and that contains a pressurized distribution pipe.
Check valve means a valve that permits flow in only one direction and prevents a return flow.
Child care centre means a child care centre as defined in subsection 2 (1) of the Child Care and Early Years Act, 2014.
Chimney means a shaft that is primarily vertical and that encloses at least one flue for conducting flue gases to the outdoors.
Chimney liner means a conduit containing a chimney flue used as a lining of a masonry or concrete chimney.
Circuit vent means a vent pipe that serves a number of fixtures and connects to the fixture drain of the most upstream fixture, and “circuit vented” has a corresponding meaning.
Class 1 fire sprinkler/standpipe system means an assembly of pipes and fittings that conveys water from the water service pipe or fire service main to the sprinkler/standpipe system’s outlets, is directly connected to the public water supply main only, has no pumps or reservoirs and in which the sprinkler drains discharge to the atmosphere, to dry wells or to other safe outlets.
Class 2 fire sprinkler/standpipe system means a Class 1 fire sprinkler/standpipe system that includes a booster pump in its connection to the public water supply main.
Class 3 fire sprinkler/standpipe system means an assembly of pipes and fittings that conveys potable water from the water service pipe or fire service main to the sprinkler/standpipe system’s outlets and that is directly connected to the public water supply main and to one or more of the following storage facilities, which are filled from the public water supply main only: elevated water storage, fire pumps supplying water from aboveground covered reservoirs or pressure tanks.
Class 4 fire sprinkler/standpipe system means an assembly of pipes and fittings that conveys water from the water service pipe or fire service main to the sprinkler/standpipe system’s outlets and is directly connected to the public water supply main (similar to Class 1 and Class 2 fire sprinkler/standpipe systems) and to an auxiliary water supply dedicated to fire department use that is located within 520 m of a pumper connection.
Class 5 fire sprinkler/standpipe system means an assembly of pipes and fittings that conveys water from the water service pipe or fire service main to the sprinkler/standpipe system’s outlets, is directly connected to the public water supply main and is interconnected with an auxiliary water supply.
Class 6 fire sprinkler/standpipe system means an assembly of pipes and fittings that conveys water from the water service pipe or fire service main to the sprinkler/standpipe system’s outlets and acts as a combined industrial water supply and fire protection system that is supplied from the public water supply main only, with or without gravity storage or pump suction tanks.
Cleanout means a fitting access in a drainage system or venting system that is installed to provide access for cleaning and inspection and that is provided with a readily replaceable air tight cover.
Clean water means water that has passed through a recirculation system.
Clear water waste means waste water containing no impurities or contaminants that are harmful to a person’s health, plant or animal life or that impair the quality of the natural environment.
Closed container means a container so sealed by means of a lid or other device that neither liquid nor vapour will escape from it at ordinary temperatures.
Closure means a device or assembly for closing an opening through a fire separation or an exterior wall, such as a door, a shutter, a damper, wired glass and glass block, and includes all components such as hardware, closing devices, frames and anchors.
Combustible means that a material fails to meet the acceptance criteria of CAN/ULC-S114, “Test for Determination of Non-Combustibility in Building Materials”.
Combustible construction means a type of construction that does not meet the requirements for noncombustible construction or encapsulated mass timber construction.
Combustible fibres means finely divided combustible vegetable or animal fibres and thin sheets or flakes of such materials which, in a loose, unbaled condition, present a flash fire hazard, and includes cotton, wool, hemp, sisal, jute, kapok, paper and cloth.
Combustible liquid means any liquid having a flash point at or above 37.8°C and below 93.3°C.
Compliance alternative means a substitute for a requirement in another Part of Division B that is listed in Part 10 or 11 of Division B, and “C.A.” has a corresponding meaning.
Compressed gas means,
(a) any contained mixture or material having a vapour pressure exceeding one or both of the following,
(i) 275.8 kPa (absolute) at 21°C, or
(ii) 717 kPa (absolute) at 54°C, or
(b) any liquid having a vapour pressure exceeding 275.8 kPa (absolute) at 37.8°C.
Computer room means a room,
(a) that contains electronic computer or data processing equipment such as main frame type,
(b) that is separated from the remainder of the building for the purpose of controlling the air quality in the room by a self-contained climate control system, and
(c) that has an occupant load of not more than one person for each 40 m² of the room.
Conditioned space means space within a building in which the temperature is controlled to limit variation in response to the exterior ambient temperature or interior differential temperatures by the provision, either directly or indirectly, of heating or cooling over substantial portions of the year.
Construction index means a level on a scale of 1 to 8 determined in accordance with Table 11.2.1.1.A. of Division B designating the expected performance level of the building structure with respect to the type of construction and fire protection of an existing building, and “C.I.” has a corresponding meaning.
Contained use area means a supervised area containing one or more rooms in which occupant movement is restricted to a single room by security measures not under the control of the occupant.
Continuous vent means a vent pipe that is an extension of a vertical section of a branch or fixture drain.
Cooktop means a cooking surface having one or more burners or heating elements.
Critical level means the level of submergence at which a back-siphonage preventer ceases to prevent back-siphonage.
Dangerous goods means those products or substances that are,
(a) regulated by the Transportation of Dangerous Goods Regulations made under the Transportation of Dangerous Goods Act, 1992 (Canada), or
(b) classified as controlled products under the Hazardous Products Regulations made under the Hazardous Products Act (Canada).
Day camp means a camp or resort that admits persons for a continuous period not exceeding 24 hours.
Dead end means a pipe that terminates with a closed fitting.
Dead load means the weight of all permanent structural and nonstructural components of a building.
Deep foundation means a foundation unit that provides support for a building by transferring loads either by end-bearing to a soil or rock at considerable depth below the building or by adhesion or friction, or both, in the soil or rock in which it is placed. Piles are the most common type of deep foundation.
Demountable stage means a structure that,
(a) consists of one or more platforms together with any wall, roof or other structures attached to or located on any of the platforms,
(b) is intended to be used for public or private performances or events, other than performances or events associated with movie or television productions,
(c) is intended to be erected, assembled or installed for a limited specified time,
(d) is capable of being dismantled at its location and moved to be reconstituted elsewhere or is erected for one-time use,
(e) is not located inside a fully enclosed building,
(f) is primarily for use by performers and workers, and
(g) may or may not be mounted on wheels.
Demountable support structure means any structure that,
(a) is capable of supporting banners, stage sets, props, sound equipment, lighting equipment or other equipment,
(b) is intended to be used for public or private performances or events, other than performances or events associated with movie or television productions,
(c) is intended to be erected, assembled or installed for a limited specified time,
(d) is capable of being dismantled at its location and moved to be reconstituted elsewhere or is erected for one-time use,
(e) is not attached to or located on a demountable stage,
(f) is not located inside a fully enclosed building,
(g) is primarily for use by performers and workers, and
(h) may or may not be mounted on wheels.
Design activities means the activities described in subsection 15.11 (5) of the Act.
Design bearing pressure means the pressure applied by a foundation unit to soil or rock, which pressure is not greater than the allowable bearing pressure.
Design capacity means, in the definition of sewage system, the total daily design sanitary sewage flow determined in accordance with Article 8.2.1.3. of Division B.
Designer means the person responsible for the design.
Design load means the load applied to a foundation unit, which load is not greater than the allowable load.
Detention occupancy (Group B, Division 1) means an occupancy in which persons are under restraint or are incapable of self preservation because of security measures not under their control.
Developed length means, when applied to a pipe and fittings, the length along the centre line of the pipe and fittings.
Directly connected means physically connected in such a way that neither water nor gas can escape from the connection.
Distilled beverage alcohol means a beverage that is produced by fermentation and contains more than 20% by volume of water-miscible alcohol.
Distillery means a process plant where distilled beverage alcohols are produced, concentrated or otherwise processed, and includes facilities on the same site where the concentrated products may be blended, mixed, stored or packaged.
Distributing pipe means a pipe or piping in a water distribution system.
Distribution box means a device for ensuring that effluent from a treatment unit is distributed in equal amounts to each line of distribution pipe or leaching chamber in a leaching bed.
Distribution pipe means a line or lines of perforated or open jointed pipe or tile installed in a leaching bed for the purpose of distributing effluent from a treatment unit to the soil, as defined in Part 8 of Division B, or leaching bed fill in the leaching bed.
Diving board means a flexible board.
Diving platform means a rigid platform that is not a starting platform.
Drainage system means an assembly of pipes, fittings, fixtures and appurtenances on a property that is used to convey sewage and clear water waste to a main sewer or a private sewage disposal system, and includes a private sewer, but does not include subsoil drainage piping.
Drinking water system has the same meaning as in subsection 2 (1) of the Safe Drinking Water Act, 2002.
Drum trap means a trap whose inlet and outlet are in the sides of the cylindrical body of the trap.
Dual vent means a vent pipe that serves two fixtures and connects at the junction of the trap arms.
Dwelling unit means a suite operated as a housekeeping unit, used or intended to be used by one or more persons and usually containing cooking, eating, living, sleeping and sanitary facilities.
Earth pit privy means a latrine consisting of an excavation in the ground surmounted by a superstructure.
Effluent means sanitary sewage that has passed through a treatment unit.
Electric space heating means an electric energy source that provides more than 10 per cent of the heating capacity provided for a building and includes,
(a) electric resistance unitary baseboard heating,
(b) electric resistance unitary cabinet heating,
(c) electric resistance ceiling cable or floor cable heating,
(d) electric resistance central furnace heating,
(e) electric hot water space heating, and
(f) air source heat pumps in combination with electric resistance backup heating.
Encapsulated mass timber construction means a type of construction in which a degree of fire safety is attained by the use of encapsulated mass timber elements with an encapsulation rating and minimum dimensions for structural members and other building assemblies.
Encapsulation rating means the time in minutes that a material or assembly of materials will delay the ignition and combustion of encapsulated mass timber elements when it is exposed to fire under specified conditions of test and performance criteria, or as otherwise prescribed by this Code.
Excavation means the space created by the removal of soil, rock or fill for the purposes of construction.
Exhaust duct means a duct through which air is conveyed from a room or space to the outdoors.
Exit means that part of a means of egress, including doorways, that leads from the floor area it serves to a separate building, an open public thoroughfare or an exterior open space protected from fire exposure from the building and having access to an open public thoroughfare.
Exit level means the level of an exit stairway in a building at which an exterior exit door or exit passageway leads to the exterior.
Exit storey means a storey having an exterior exit door in a building governed by Subsection 3.2.6. of Division B.
Exposing building face means that part of the exterior wall of a building that faces one direction and is located between ground level and the ceiling of its top storey or, where the building is divided into fire compartments, the exterior wall of a fire compartment that faces one direction.
Exterior cladding means those components of a building that are exposed to the outdoor environment and are intended to provide protection against wind, water or vapour.
Factory-built chimney means a chimney consisting entirely of factory-made parts, each designed to be assembled with the other without requiring fabrication on site.
Farm building means all or part of a building,
(a) that does not contain any area used for residential occupancy,
(b) that is associated with and located on land devoted to the practice of farming, and
(c) that is used essentially for the housing of equipment or livestock or the production, storage or processing of agricultural and horticultural produce or feeds.
Fill means soil, rock, rubble, industrial waste such as slag, organic material or a combination of these that is transported and placed on the natural surface of a soil or rock or organic terrain; it may or may not be compacted.
Fire block means a material, component or system that restricts the spread of fire within a concealed space or from a concealed space to an adjacent space.
Fire compartment means an enclosed space in a building that is separated from all other parts of the building by enclosing construction providing a fire separation having a required fire-resistance rating.
Fire damper means a closure that consists of a normally held open damper installed in an air distribution system or in a wall or floor assembly and designed to close automatically in the event of a fire in order to maintain the integrity of the fire separation.
Fire detector means a device that detects a fire condition and automatically initiates an electrical signal to actuate an alert signal or alarm signal and includes heat detectors and smoke detectors.
Fire load means, when applied to occupancy, the combustible contents of a room or floor area expressed in terms of the average weight of combustible materials per unit area, from which the potential heat liberation may be calculated based on the calorific value of the materials, and includes the furnishings, finished floor, wall and ceiling finishes, trim and temporary and movable partitions.
Fire-protection rating means the time in minutes or hours that a closure will withstand the passage of flame when exposed to fire under specified conditions of test and performance criteria, or as otherwise prescribed in this Code.
Fire-resistance rating means the time in minutes or hours that a material or assembly of materials will withstand the passage of flame and the transmission of heat when exposed to fire under specified conditions of test and performance criteria, or as determined by extension or interpretation of information derived from that test and performance as prescribed in this Code.
Fire-retardant treated wood means wood or a wood product that has been impregnated with fire-retardant chemicals to reduce its surface-burning characteristics such as flame spread, rate of fuel contribution and the density of smoke developed.
Fire separation means a construction assembly that acts as a barrier against the spread of fire.
Fire service main means a pipe and its appurtenances that are connected to a source of water and that are located on a property,
(a) between the source of water and the base of the riser of a water-based fire protection system,
(b) between the source of water and inlets to foam making systems,
(c) between the source of water and the base elbow of private hydrants or monitor nozzles,
(d) as fire pump suction and discharge piping not within a building, or
(e) beginning at the inlet side of the check valve on a gravity or pressure tank.
Fire stop means a system consisting of a material, component and means of support, used to fill gaps between fire separations or between fire separations and other assemblies, or used around items that wholly or partially penetrate a fire separation.
Fire stop flap means a device,
(a) that is intended for use in horizontal assemblies that are required to have a fire-resistance rating and incorporate protective ceiling membranes, and
(b) that operates to close off a duct opening through the membrane in the event of a fire.
Firewall means a type of fire separation of noncombustible construction that subdivides a building or separates adjoining buildings to resist the spread of fire and that has a fire-resistance rating as prescribed in this Code and the structural stability to remain intact under fire conditions for the required fire-rated time.
First storey means the storey that has its floor closest to grade and its ceiling more than 1.8 m above grade.
Fixture means a receptacle, plumbing appliance, apparatus or other device that discharges sewage or clear water waste, and includes a floor drain.
Fixture drain means the pipe that connects a trap serving a fixture to another part of a drainage system.
Fixture outlet pipe means a pipe that connects the waste opening of a fixture to the trap serving the fixture.
Fixture unit means, when applied to a drainage system, the unit of measure based on the rate of discharge, time of operation and frequency of use of a fixture that expresses the hydraulic load that is imposed by that fixture on the drainage system.
Fixture unit means, when applied to a water distribution system, the unit of measure based on the rate of supply, time of operation and frequency of use of a fixture or outlet that expresses the hydraulic load that is imposed by that fixture or outlet on the supply system.
Flame-spread rating means an index or classification indicating the extent of the spread of flame on the surface of a material or an assembly of materials, as determined in a standard fire test prescribed in this Code.
Flammable liquid means any liquid having a flash point below 37.8°C and having a vapour pressure not more than 275.8 kPa (absolute) at 37.8°C as determined by ASTM D323, “Vapor Pressure of Petroleum Products (Reid Method)”.
Flash point means the minimum temperature at which a liquid within a container gives off vapour in sufficient concentration to form an ignitable mixture with air near the surface of the liquid.
Flight means a series of steps between landings.
Flood level rim means the top edge at which water can overflow from a fixture or device.
Floor area means the space on any storey of a building between exterior walls and required firewalls, including the space occupied by interior walls and partitions, but not including exits, vertical service spaces and their enclosing assemblies.
Flow control roof drain means a roof drain that restricts the flow of storm water into the storm drainage system.
Flue means an enclosed passageway for conveying flue gases.
Flue collar means the portion of a fuel-fired appliance designed for the attachment of the flue pipe or breeching.
Flue pipe means the pipe connecting the flue collar of an appliance to a chimney.
Food premises means a floor area where food or drink for human consumption, or an ingredient of food or drink for human consumption, is manufactured, processed, prepared, stored, displayed, handled, served, distributed, sold or offered for sale, but does not include,
(a) a private residence,
(b) a boarding house that provides meals for fewer than 10 boarders,
(c) a building to which Ontario Regulation 502/17 (Camps in Unorganized Territory) or Ontario Regulation 503/17 (Recreational Camps) made under the Health Protection and Promotion Act applies,
(d) a plant, as defined in the Milk Act, that is required to be operated under the authority of a licence issued under that Act,
(e) premises where a licensed activity, as defined in the Food Safety and Quality Act, 2001, is carried on by a person who is required to hold a licence issued under that Act,
(f) an egg-grading station or an egg-processing station, as defined in subsection 1 (1) of Ontario Regulation 171/10 (Eggs and Processed Egg), made under the Food Safety and Quality Act, 2001,
(g) a floor area occupied by a church, service club or fraternal organization for the purpose of,
(i) preparing meals for special events for its members and personally invited guests, or
(ii) conducting bake sales, or
(h) a farm building.
Forced-air furnace means a furnace equipped with a fan that provides the primary means for the circulation of air.
Force main means a sanitary drainage pipe through which sanitary sewage is conveyed by mechanical or pneumatic propulsion.
Foundation means a system or arrangement of foundation units through which the loads from a building are transferred to supporting soil or rock.
Foundation unit means one of the structural members of the foundation of a building, such as a footing, raft and pile.
Fresh air inlet means a vent pipe that is installed in conjunction with a building trap and terminates in open air.
Frost action means the phenomenon that occurs when,
(a) water in soil is subjected to freezing which, because of the water ice phase change or ice lens growth, results in a total volume increase or the build-up of expansive forces under confined conditions or both, and
(b) the subsequent thawing leads to loss of soil strength and increased compressibility.
Functional statement means a function set out in Table 3.2.1.1. that a building or an element of a building is intended to perform.
Furnace means a space-heating appliance that uses warm air as the heating medium and usually provides for the attachment of ducts.
Gaming premises means premises that are a gaming site as defined in the Ontario Lottery and Gaming Corporation Act, 1999.
Gas vent means that portion of a venting system designed to convey vent gases to the outdoors,
(a) from the vent connector of a gas-fired appliance, or
(b) directly from the appliance when a vent connector is not used.
Grade means the average level of proposed or finished ground adjoining a building at all exterior walls.
Graded lumber means lumber that has been graded and stamped to indicate its grade, as determined by the NLGA, “Standard Grading Rules for Canadian Lumber”.
Greywater means sanitary sewage of domestic origin that is derived from fixtures other than sanitary units.
Gross area means the total area of all floors above grade measured between the outside surfaces of exterior walls or between the outside surfaces of exterior walls and the centre line of firewalls, except that, in any occupancy other than a residential occupancy, where an access or a building service penetrates a firewall, measurements shall not be taken to the centre line of such firewall.
Ground water means, when applied to a sewage system, water below the surface of the ground that occupies a zone of the earth’s mantle that is saturated with water.
Ground water table means, when applied to a sewage system, the elevation of the upper surface of the ground water existing in the area of the sewage system.
Groundwater means a free standing body of water in the ground.
Groundwater level means the top surface of groundwater.
Guard means a protective barrier, with or without openings through it, that is around openings in floors or at the open sides of stairs, landings, balconies, mezzanines, galleries, raised walkways or other locations to prevent accidental falls from one level to another.
Hauled sewage means sanitary sewage that,
(a) is not finally disposed of at the site where it is produced and is not conveyed by a sewer to sewage works, and
(b) is stored or retained at the site where it is produced for periodic collection, handling, treatment, transportation, storage or processing prior to final disposal at a place other than where it was produced,
and includes sanitary sewage that is removed from a sewage system for the purpose of cleaning or maintaining the system.
Hauled sewage system means works, installations, equipment, operations and land used in connection with the collection, handling, treatment, transportation, storage, processing and disposal of hauled sewage, as regulated under the Environmental Protection Act.
Hazard index means a level on a scale of 1 to 8 determined in accordance with Tables 11.2.1.1.B. to 11.2.1.1.N. of Division B, designating the life safety hazard to occupants of a building based on,
(a) use and occupancy,
(b) occupant load,
(c) the use and function of floor spaces,
(d) the difficulty of egress,
(e) the fire load of contents, finishes and furnishings,
(f) the configuration or compartmentation of floor spaces, and
(g) the size of the building,
and “H.I.” has a corresponding meaning.
Hazardous classroom means a classroom,
(a) that is supplied with flammable gas,
(b) that contains hazardous substances such as chemicals or explosive dusts,
(c) that contains large quantities of combustible materials, or
(d) where cooking equipment is used.
Hazardous extraction means a process to remove or separate a substance from a solution or mixture that involves the use of flammable liquids, combustible liquids or flammable gases as solvents in the process.
Hazardous room means a room containing sufficient quantities of a substance that, because of its chemical nature, may create an atmosphere or condition of imminent hazard to health.
Header means a vent pipe that connects two or more vent stacks or stack vents to open air.
Header line means a line of pipe with watertight joints installed in a sewage system for the purpose of distributing effluent from a treatment unit to the distribution pipe in a leaching bed.
Heat detector means a fire detector designed to operate at a predetermined temperature or rate of temperature rise.
Heavy timber construction means that type of combustible construction in which a degree of fire safety is attained,
(a) by placing limitations on the sizes of wood structural members and on the thickness and composition of wood floors and roofs, and
(b) by the avoidance of concealed spaces under floors and roofs.
Heritage building means a building,
(a) that is designated under the Ontario Heritage Act, or
(b) that is certified to be of significant architectural or historical value by a recognized, non-profit public organization whose primary object is the preservation of structures of architectural or historical significance and the certification has been accepted by the chief building official.
High ground water table means the highest elevation at which there is physical evidence that the soil, as defined in Part 8 of Division B, or the leaching bed fill has been saturated with water.
High hazard industrial occupancy (Group F, Division 1) means an industrial occupancy containing sufficient quantities of highly combustible and flammable or explosive materials to constitute a special fire hazard because of their inherent characteristics.
Holding tank means a tank designed to totally retain all sanitary sewage discharged into it and requiring periodic emptying.
Home for special care means a home for the care of persons requiring nursing, residential or sheltered care.
Horizontal branch means that part of a waste pipe that is horizontal and installed to convey the discharge from more than one fixture.
Horizontal exit means an exit from one building to another by means of a doorway, vestibule, walkway, bridge or balcony.
Horizontal service space means a space such as an attic, duct, ceiling, roof or crawl space,
(a) that is oriented essentially in a horizontal plane,
(b) that is concealed and generally inaccessible, and
(c) through which building service facilities such as pipes, ducts and wiring may pass.
Hotel means floor areas, a floor area or part of a floor area that contains four or more suites and that provides sleeping accommodation for the travelling public or for recreational purposes.
House means a detached house, semi-detached house or row house containing not more than two dwelling units.
Hub drain means a drain opening for indirect liquid wastes,
(a) that does not serve as a floor drain,
(b) that has the same pipe size, material and venting requirements as a floor drain,
(c) that has a flood level rim above the floor in which it is installed, and
(d) that receives wastes that are discharged directly into the drain opening.
Impeded egress zone means a supervised area in which occupants have free movement but require the release, by security personnel, of security doors at the boundary before being able to leave the area, but does not include a contained use area.
Indirectly connected means not directly connected.
Indirect service water heater means a service water heater that derives its heat from a heating medium such as warm air, steam or hot water.
Individual vent means a vent pipe that serves one fixture.
Indoor pool means a public pool where the pool and pool deck are totally or partially covered by a roof.
Industrial occupancy means the occupancy or use of a building or part of a building for the assembling, fabricating, manufacturing, processing, repairing or storing of goods or materials.
Interceptor means a receptacle that is designed and installed to prevent oil, grease, sand or other materials from passing into a drainage system.
Interconnected floor space means superimposed floor areas or parts of floor areas in which floor assemblies that are required to be fire separations are penetrated by openings that are not provided with closures.
Lake Simcoe shoreline has the same meaning as in the Lake Simcoe Protection Plan established under the Lake Simcoe Protection Act, 2008 and dated July, 2009.
Lake Simcoe watershed has the same meaning as in section 2 of the Lake Simcoe Protection Act, 2008.
Leaching means dispersal of liquid by downward or lateral drainage or both into permeable soil, as defined in Part 8 of Division B, or leaching bed fill.
Leaching bed means an absorption system constructed as absorption trenches or as a filter bed, located wholly in ground or raised or partly raised above ground, as required by local conditions, to which effluent from a treatment unit is applied for treatment and disposal and that is composed of,
(a) the soil, as defined in Part 8 of Division B, leaching bed fill or other filter media that is contained between the surface on which the sanitary sewage is applied and the bottom of the bed,
(b) the leaching chamber or the distribution pipe and the stone or gravel layer in which the distribution pipe is located, and
(c) the backfill above the distribution pipe or the leaching chamber, including the topsoil and sodding or other anti-erosion measure, and the side slopes of any portion elevated above the natural ground elevation.
Leaching bed fill means unconsolidated material suitable for the construction of a leaching bed, placed in the area of the leaching bed in order to obtain the required unsaturated zone below the distribution pipes or leaching chambers and the required lateral extent such that the effluent is absorbed.
Leaching chamber means a formed structure with an open bottom and permeable sidewalls installed in a leaching bed for the purpose of distributing effluent from a treatment unit to the soil, as defined in Part 8 of Division B, or leaching bed fill in the leaching bed.
Leader means a pipe that is installed to carry storm water from a roof to a storm building drain, sewer or other place of disposal.
Limiting distance means the distance from an exposing building face to a property line, to the centre line of a street, lane or public thoroughfare or to an imaginary line between two buildings or fire compartments on the same property, measured at right angles to the exposing building face.
Listed means equipment or materials included in a list published by a certification organization accredited by the Standards Council of Canada.
Liquid manure means manure having a dry matter content of less than 18 per cent or a slump of more than 150 millimetres using the Test Method for the Determination of Liquid Waste (slump test) set out in Schedule 9 to Regulation 347 of the Revised Regulations of Ontario, 1990 (General — Waste Management) made under the Environmental Protection Act.
Live load means a variable load due to the intended use and occupancy that is to be assumed in the design of the structural members of a building and includes loads due to cranes and the pressure of liquids in containers.
Live/work unit means a dwelling unit having an area of not more than 200 m2 that contains a subsidiary business and personal services occupancy or a subsidiary low hazard industrial occupancy, and which is used and operated by one or more persons of a single household.
Loadbearing means, when applied to a building element, subjected to or designed to carry loads in addition to its own dead load, but does not include a wall element subject only to wind or earthquake loads in addition to its own dead load.
Loading rate means the volume in litres of effluent per square metre applied in a single day to soil, as defined in Part 8 of Division B, or leaching bed fill.
Low hazard industrial occupancy (Group F, Division 3) means an industrial occupancy in which the combustible content is not more than 50 kg/m² or 1200 MJ/m² of floor area.
Low human occupancy means, when applied to a farm building, an occupancy in which the occupant load is not more than one person per 40 m² of floor area during normal use.
Major occupancy means the principal occupancy for which a building or part of a building is used or intended to be used, and is deemed to include the subsidiary occupancies that are an integral part of the principal occupancy. The major occupancy classifications used in this Code are as follows:
(a) Group A, Division 1 - Assembly occupancies intended for the production and viewing of the performing arts,
(b) Group A, Division 2 - Assembly occupancies not elsewhere classified in Group A,
(c) Group A, Division 3 - Assembly occupancies of the arena type,
(d) Group A, Division 4 - Assembly occupancies in which occupants are gathered in the open air,
(e) Group B, Division 1 - Detention occupancies,
(f) Group B, Division 2 - Care and treatment occupancies,
(g) Group B, Division 3 - Care occupancies,
(h) Group C - Residential occupancies,
(i) Group D - Business and personal services occupancies,
(j) Group E - Mercantile occupancies,
(k) Group F, Division 1 - High hazard industrial occupancies,
(l) Group F, Division 2 - Medium hazard industrial occupancies, and
(m) Group F, Division 3 - Low hazard industrial occupancies.
Make-up water means water added to a public pool from an external source.
Marquee means a canopy over an entrance to a building.
Masonry or concrete chimney means a chimney of brick, stone, concrete or masonry units constructed on site.
Means of egress includes exits and access to exits and means a continuous path of travel provided for the escape of persons from any point in a building or in a contained open space to,
(a) a separate building,
(b) an open public thoroughfare, or
(c) an exterior open space that is protected from fire exposure from the building and that has access to an open public thoroughfare.
Medium hazard industrial occupancy (Group F, Division 2) means an industrial occupancy in which the combustible content is more than 50 kg/m² or 1200 MJ/m² of floor area and that is not classified as a high hazard industrial occupancy.
Mercantile occupancy means the occupancy or use of a building or part of a building for the displaying or selling of retail goods, wares or merchandise.
Mezzanine means an intermediate floor assembly between the floor and ceiling of any room or storey and includes an interior balcony.
Mobility assistive device means a mobility assistive device as defined in section 2 of Ontario Regulation 191/11 (Integrated Accessibility Standards) made under the Accessibility for Ontarians with Disabilities Act, 2005.
Modified pool means a public pool that has a basin-shaped floor sloping downward and inward toward the interior from the rim.
Modified stack venting means a stack venting arrangement in which the stack vent above the connection of the highest stack vented fixture is reduced in diameter.
Municipal drinking water system has the same meaning as in subsection 2 (1) of the Safe Drinking Water Act, 2002.
Nominally horizontal means at an angle of less than 45° with the horizontal.
Nominally vertical means at an angle of not more than 45° with the vertical.
Noncombustible means that a material meets the acceptance criteria of CAN/ULC-S114, “Test for Determination of Non-Combustibility in Building Materials”.
Noncombustible construction means a type of construction in which a degree of fire safety is attained by the use of noncombustible materials for structural members and other building assemblies.
Objective means an objective set out in Article 2.2.1.1.
Occupancy means the use or intended use of a building or part of a building for the shelter or support of persons, animals or property.
Occupant load means the number of persons for which a building or part of a building is designed.
Offset means the piping that connects the ends of two pipes that are parallel.
Offset relief vent means a relief vent that provides additional air circulation upstream and downstream of an offset in a soil or waste stack.
Open air means the atmosphere outside a building.
Open-air storey means a storey in which at least 25 per cent of the total area of its perimeter walls is open to the outdoors in a manner that will provide cross ventilation to the entire storey.
Outdoor pool means a public pool that is not an indoor pool.
Pail privy means a latrine in which the receptacle for human waste consists of a removable container surmounted by a superstructure.
Partition means an interior wall, one storey or part-storey in height, that is not loadbearing.
Party wall means a wall,
(a) that is jointly owned and jointly used by two parties under an easement agreement or by a right in law, and
(b) that is erected at or upon a line separating two parcels of land each of which is, or is capable of being, a separate real estate entity.
Perched groundwater means a free standing body of water in the ground extending to a limited depth.
Percolation time means the average time in minutes that is required for water to drop one centimetre during a percolation test or as determined by a soil evaluation or analysis.
Performance level means the level of performance under which all or part of an existing building functions with respect to its building systems.
Permanent solid nutrient storage facility has the same meaning as in subsection 1 (1) of Ontario Regulation 267/03 (General) made under the Nutrient Management Act, 2002.
Pharmacy means the premises in a building or the part of the premises in which prescriptions are compounded and dispensed for the public or in which drugs are sold by retail.
Pile means a slender deep foundation unit,
(a) that is made of materials such as wood, steel or concrete or a combination of them, and
(b) that is either pre-manufactured and placed by driving, jacking, jetting or screwing, or cast-in-place in a hole formed by driving, excavating or boring.
Plenum means a chamber forming part of an air duct system.
Plumbing appliance means a receptacle or equipment that receives or collects water, liquids or sewage and discharges water, liquid or sewage directly or indirectly to a plumbing system.
Plumbing system means a system of connected piping, fittings, valves, equipment, fixtures and appurtenances contained in plumbing.
Point of entry treatment unit has the same meaning as in subsection 1 (1) of Ontario Regulation 170/03 (Drinking Water Systems) made under the Safe Drinking Water Act, 2002.
Pool deck means the area immediately surrounding a public pool.
Portable privy means a portable latrine in which the receptacle for human body waste and the superstructure are combined structurally into one unit.
Post-disaster building means a building that is essential to the provision of services in the event of a disaster, and includes,
(a) hospitals, emergency treatment facilities and blood banks,
(b) telephone exchanges,
(c) power generating stations and electrical substations,
(d) control centres for land transportation,
(e) public water treatment and storage facilities,
(f) water and sewage pumping stations,
(g) emergency response facilities,
(h) fire, rescue and police stations,
(i) storage facilities for vehicles or boats used for fire, rescue and police purposes, and
(j) communications facilities, including radio and television stations.
Potable means fit for human consumption.
Potable water system means the plumbing that conveys potable water.
Pressurized distribution system means a leaching bed in which the effluent is distributed through the use of pressurized distribution pipes.
Private sewage disposal system means a sewage system or a sewage works that is not owned and operated by the Crown, a municipality or an organization acceptable to the Director responsible for issuing an environmental compliance approval required under section 53 of the Ontario Water Resources Act.
Private sewer means a sewer other than a building sewer that,
(a) is not owned or operated by a municipality, the Ministry of the Environment, Conservation and Parks or another public agency,
(b) receives drainage from more than one sanitary building drain either directly or through more than one sanitary building sewer or receives drainage from more than one storm building drain either directly or through one or more storm building sewers, and connects to a main sewer, or
(c) serves as a place of disposal on the property,
but does not include,
(d) a sewer that carries only the sanitary waste or storm sewage from semi-detached houses each containing not more than two dwelling units,
(e) a sewer that carries only the sanitary waste or storm sewage from one main building that is of care, care and treatment, detention, commercial or industrial occupancy and one ancillary building, or
(f) a sewer that carries only the sanitary waste or storm sewage from a row housing complex having five or fewer dwelling units.
Private use means, when applied to plumbing fixtures, fixtures in residences and apartments, in private bathrooms of hotels, and in similar installations in other buildings for a single household or an individual.
Private water supply means piping that serves as a source of supply on the property to more than one water service pipe.
Private water supply system means an assembly of pipes, fittings, valves, equipment and appurtenances that supplies water from a private source to a potable water system.
Privy vault means a latrine in which the receptacle for human waste consists of a constructed vault from which the waste is periodically removed.
Process plant means an industrial occupancy where materials, including flammable liquids, combustible liquids or gases, are produced or used in a process.
Professional engineer means a person who holds a licence or a temporary licence under the Professional Engineers Act.
Public corridor means a corridor that provides access to exit from more than one suite.
Public heritage building means a heritage building where the occupancy in whole or in part includes viewing of the building by the public provided that displays in it are limited to those relevant to the heritage significance of the building.
Public pool means a structure, basin, chamber or tank containing or intended to contain an artificial body of water for swimming, water sport, water recreation or entertainment, but does not include,
(a) pools operated in conjunction with less than six dwelling units, suites or single family residences or any combination of them,
(b) pools that are used only for commercial display and demonstration purposes,
(c) wading pools,
(d) hydro-massage pools, or
(e) pools that serve only as receiving basins for persons at the bottom of water slides.
Public spa means a hydro-massage pool that contains an artificial body of water, that is intended primarily for therapeutic or recreational use, that is not drained, cleaned or refilled before use by each individual and that utilizes hydrojet circulation, air induction bubbles, current flow or a combination of them over the majority of the pool area, but does not include,
(a) wading pools, or
(b) spas operated in conjunction with less than six dwelling units, suites or single family residences, or any combination of them, for the use of occupants or residents and their visitors.
Public use means, when applied to plumbing fixtures, fixtures in general washrooms of schools, gymnasiums, hotels, bars, public comfort stations and other installations in which fixtures are installed so that their use is unrestricted.
Public way means a sidewalk, street, highway, square or another open space to which the public has access, as of right or by invitation, expressed or implied.
Rainwater means storm sewage runoff that is collected from a roof or the ground, but not from accessible patios and driveways.
Recirculation system means a system,
(a) that maintains the circulation of water through a public pool by pumps, and
(b) that provides continuous treatment of the water, including filtration and chlorination or bromination and any other process that may be necessary for the treatment of the water.
Recreational camp means a camp for recreational activities consisting of one or more buildings or other structures established or maintained as living quarters, with or without charge, for the temporary occupancy of 10 or more persons for five or more days.
Relief vent means a vent pipe that is used in conjunction with a circuit vent to provide additional air circulation between a drainage system and a venting system.
Repair garage means a building or part of a building where facilities are provided for the repair or servicing of motor vehicles.
Residential full flow-through fire sprinkler/standpipe system means an assembly of pipes and fittings installed in the residential portions of a building containing one or two dwelling units that conveys water from the water service pipe to outlets in the sprinkler and standpipe systems and is fully integrated into the potable water system to ensure a regular flow of water through all parts of the sprinkler and standpipe systems.
Residential occupancy means an occupancy in which sleeping accommodation is provided to residents who are not harboured for the purpose of receiving special care or treatment and are not involuntarily detained and includes an occupancy in which sleeping accommodation is provided to residents of a retirement home.
Residential partial flow-through sprinkler/standpipe system means an assembly of pipes and fittings installed in the residential portions of a building containing one or two dwelling units that conveys water from the water service pipe to outlets in the sprinkler and standpipe systems and in which flow occurs during inactive periods of the sprinkler and standpipe systems only through the main header to the water closet located at the farthest point of the sprinkler and standpipe systems.
Retirement home means a building or part of a building that is a retirement home as defined in subsection 2 (1) of the Retirement Homes Act, 2010.
Return duct means a duct for conveying air from a space being heated, ventilated or air-conditioned back to the heating, ventilating or air-conditioning appliance.
Riser means a water distributing pipe that extends through at least one full storey, as defined in Part 7 of Division B.
Rock means a portion of the earth’s crust that is consolidated, coherent and relatively hard and that is a naturally formed, solidly bonded, mass of mineral matter that cannot readily be broken by hand.
Roof drain means a fitting or device that is installed in the roof to permit storm sewage to discharge into a leader.
Roof gutter means an exterior channel installed at the base of a sloped roof to convey storm sewage.
Run means the horizontal distance between two adjacent tread nosings on a stair.
Sanitary building drain means a building drain that conducts sewage to a building sewer from the most upstream soil or waste stack, branch or fixture drain serving a water closet.
Sanitary building sewer means a pipe that is connected to a sanitary building drain 1 000 mm outside a wall of a building and that conducts sewage to a public sewer or private sewage disposal system.
Sanitary drainage pipe means all piping that conveys sanitary sewage to a place of disposal, including the sanitary building drain, sanitary building sewer, soil pipe, soil stack, waste stack and waste pipe but not the main sewer or piping in a sewage treatment plant.
Sanitary drainage system means a drainage system that conducts sanitary sewage.
Sanitary sewage means,
(a) liquid or water borne waste,
(i) of industrial or commercial origin, or
(ii) of domestic origin, including human body waste, toilet or other bathroom waste, and shower, tub, culinary, sink and laundry waste, or
(b) liquid or water borne waste discharged from a public pool to a drain.
Sanitary sewer means a sewer that conducts sewage.
Sanitary unit means a water closet, urinal, bidet or bedpan washer.
Self-service storage building means a building that is used to provide individual storage spaces to the public and that is open to the public only for those purposes.
Septic tank means a watertight vault in which sanitary sewage is collected for the purpose of removing scum, grease and solids from the liquid without the addition of air and in which solids settling and anaerobic digestion of the sanitary sewage takes place.
Service room means a room provided in a building to contain equipment associated with building services.
Service space means space provided in a building to facilitate or conceal the installation of building service facilities such as chutes, ducts, pipes, shafts or wires.
Service water heater means a device for heating water for plumbing services.
Sewage means sanitary sewage or storm sewage.
Sewage system means,
(a) a chemical toilet, an incinerating toilet, a recirculating toilet, a self-contained portable toilet and all forms of privy, including a portable privy, an earth pit privy, a pail privy, a privy vault and a composting toilet system,
(b) a greywater system,
(c) a cesspool,
(d) a leaching bed system, or
(e) a system that requires or uses a holding tank for the retention of hauled sewage at the site where it is produced before its collection by a hauled sewage system,
where these,
(f) have a design capacity of 10,000 litres per day or less,
(g) have, in total, a design capacity of 10,000 litres per day or less, where more than one of these are located on a lot or parcel of land, and
(h) are located wholly within the boundaries of the lot or parcel of land on which is located the building or buildings they serve.
Sewage works means sewage works as defined in subsection 1 (1) of the Ontario Water Resources Act.
Sewer lateral extension means the portion of a storm building sewer or sanitary building sewer that extends from the public sewer up to 1.5 m into the property.
Shallow buried trench means an absorption trench that contains a chamber or leaching chamber.
Shallow foundation means a foundation unit that derives its support from soil or rock located close to the lowest part of the building that it supports.
Shelf and rack storage system means a self-contained structural system within a building, having one or more elevated platforms or walkway levels for personnel access that may also support conveyors and other material handling, storage and distribution equipment.
Significant drinking water threat has the same meaning as in subsection 2 (1) of the Clean Water Act, 2006.
Size means the nominal diameter by which a pipe, fitting, trap or other similar item is commercially designated.
Smoke alarm means a combined smoke detector and audible alarm device designed to sound an alarm within the room or suite in which it is located on the detection of smoke within that room or suite.
Smoke detector means a fire detector designed to operate when the concentration of airborne combustion products exceeds a pre-determined level.
Soil means, except for the purposes of Part 8 of Division B, a portion of the earth’s crust that is fragmentary or such that individual particles of a dried sample may be readily separated by agitation in water, and includes boulders, cobbles, gravel, sand, silt, clay and organic matter.
Soil pipe means a sanitary drainage pipe that carries the discharge of a sanitary unit, with or without the discharge from any other fixture.
Soil stack means a vertical soil pipe that passes through one or more storeys and includes any offset that is part of the stack.
Solid masonry means a single-wythe or multi-wythe construction made of solid masonry units or semi-solid, cored or hollow masonry units, the cells of which may or may not be filled with mortar or grout. In multi-wythe masonry construction, the space between the wythes consists of a mortar-filled collar joint or grout-filled space and the wythes may or may not be constructed of the same masonry materials.
Solid masonry unit means a concrete block or brick unit, a clay brick unit or a calcium silicate brick unit, the net solid area of which is at least 75% of its gross area.
Sound transmission class means a single number rating of the airborne sound attenuation of a building assembly separating two adjoining spaces, taking into account only the direct sound transmission path, and “STC” has a corresponding meaning.
Source protection area has the same meaning as in subsection 2 (1) of the Clean Water Act, 2006.
Source protection plan has the same meaning as in subsection 2 (1) of the Clean Water Act, 2006.
Space heater means a space-heating appliance for heating the room or space within which it is located, without the use of ducts.
Space-heating appliance means an appliance,
(a) that is intended to supply heat directly to a room or space, such as a space heater, fireplace and unit heater, or
(b) that is intended to supply heat to rooms or spaces of a building through a heating system, such as a central furnace or boiler.
Sprinklered means equipped with a system of automatic sprinklers.
Stack vent means a vent pipe that connects the top of a soil stack or waste stack to a header or open air and “stack vented” has a corresponding meaning.
Stack venting means, when used with reference to fixtures, an arrangement such that the connections of the drainage piping from the stack vented fixtures to the stack provide venting to the fixture traps so that no additional vent pipe is required.
Stage means a space that is designed primarily for theatrical performances with provision for quick change scenery and overhead lighting, including environmental control for a wide range of lighting and sound effects, and that is traditionally, but not necessarily, separated from the audience by a proscenium wall and curtain opening.
Starting platform means a rigid platform located entirely on a pool deck that consists of a top that, if projected horizontally over the water surface, would be less than 1 000 mm in vertical height above the surface and that is designed to be used by a swimmer to dive from at the start of a swimming race.
Storage garage means a building or part of a building that is intended for the storage or parking of motor vehicles and that contains no provision for the repair or servicing of motor vehicles.
Storage-type service water heater means a service water heater with an integral hot water storage tank.
Storey means, except for the purposes of Part 7 of Division B, the portion of a building,
(a) that is situated between the top of any floor and the top of the floor next above it, or
(b) that is situated between the top of the floor and the ceiling above the floor, if there is no floor above it.
Storm building drain means a building drain that conducts storm water and is connected at its upstream end to a leader, sump or catch basin, and at its downstream end to a building sewer or a designated storm water disposal location.
Storm building sewer means a building sewer that conveys storm sewage to a place of disposal and commences 1 000 mm from the building.
Storm drainage pipe means all the connected piping that conveys storm sewage to a place of disposal and includes the storm building drain, storm building sewer, rain water leader, catch basin and area drain installed to collect water from the property and the piping that drains water from a swimming pool, other than a public pool, or from water cooled air-conditioning equipment, but does not include,
(a) a subsoil drainage pipe, or
(b) a private sewage treatment and disposal facility designed for the treatment or retention of storm sewage prior to discharge to the natural environment.
Storm drainage system means a drainage system that conveys storm sewage.
Storm sewage means water that is discharged from a surface as a result of rainfall, snow melt or snowfall.
Storm sewer means a sewer that conveys storm sewage.
Stove means an appliance intended for cooking or space heating or both.
Street means any highway, road, boulevard, square or other improved thoroughfare that is 9 m or more in width, that has been dedicated or deeded for public use and that is accessible to fire department vehicles and equipment.
Subsoil drainage pipe means a pipe that is installed underground to intercept and convey subsurface water, and includes foundation drain pipes.
Subsurface investigation means the appraisal of the general subsurface conditions at a building site by analysis of information gained by methods such as geological surveys, in situ testing, sampling, visual inspection, laboratory testing of samples of the subsurface materials and groundwater observations and measurements.
Suite means a single room or series of rooms of complementary use, operated under a single tenancy, and includes,
(a) dwelling units,
(b) individual guest rooms in motels, hotels, boarding houses, rooming houses and dormitories, and
(c) individual stores and individual or complementary rooms for business and personal services occupancies.
Supply duct means a duct for conveying air from a heating, ventilating or air-conditioning appliance to a space to be heated, ventilated or air-conditioned.
Surface water means water on the surface of the ground.
Tapered tread means a tread with non-parallel edges that increases or decreases its run uniformly over its width.
Tarion Warranty Corporation means Tarion Warranty Corporation as designated under section 2 of the Ontario New Home Warranties Plan Act.
Theatre means a place of public assembly intended for the production and viewing of the performing arts or the screening and viewing of motion pictures, and consisting of an auditorium with permanently fixed seats intended solely for a viewing audience.
Trap means a fitting or device that is designed to hold a liquid seal that will prevent the passage of gas but will not materially affect the flow of a liquid.
Trap arm means that portion of a fixture drain between the trap weir and the vent pipe fitting.
Trap dip means the lowest part of the upper interior surface of a trap.
Trap seal depth means the vertical distance between the trap dip and the trap weir.
Trap standard means the trap for a fixture that is integral with the support for the fixture.
Trap weir means the highest part of the lower interior surface of a trap.
Treatment unit means a device that, when designed, installed and operated in accordance with its design specifications, provides a specific degree of sanitary sewage treatment to reduce the contaminant load from that of sanitary sewage to a given effluent quality.
Tribunal means the Licence Appeal Tribunal established under the Licence Appeal Tribunal Act, 1999.
Type A dispersal bed means a leaching bed that receives effluent from a Level IV treatment unit as described in Table 8.6.2.2. of Division B and that is comprised of a stone layer or leaching chambers installed over an unsaturated sand layer as described in Subsection 8.7.7. of Division B.
Type B dispersal bed means a leaching bed comprised of a pressurized distribution system that uniformly distributes effluent from a Level IV treatment unit as described in Table 8.6.2.2. of Division B to the underlying soil, as defined in Part 8 of Division B, through a set of distribution pipes installed in a bed comprised of septic stone.
Unit heater means a suspended space heater with an integral air circulating fan.
Unprotected opening means, when applied to an exposing building face,
(a) a doorway, window or opening, other than one equipped with a closure having the required fire-protection rating, or
(b) any part of a wall forming part of the exposing building face that has a fire-resistance rating less than required for the exposing building face.
Unstable liquid means a liquid, including flammable liquids and combustible liquids, that is chemically reactive to the extent that it will vigorously react or decompose at or near normal temperature and pressure conditions or that is chemically unstable when subjected to impact.
Vacuum breaker means back-siphonage preventer.
Vapour barrier means the elements installed to control the diffusion of water vapour.
Vent connector means, when applied to a heating or cooling system, the part of a venting system that conducts the flue gases or vent gases from the flue collar of a gas appliance to the chimney or gas vent, and may include a draft control device.
Vent pipe means a pipe that is part of a venting system.
Vent stack means a vent pipe that is connected at its upper end to a header or is terminated in open air and that is used to limit pressure differential in a soil or waste stack.
Venting system means an assembly of pipes and fittings that connects a drainage system with open air for circulation of air and the protection of trap seals in the drainage system.
Vertical leg means the vertical portion of a fixture drain and includes the portion of a drain from the outlet of a water closet bowl to the point where the connecting piping changes to horizontal.
Vertical service space means a shaft that is oriented essentially vertically and that is provided in a building to facilitate the installation of building services, including mechanical, electrical and plumbing installations and facilities such as elevators, refuse chutes and linen chutes.
Vulnerable area has the same meaning as in subsection 2 (1) of the Clean Water Act, 2006.
Walkway means a covered or roofed pedestrian thoroughfare used to connect two or more buildings.
Waste pipe means a sanitary drainage pipe that carries the discharge from a fixture directly to a waste stack, soil stack, sanitary building drain, branch or sewage system.
Waste stack means a vertical waste pipe that passes through one or more storeys and includes any offset that is part of the stack that conducts liquid waste from fixtures other than sanitary units.
Water distribution system means an assembly of pipes, fittings, valves and appurtenances that conveys potable water to water supply outlets, fixtures, plumbing appliances and devices from the water service pipe or from a point of entry treatment unit located in the building.
Water purveyor means the owner or operator of a drinking water system.
Water service pipe means a pipe on the property that conveys potable water from a drinking water system or a private water supply to the inside of the building.
Water system means a water service pipe, a private water supply, a water distribution system, a fire service main or any part of any of them.
Wave action pool means a public pool equipped with a means for inducing wave motion in the water.
Wet vent means a waste pipe that also serves as a vent pipe.
Working capacity means the volume of liquid that a treatment unit or holding tank is capable of holding without overflowing while it is in its working position, but does not include the volume of liquid contained in a compartment in which a pump or siphon is installed.
X-ray equipment includes x-ray imaging systems, processing equipment and equipment directly related to the production of images for diagnosis or directly related to irradiation with x-rays for therapy.
X-ray machine means an electrically-powered device producing x-rays,
(a) for the irradiation of a human being or an animal for a therapeutic or diagnostic purpose, or
(b) for industrial use.
Yoke vent means a vent pipe that is connected at its lower end to a soil or waste stack and at its upper end to a vent stack or a branch vent that is connected to a vent stack.
1.4.1.3. Definition of Applicable Law
(1) For the purposes of clause 8 (2) (a) of the Act, applicable law means,
(a) the statutory requirements in the following provisions with respect to the following matters:
(0.0.i) section 3 of the Building Transit Faster Act, 2020 with respect to the issuance of a permit under that section,
(0.i) section 14 of Ontario Regulation 137/15 (General) made under the Child Care and Early Years Act, 2014 with respect to the approval of plans for a new building to be erected or an existing building to be used, altered or renovated for use as a child care centre or for alterations or renovations to be made to premises used by a child care centre,
(i) section 114 of the City of Toronto Act, 2006 with respect to the approval by the City of Toronto or the Ontario Land Tribunal of plans and drawings,
(ii) section 59 of the Clean Water Act, 2006 with respect to the issuance of a notice by the risk management official for the construction of a building,
(iii) Revoked: O. Reg. 139/17, s. 5 (2).
(iv) section 194 of the Education Act with respect to the approval of the Minister for the demolition of a building,
(v) Revoked: O. Reg. 88/19, s. 2.
(vi) section 5 of the Environmental Assessment Act with respect to the approval of the Minister or the Ontario Land Tribunal to proceed with an undertaking,
(vii) section 46 of the Environmental Protection Act with respect to the approval of the Minister to use land or land covered by water that has been used for the disposal of waste,
(viii) section 47.3 of the Environmental Protection Act with respect to the issuance of a renewable energy approval,
(ix) section 168.3.1 of the Environmental Protection Act with respect to the construction of a building to be used in connection with a change of use of a property,
(x) paragraph 2 of subsection 168.6 (1) of the Environmental Protection Act if a certificate of property use has been issued in respect of the property under subsection 168.6 (1) of that Act,
(xi) section 14 of the Milk Act with respect to the permit from the Director for the construction or alteration of any building intended for use as a plant,
(xii) section 11.1 of Ontario Regulation 267/03 (General), made under the Nutrient Management Act, 2002, with respect to a proposed building or structure to house farm animals or store nutrients if that Regulation requires the preparation and approval of a nutrient management strategy before construction of the proposed building or structure,
(xiii) subsection 30 (2) of the Ontario Heritage Act with respect to a consent of the council of a municipality to the alteration or demolition of a building where the council of the municipality has given a notice of intent to designate the building under subsection 29 (3) of that Act,
(xiv) section 33 of the Ontario Heritage Act with respect to the consent of the council of a municipality for the alteration of property,
(xv) section 34 of the Ontario Heritage Act with respect to the consent of the council of a municipality for the demolition of a building,
(xvi) section 34.5 of the Ontario Heritage Act with respect to the consent of the Minister to the alteration or demolition of a designated building,
(xvii) subsection 34.7 (2) of the Ontario Heritage Act with respect to a consent of the Minister to the alteration or demolition of a building where the Minister has given a notice of intent to designate the building under section 34.6 of that Act,
(xviii) section 42 of the Ontario Heritage Act with respect to the permit given by the council of a municipality for the erection, alteration or demolition of a building,
(xviii.1) section 17.4 of the Ontario New Home Warranties Plan Act with respect to the provision of a confirmation by the Registrar for the construction of a residential condominium conversion project,
(xix) section 14 of the Ontario Planning and Development Act, 1994 with respect to any conflict between a development plan made under that Act and a zoning by-law that affects the proposed building or structure,
(xix.1) section 37 of the Planning Act,
(A) with respect to the payment of money or making arrangements satisfactory to the council of a municipality for the payment of money, where the payment is required by a community benefits charge by-law passed under subsection 37 (2) of the Planning Act, and
(B) with respect to the provision of facilities, services or matters in accordance with subsection 37 (6) of the Planning Act or making arrangements satisfactory to the council of a municipality for their provision,
(xx) section 41 of the Planning Act with respect to the approval by the council of the municipality or the Ontario Land Tribunal of plans and drawings,
(xxi) section 42 of the Planning Act with respect to the payment of money or making arrangements satisfactory to the council of a municipality for the payment of money, where the payment is required under subsection 42 (6) of that Act,
(xxii) section 2 of Ontario Regulation 239/13 (Activities on Public Lands and Shore Lands — Work Permits and Exemptions), made under the Public Lands Act, with respect to the work permit authorizing the construction or placement of a building on public land,
(xxii.1) section 5 of Ontario Regulation 239/13 with respect to the exemption from the requirement to obtain a work permit authorizing the construction or placement of a building within an unpatented mining claim,
(xxiii) section 34 or 38 of the Public Transportation and Highway Improvement Act with respect to the permit from the Minister for the placement, erection or alteration of any building or other structure or the use of land,
(b) the following provisions of Acts and regulations:
(i) subsection 102 (3) of the City of Toronto Act, 2006,
(ii) sections 28 and 53 of the Development Charges Act, 1997,
(iii) sections 257.83 and 257.93 of the Education Act,
(iv) subsection 5 (4) of the Environmental Assessment Act,
(v) subsection 133 (4) of the Municipal Act, 2001,
(vi) subsection 24 (3) of the Niagara Escarpment Planning and Development Act,
(vii) subsection 27 (9) of the Ontario Heritage Act,
(viii) section 33 of the Planning Act except where, in the case of the demolition of a residential property, a permit to demolish the property is obtained under that section,
(ix) section 46 of the Planning Act,
(b.1) by-laws made by a municipality under an agreement entered into under section 5.81 of the Aeronautics Act (Canada),
(c) regulations made by a conservation authority under clause 28 (1) (c) of the Conservation Authorities Act with respect to permission of the authority for the construction of a building or structure if, in the opinion of the authority, the control of flooding, erosion, dynamic beaches or pollution or the conservation of land may be affected by the development,
(d) by-laws made under section 108 of the City of Toronto Act, 2006, but only with respect to the issuance of a permit for the construction of a green roof if the construction of the roof is prohibited unless a permit is obtained,
(e) by-laws made under section 40.1 of the Ontario Heritage Act,
(f) by-laws made under section 34 or 38 of the Planning Act,
(g) subject to clause (h), by-laws made under Ontario Regulation 173/16 (Community Planning Permits) made under the Planning Act,
(h) by-laws referred to in clause (g) in relation to the development of land, but only with respect to the issuance of a development permit if the development of land is prohibited unless a development permit is obtained,
(i) by-laws made under Ontario Regulation 246/01 (Development Permits) made under the Planning Act which continue in force despite the revocation of that Regulation by reason of section 19 of Ontario Regulation 173/16 (Community Planning Permits) made under that Act,
(j) orders made by the Minister under section 34.1 or 47 of the Planning Act or subsection 17 (1) of the Ontario Planning and Development Act, 1994, and
(k) by-laws made under any private Act that prohibit the proposed construction or demolition of the building unless the by-law is complied with.
(2) For the purposes of clause 10 (2) (a) of the Act, applicable law means any general or special Act, and all regulations and by-laws enacted under them that prohibit the proposed use of the building unless the Act, regulation or by-law is complied with.
1.4.1.4. Other definitions for the purposes of the Act
(1) For the purposes of the Act, architect, as constructed plans and professional engineer have the same meaning as that set out in Clause 1.4.1.2.(1)(c).
1.4.2. Symbols and Other Abbreviations
1.4.2.1. Symbols and Other Abbreviations
(1) In this Code, a symbol or abbreviation listed in Column 1 of Table 1.4.2.1. has the meaning listed opposite it in Column 2.
Table 1.4.2.1.
Symbols and Abbreviations
Forming Part of Sentence 1.4.2.1.(1)
Item |
Column 1 Symbol or Abbreviation |
Column 2 Meaning |
1. |
1 in 2 |
slope of 1 vertical to 2 horizontal |
2. |
ASWG |
American Steel Wire Gage |
3. |
ABS |
acrylonitrile-butadiene-styrene |
4. |
Bq |
becquerel(s) |
5. |
CBOD5 |
the five day carbonaceous biochemical oxygen demand |
6. |
cd |
candela(s) |
7. |
CFU |
colony forming units |
8. |
cm |
centimetre(s) |
9. |
cm² |
square centimetre(s) |
9.1 |
CO2e |
carbon dioxide equivalent |
10. |
CPVC |
chlorinated poly (vinyl chloride) |
11. |
dB(A) |
A-weighted sound level |
12. |
° |
degree(s) |
13. |
°C |
degree(s) Celsius |
14. |
diam |
diameter |
15. |
DWV |
drain, waste and vent |
16. |
ft |
foot (feet) |
17. |
g |
gram(s) |
18. |
ga |
gauge |
19. |
gal |
imperial gallon(s) |
20. |
gal/min |
imperial gallon(s) per minute |
21. |
h |
hour(s) |
22. |
HVAC |
heating, ventilating and air-conditioning |
23. |
Hz |
hertz |
24. |
in. |
inch(es) |
25. |
J |
joule(s) |
26. |
kg |
kilogram(s) |
27. |
kg/m² |
kilograms per square metre |
28. |
kN |
kilonewton(s) |
29. |
kPa |
kilopascal(s) |
29.1 |
kV |
kilovolt(s) |
30. |
kW |
kilowatt(s) |
31. |
L |
litre(s) |
32 |
L/min |
litre(s) per minute |
33. |
L/s |
litre(s) per second |
34. |
LPF |
litres per flush |
35. |
lx |
lux |
36. |
m |
metre(s) |
37. |
m² |
square metre(s) |
38 |
m3 |
cubic metre(s) |
39. |
m/s |
metre(s) per second |
40. |
max. |
maximum |
41. |
mg/L |
milligram(s) per litre |
42. |
min |
minute(s) |
43. |
min. |
minimum |
44. |
MJ |
megajoule(s) |
45. |
mm |
millimetre(s) |
46. |
MPa |
megapascal(s) |
47. |
N |
newton |
48. |
N/A |
not applicable |
49. |
ng |
nanogram(s) |
50. |
No. |
number(s) |
51. |
nom. |
nominal |
52. |
o.c. |
on centre |
53. |
OSB |
oriented strandboard |
54. |
Pa |
pascal(s) |
55. |
PB |
polybutylene |
56. |
PE |
polyethylene |
57. |
PE/AL/PE |
polyethylene/aluminum/polyethylene |
58. |
PEX |
crosslinked polyethylene |
59. |
PEX/AL/PEX |
crosslinked polyethylene/aluminum/crosslinked polyethylene |
60. |
PVC |
poly (vinyl chloride) |
61. |
RSI |
thermal resistance, International System of Units |
62. |
s |
second(s) |
63. |
temp. |
temperature |
64. |
T&G |
tongue and groove |
64.1 |
V |
volt(s) |
65. |
W |
watt(s) |
66. |
wt |
weight |
67. |
% |
percent |
68. |
µg |
microgram(s) |
69. |
µm |
micron |
Section 1.5. Referenced Documents and Organizations
1.5.1. Referenced Documents
1.5.1.1. Application of Referenced Documents
(1) The provisions of a referenced document in Divisions A and B apply only to the extent that the provisions relate to,
(a) buildings, and
(b) the objectives and functional statements attributed to the applicable acceptable solutions in Division B where the document is referenced.
1.5.1.2. Conflicting Requirements
(1) In the case of a conflict between the provisions of this Code and those of a referenced document, the provisions of this Code shall govern.
1.5.1.3. Applicable Editions
(1) Where documents are referenced in this Code, they shall be the editions designated in Subsection 1.3.1. of Division B.
1.5.2. Organizations
1.5.2.1. Abbreviations of Proper Names
(1) The abbreviations of proper names in this Code shall have the meanings assigned to them in Article 1.3.2.1. of Division B.
O. Reg. 332/12, Division A, Part 1; O. Reg. 151/13, ss. 1, 2; O. Reg. 361/13, ss. 1, 2; O. Reg. 368/13, s. 1; O. Reg. 191/14, ss. 1-4; O. Reg. 332/12, Sentence 4.2.1.1.(1); O. Reg. 139/17, ss. 1-6; O. Reg. 462/17, s. 1; O. Reg. 79/18, s. 1; O. Reg. 87/19, s. 1, 2; O. Reg. 88/19, s. 1, 2; O. Reg. 511/20, s. 1; O. Reg. 762/20, s. 1; O. Reg. 867/21, s. 1; O. Reg. 451/22, s. 1; O. Reg. 30/23, s. 1-3; O. Reg. 89/23, s. 1.
Part 2
Objectives
Section |
2.1. |
Application |
|
2.1.1. |
Application |
|
|
|
Section |
2.2. |
Objectives |
|
2.2.1. |
Objectives |
Section 2.1. Application
2.1.1. Application
2.1.1.1. Application of Objectives
(1) The objectives set out in Table 2.2.1.1. apply only to the extent that they relate to compliance with this Code as required in Article 1.2.1.1.
Section 2.2. Objectives
2.2.1. Objectives
2.2.1.1. Objectives
(1) The objectives of this Code shall be those set out in Table 2.2.1.1.
Table 2.2.1.1.
Objectives
Forming Part of Sentence 2.2.1.1.(1)
Item |
Column 1 Category |
Column 2 Number |
Column 3 Objective |
1. |
Safety |
OS |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury. |
|
Safety — Fire Safety |
OS1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to fire. |
|
|
OS1.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to fire caused by a fire or explosion. |
|
|
OS1.2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to fire caused by fire or explosion impacting areas beyond its point of origin. |
|
|
OS1.3 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to fire caused by the collapse of physical elements due to a fire or explosion. |
|
|
OS1.4 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to fire caused by fire safety systems failing to function as expected. |
|
|
OS1.5 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to fire caused by persons being delayed in or impeded from moving to a safe place during a fire emergency. |
|
Safety — Structural Safety |
OS2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to structural failure. |
|
|
OS2.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to structural failure caused by loads bearing on the building elements that exceed their loadbearing capacity. |
|
|
OS2.2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to structural failure caused by loads bearing on the building that exceed the loadbearing properties of the supporting medium. |
|
|
OS2.3 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to structural failure caused by damage to or deterioration of building elements. |
|
|
OS2.4 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to structural failure caused by vibration or deflection of building elements. |
|
|
OS2.5 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to structural failure caused by instability of the building or part of it. |
|
|
OS2.6 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to structural failure caused by collapse of the excavation. |
|
Safety — Safety in Use |
OS3 |
An objective of this Code is to limit the probability that, as a result of the design or construction of the building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to hazards. |
|
|
OS3.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to hazards caused by tripping, slipping, falling, contact, drowning or collision. |
|
|
OS3.2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to hazards caused by contact with hot surfaces or substances. |
|
|
OS3.3 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to hazards caused by contact with energized equipment. |
|
|
OS3.4 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to hazards caused by exposure to hazardous substances. |
|
|
OS3.5 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to hazards caused by exposure to high levels of sound from fire alarm systems. |
|
|
OS3.6 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to hazards caused by persons becoming trapped in confined spaces. |
|
|
OS3.7 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of injury due to hazards caused by persons being delayed in or impeded from moving to a safe place during an emergency. |
|
Safety — Resistance to Unwanted Entry |
OS4 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of injury due to the building’s low level of resistance to unwanted entry. |
|
|
OS4.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of injury due to the building’s low level of resistance to unwanted entry caused by intruders being able to force their way through locked doors or windows. |
|
|
OS4.2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of injury due to the building’s low level of resistance to unwanted entry caused by occupants being unable to identify potential intruders as such. |
2. |
Health |
OH |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person will be exposed to an unacceptable risk of illness. |
|
Health — Indoor Conditions |
OH1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to indoor conditions. |
|
|
OH1.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to indoor conditions caused by inadequate indoor air quality. |
|
|
OH1.2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to indoor conditions caused by inadequate thermal comfort. |
|
|
OH1.3 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to indoor conditions caused by contact with moisture. |
|
Health — Sanitation |
OH2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in or adjacent to the building will be exposed to an unacceptable risk of illness due to unsanitary conditions. |
|
|
OH2.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to unsanitary conditions caused by exposure to human or domestic waste. |
|
|
OH2.2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to unsanitary conditions caused by consumption of contaminated water. |
|
|
OH2.3 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to unsanitary conditions caused by inadequate facilities for personal hygiene. |
|
|
OH2.4 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to unsanitary conditions caused by contact with contaminated surfaces. |
|
|
OH2.5 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to unsanitary conditions caused by contact with vermin and insects. |
|
|
OH2.6 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person adjacent to the building will be exposed to an unacceptable risk of illness due to unsanitary conditions caused by exposure to human or domestic waste. |
|
Health — Noise Protection |
OH3 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to high levels of sound originating in adjacent spaces in the building. |
|
|
OH3.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to high levels of sound originating in adjacent spaces in the building caused by exposure to airborne sound transmitted through assemblies separating dwelling units from adjacent spaces in the building. |
|
Health — Vibration and Deflection Limitation |
OH4 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be exposed to an unacceptable risk of illness due to high levels of vibration or deflection of building elements. |
|
Health — Hazardous Substances Containment |
OH5 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, the public will be exposed to an unacceptable risk of illness due to the release of hazardous substances from the building. |
|
Health — Privacy |
OH6 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be provided with an unacceptable level of privacy. |
|
Health — View to the Outdoors |
OH7 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person in the building will be unable to experience a view to the outdoors. |
3. |
Accessibility |
OA |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person with a physical or sensory disability will be unacceptably impeded from accessing or using the building or its facilities. |
|
Accessibility — Barrier-free Path of Travel |
OA1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person with a physical or sensory disability will be unacceptably impeded from accessing the building or circulating within it. |
|
Accessibility — Barrier-free Facilities |
OA2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a person with a physical or sensory disability will be unacceptably impeded from using the building’s facilities. |
4. |
Fire, Structural, Water and Sewage Protection of Buildings |
OP |
An objective of this Code is to limit the probability that, as a result of its design or construction, the building or adjacent buildings will be exposed to an unacceptable risk of damage due to fire or structural insufficiency, or the building or part of it will be exposed to an unacceptable risk of loss of use also due to structural insufficiency. |
|
Fire, Structural, Water and Sewage Protection of Buildings — Fire Protection of the Building |
OP1 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building will be exposed to an unacceptable risk of damage due to fire. |
|
|
OP1.1 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building will be exposed to an unacceptable risk of damage due to fire caused by fire or explosion occurring. |
|
|
OP1.2 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building will be exposed to an unacceptable risk of damage due to fire caused by fire or explosion impacting areas beyond its point of origin. |
|
|
OP1.3 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building will be exposed to an unacceptable risk of damage due to fire caused by collapse of physical elements due to a fire or explosion. |
|
|
OP1.4 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building will be exposed to an unacceptable risk of damage due to fire caused by fire safety systems failing to function as expected. |
|
Fire, Structural, Water and Sewage Protection of Buildings — Structural Sufficiency of the Building |
OP2 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building or part of it will be exposed to an unacceptable risk of damage or loss of use due to structural failure or lack of structural serviceability. |
|
|
OP2.1 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building or part of it will be exposed to an unacceptable risk of damage or loss of use due to structural failure or lack of structural serviceability caused by loads bearing on the building elements that exceed their loadbearing capacity. |
|
|
OP2.2 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building or part of it will be exposed to an unacceptable risk of damage or loss of use due to structural failure or lack of structural serviceability caused by loads bearing on the building that exceed the loadbearing properties of the supporting medium. |
|
|
OP2.3 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building or part of it will be exposed to an unacceptable risk of damage or loss of use due to structural failure or lack of structural serviceability caused by damage to or deterioration of building elements. |
|
|
OP2.4 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building or part of it will be exposed to an unacceptable risk of damage or loss of use due to structural failure or lack of structural serviceability caused by vibration or deflection of building elements. |
|
|
OP2.5 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building or part of it will be exposed to an unacceptable risk of damage or loss of use due to structural failure or lack of structural serviceability caused by instability of the building or part of it. |
|
|
OP2.6 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building or part of it will be exposed to an unacceptable risk of damage or loss of use due to structural failure or lack of structural serviceability caused by instability or movement of the supporting medium. |
|
Fire, Structural, Water and Sewage Protection of Buildings — Protection of |
OP3 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, adjacent buildings will be exposed to an unacceptable risk of damage due to fire. |
|
Adjacent Buildings from Fire |
OP3.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, adjacent buildings will be exposed to an unacceptable risk of damage due to fire caused by fire or explosion impacting areas beyond the building of origin. |
|
Fire, Structural, Water and Sewage Protection of Buildings — Protection of |
OP4 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, adjacent buildings will be exposed to an unacceptable risk of structural damage. |
|
Adjacent Buildings from Structural Damage |
OP4.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, adjacent buildings will be exposed to an unacceptable risk of structural damage caused by settlement of the medium supporting adjacent buildings. |
|
|
OP4.2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of the building, adjacent buildings will be exposed to an unacceptable risk of structural damage caused by collapse of the building or portion of it onto adjacent buildings. |
|
|
OP4.3 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, adjacent buildings will be exposed to an unacceptable risk of structural damage caused by impact of the building on adjacent buildings. |
|
|
OP4.4 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, adjacent buildings will be exposed to an unacceptable risk of structural damage caused by collapse of the excavation. |
|
Fire, Structural, Water and Sewage Protection of Buildings — Water and Sewage Protection of Buildings and Facilities |
OP5 |
An objective of this Code is to limit the probability that, as a result of its design or construction, a building will be exposed to unacceptable risk of damage due to leakage of service water or sewage. |
5. |
Resource Conservation |
OR |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a resource will be exposed to an unacceptable risk of depletion or the capacity of the infrastructure supporting the use, treatment or disposal of the resource will be exposed to an unacceptable risk of being exceeded. |
|
Resource Conservation — Water and Energy Conservation |
OR1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a resource will be exposed to an unacceptable risk of depletion. |
|
|
OR1.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, water resources will be exposed to an unacceptable risk of depletion due to the consumption of water. |
|
|
OR1.2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, a resource will be exposed to an unacceptable risk of depletion due to the consumption of energy. |
|
Resource Conservation — Infrastructure Capacity |
OR2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, the capacity of the infrastructure supporting the use, treatment or disposal of a resource will be exposed to an unacceptable risk of being exceeded. |
|
|
OR2.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, the capacity of the infrastructure supporting the use, treatment or disposal of a resource will be exposed to an unacceptable risk of being exceeded due to excessive demand on the infrastructure. |
6. |
Environmental Integrity |
OE |
An objective of this Code is to limit the probability that, as a result of the design, construction or operation of a building, the natural environment will be exposed to an unacceptable risk of degradation. |
|
Environmental Integrity — Air Quality |
OE1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, the natural environment will be exposed to an unacceptable risk of degradation due to emissions into the air. |
|
|
OE1.1 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, the natural environment will be exposed to an unacceptable risk of degradation due to emissions of greenhouse gases into the air. |
|
|
OE1.2 |
An objective of this Code is to limit the probability that, as a result of the design or construction of a building, the natural environment will be exposed to an unacceptable risk of degradation due to the release of contaminants, other than greenhouse gases, into the air. |
|
Environmental Integrity — Water and Soil Quality |
OE2 |
An objective of this Code is to limit the probability that, as a result of the design, construction or operation of a building, the natural environment will be exposed to an unacceptable risk of degradation due to excessive release of contaminants into water or soil. |
7. |
Conservation of Buildings |
OC |
An objective of this Code is to limit the probability that, as a result of the extension, material alteration or repair of an existing building or a change in use of an existing building, the existing building cannot be acceptably conserved. |
O. Reg. 332/12, Division A, Part 2.
Part 3
Functional Statements
Section |
3.1. |
Application |
|
3.1.1. |
Application of Functional Statements |
|
|
|
Section |
3.2. |
Functional Statements |
|
3.2.1. |
Functional Statements |
Section 3.1. Application
3.1.1. Application of Functional Statements
3.1.1.1. Application of Functional Statements
(1) The functional statements set out in Table 3.2.1.1. apply only to the extent that they relate to compliance with this Code as required in Article 1.2.1.1.
Section 3.2. Functional Statements
3.2.1. Functional Statements
3.2.1.1. Functional Statements
(1) The functional statements of this Code are those set out in Table 3.2.1.1.
Table 3.2.1.1.
Functional Statements
Forming Part of Sentence 3.2.1.1.(1)
Item |
Column 1 Number |
Column 2 Function |
1. |
F01 |
To minimize the risk of accidental ignition. |
|
F02 |
To limit the severity and effects of fire or explosions. |
|
F03 |
To retard the effects of fire on areas beyond its point of origin. |
|
F04 |
To retard failure or collapse due to the effects of fire. |
|
F05 |
To retard the effects of fire on emergency egress facilities. |
|
F06 |
To retard the effects of fire on facilities for notification, suppression and emergency response. |
2. |
F10 |
To facilitate the timely movement of persons to a safe place in an emergency. |
|
F11 |
To notify persons, in a timely manner, of the need to take action in an emergency. |
|
F12 |
To facilitate emergency response. |
|
F13 |
To notify emergency responders, in a timely manner, of the need to take action in an emergency. |
3. |
F20 |
To support and withstand expected loads and forces. |
|
F21 |
To limit or accommodate dimensional change. |
|
F22 |
To limit movement under expected loads and forces. |
|
F23 |
To maintain equipment in place during structural movement. |
4. |
F30 |
To minimize the risk of injury to persons as a result of tripping, slipping, falling, contact, drowning or collision. |
|
F31 |
To minimize the risk of injury to persons as a result of contact with hot surfaces or substances. |
|
F32 |
To minimize the risk of injury to persons as a result of contact with energized equipment. |
|
F33 |
To limit the level of sound of a fire alarm system. |
|
F34 |
To resist or discourage unwanted access or entry. |
|
F35 |
To facilitate the identification of potential intruders. |
|
F36 |
To minimize the risk that persons will be trapped in confined spaces. |
5. |
F40 |
To limit the level of contaminants. |
|
F41 |
To minimize the risk of generation of contaminants. |
|
F42 |
To resist the entry of vermin and insects. |
|
F43 |
To minimize the risk of release of hazardous substances. |
|
F44 |
To limit the spread of hazardous substances beyond their point of release. |
|
F45 |
To minimize the risk of the spread of diseases through communal shower facilities. |
|
F46 |
To minimize the risk of contamination of potable water. |
6. |
F50 |
To provide air suitable for breathing. |
|
F51 |
To maintain appropriate air and surface temperatures. |
|
F52 |
To maintain appropriate relative humidity. |
|
F53 |
To maintain appropriate indoor/outdoor air pressure differences. |
|
F54 |
To limit drafts. |
|
F55 |
To resist the transfer of air through environmental separators. |
|
F56 |
To limit the transmission of airborne sound into a dwelling unit from spaces elsewhere in the building. |
7. |
F60 |
To control the accumulation and pressure of water on and in the ground. |
|
F61 |
To resist the ingress of precipitation, water or moisture from the exterior or from the ground. |
|
F62 |
To facilitate the dissipation of water and moisture from the building. |
|
F63 |
To limit moisture condensation. |
8. |
F70 |
To provide potable water. |
|
F71 |
To provide facilities for personal hygiene. |
|
F72 |
To provide facilities for the sanitary disposal of human and domestic wastes. |
|
F73 |
To facilitate access to and circulation in the building and its facilities by persons with physical or sensory disabilities. |
|
F74 |
To facilitate the use of a building’s facilities by persons with physical or sensory disabilities. |
9. |
F80 |
To resist deterioration resulting from expected service conditions. |
|
F81 |
To minimize the risk of malfunction, interference, damage, tampering, lack of use or misuse. |
|
F82 |
To minimize the risk of inadequate performance due to improper maintenance or lack of maintenance. |
10. |
F101 |
To limit unwanted visual exposure. |
|
F102 |
To provide a view to the outdoors in buildings. |
11. |
F110 |
To control the release of contaminants into soil, groundwater, surface water and air. |
F111 |
To minimize the risk of malfunction, damage or failure of a sewage system. |
|
|
F112 |
To provide adequate treatment of sanitary sewage and effluent. |
F113 |
To minimize the risk of injury as a result of contact with sanitary sewage or partially treated effluent. |
|
12. |
F120 |
To minimize the risk of injury to persons entering or exiting the pool, as a result of unfamiliarity with the pool. |
|
F121 |
To minimize the risk of injury to persons using the pool, as a result of unfamiliarity with the pool. |
|
F122 |
To minimize the risk of contamination of pool water. |
|
F123 |
To facilitate timely response to incapacitated pool users. |
|
F124 |
To minimize the risk of entrapment or injury to a person within the pool, as a result of water, air or vacuum action. |
13. |
F130 |
To limit excessive water consumption. |
|
F131 |
To limit excessive energy consumption. |
|
F132 |
To limit excessive demand on the infrastructure. |
|
F133 |
To limit excessive peak demand on the infrastructure. |
14. |
F140 |
To facilitate the reuse and material alteration and repair of existing buildings. |
15. |
F150 |
To limit excessive emissions of greenhouse gases into the air. |
F151 |
To limit excessive release of contaminants, other than greenhouse gases, into the air. |
O. Reg. 332/12, Division A, Part 3.
DIVISION b
acceptable solutions
Part 1
General
Section |
1.1. |
General |
|
1.1.1. |
Application |
|
1.1.2. |
Climatic Data |
|
|
|
Section |
1.2. |
Reserved |
|
|
|
Section |
1.3. |
Referenced Documents and Organizations |
|
1.3.1. |
Referenced Documents |
|
1.3.2. |
Abbreviations |
Section 1.1. General
1.1.1. Application
1.1.1.1. Application
(1) This Part applies to all buildings covered in this Code.
1.1.2. Climatic Data
1.1.2.1. Climatic and Seismic Design Values
(1) The climatic and seismic values required for the design of buildings under this Code shall be in conformance with the climatic and seismic values provided in MMAH Supplementary Standard SB-1, “Climatic and Seismic Data”.
(2) The outside winter design temperatures determined from MMAH Supplementary Standard SB-1, “Climatic and Seismic Data”, shall be those listed for the January 2.5% values.
1.1.2.2. Depth of Frost Penetration
(1) Depth of frost penetration shall be established on the basis of local experience.
Section 1.2. Reserved
Section 1.3. Referenced Documents and Organizations
1.3.1. Referenced Documents
1.3.1.1. Effective Date
(1) Unless otherwise specified in this Code, the documents referenced in this Code shall include all amendments, revisions and supplements effective to June 30, 2017.
1.3.1.2. Applicable Editions
(1) Where documents are referenced in this Code, they shall be in the editions designated in Column 2 of Table 1.3.1.2.
Table 1.3.1.2.
Documents Referenced in the Building Code
Forming Part of Sentence 1.3.1.2.(1)
Item |
Column 1 Issuing Agency |
Column 2 Document Number |
Column 3 Title of Document(1) |
Column 4 Code Reference |
1. |
ACGIH |
2013, 28th Edition |
Industrial Ventilation Manual |
6.2.1.1.(1) |
2. |
AISI |
S201-12 |
North American Standard for Cold-Formed Steel Framing - Product Data |
9.24.1.2.(1) |
3. |
ANSI |
A208.1-2009 |
Particleboard |
9.23.14.2.(3) 9.29.9.1.(1) 9.30.2.2.(1) |
3.0.1 |
ANSI |
E1.21-2013 |
Entertainment Technology - Temporary Structures Used for Technical Production of Outdoor Entertainment Events |
3.16A.2.8.(1) |
3.1 |
ANSI/APA |
PRG 320-2018 |
Standard for Performance-Rated Cross-Laminated Timber |
3.1.6.3.(3) |
4. |
ANSI/ASHRAE |
62.1-2010 |
Ventilation for Acceptable Indoor Air Quality |
6.2.2.1.(2) 6.2.3.8.(15) 6.2.3.21A.(1) |
5. |
ANSI/ASHRAE/IESNA |
90.1-2013 |
Energy Standard for Buildings Except Low-Rise Residential Buildings |
6.2.1.1.(1)
|
6. |
ANSI/CSA |
ANSI Z21.22-2015 / CSA 4.4-2015 |
Relief Valves for Hot Water Supply Systems |
7.2.10.11.(1) |
7. |
APHA/AWWA/WEF |
2012, 22nd Edition |
Standard Methods for the Examination of Water and Wastewater |
8.9.2.4.(1) |
8. |
ASCE |
ASCE/SEI 49-12 |
Wind Tunnel Testing for Buildings and Other Structures |
4.1.7.12.(1) |
9. |
ASHRAE |
2017 |
Fundamentals |
5.2.1.3.(1) 6.2.1.1.(1) |
10. |
ASHRAE |
2015 |
HVAC Applications |
6.2.1.1.(1) |
11. |
ASHRAE |
2016 |
HVAC Systems and Equipment |
6.2.1.1.(1) |
12. |
ASHRAE |
2018 |
Refrigeration |
6.2.1.1.(1) |
13. |
ASHRAE |
Guideline 12-2000 |
Minimizing the Risk of Legionellosis Associated with Building Water Systems |
6.2.3.14.(3) 6.2.3.14A.(3) |
14. |
ASME |
A112.19.8-2007 |
Suction Fittings for Use in Swimming Pools, Wading Pools, Spas, and Hot Tubs |
3.12.4.1.(9) |
15. |
ASME |
B16.3-2016 |
Malleable Iron Threaded Fittings: Classes 150 and 300 |
7.2.6.6.(1) |
16. |
ASME |
B16.4-2011 |
Gray Iron Threaded Fittings: Classes 125 and 250 |
7.2.6.5.(1) Table 7.2.11.2. |
17. |
ASME |
B16.5-2017 |
Pipe Flanges and Flanged Fittings: NPS ½ through NPS 24 Metric/Inch Standard |
7.2.6.12.(1) |
18. |
ASME |
B16.9-2012 |
Factory-Made Wrought Buttwelding Fittings |
7.2.6.11.(1) 7.2.6.14.(1) |
19. |
ASME |
B16.12-2009 |
Cast Iron Threaded Drainage Fittings |
7.2.6.3.(1) |
20. |
ASME |
B16.15-2013 |
Cast Copper Alloy Threaded Fittings: Classes 125 and 250 |
7.2.7.3.(1) |
21. |
ASME |
B16.18-2012 |
Cast Copper Alloy Solder Joint Pressure Fittings |
7.2.7.6.(1) 7.2.7.6.(2) Table 7.2.11.2. |
22. |
ASME |
B16.22-2013 |
Wrought Copper and Copper Alloy Solder Joint Pressure Fittings |
7.2.7.6.(1) Table 7.2.11.2. |
23. |
ASME |
B16.23-2016 |
Cast Copper Alloy Solder Joint Drainage Fittings: DWV |
7.2.7.5.(1) |
24. |
ASME |
B16.24-2016 |
Cast Copper Alloy Pipe Flanges and Flanged Fittings: Classes 150, 300, 600, 900, 1500, and 2500 |
7.2.7.2.(1) |
25. |
ASME |
B16.26-2013 |
Cast Copper Alloy Fittings for Flared Copper Tubes |
7.2.7.7.(1) 7.2.7.7.(2) Table 7.2.11.2. |
26. |
ASME |
B16.29-2012 |
Wrought Copper and Wrought Copper Alloy Solder-Joint Drainage Fittings – DWV |
7.2.7.5.(1) |
27. |
ASME |
ANSI/ASME B18.6.1-1981 |
Wood Screws (Inch Series) |
Table 5.10.1.1. 9.23.3.1.(3) |
28. |
ASME |
B31.9-2014 |
Building Services Piping |
7.3.2.8.(1) |
29. |
ASME |
B36.19M-2004 |
Stainless Steel Pipe |
7.2.6.10.(1) |
30. |
ASME / CSA |
ASME A17.1-2010 / CSA B44-10 |
Safety Code for Elevators and Escalators |
3.5.2.2.(1) Table 4.1.5.11. Table 4.1.8.18. 7.4.3.6.(1) |
31. |
ASME / CSA |
ASME A112.3.4-2013 / CSA B45.9-13 |
Plumbing Fixtures with Pumped Waste and Macerating Toilet Systems |
7.2.2.2.(8) |
32. |
ASME / CSA |
ASME A112.18.1-2012 / CSA B125.1-12 |
Plumbing Supply Fittings |
7.2.10.6.(1) 7.6.5.2.(1) |
33. |
ASME / CSA |
ASME A112.18.2-2015 / CSA B125.2-15 |
Plumbing Waste Fittings |
7.2.3.3.(1) 7.2.10.6.(2) |
34. |
ASME / CSA |
ASME A112.19.1-2013 / CSA B45.2-13 |
Enamelled Cast Iron and Enamelled Steel Plumbing Fixtures |
7.2.2.2.(3) 7.2.2.2.(4) |
35. |
ASME / CSA |
ASME A112.19.2-2013 / CSA B45.1-13 |
Ceramic Plumbing Fixtures |
7.2.2.2.(2) |
36. |
ASME / CSA |
ASME A112.19.3-2017 / CSA B45.4-17 |
Stainless Steel Plumbing Fixtures |
7.2.2.2.(5) |
37. |
ASME / CSA |
ASME A112.19.7-2012 / CSA B45.10-12 |
Hydromassage Bathtub Systems |
7.2.2.2.(7) |
38. |
ASPE |
2005 |
Data Books |
7.6.3.1.(2) 7.7.4.1.(1) |
39. |
ASSE |
ANSI/ASSE 1010-2004 |
Water Hammer Arresters |
7.2.10.15.(1) |
40. |
ASSE |
1051-2009 |
Individual and Branch Type Air Admittance Valves for Sanitary Drainage Systems |
7.2.10.16.(1) |
41. |
ASTM |
A53 / A53M-12 |
Pipe, Steel, Black and Hot-Dipped, Zinc-Coated Welded and Seamless |
7.2.6.7.(4) |
42. |
ASTM |
A123 / A123M-13 |
Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products |
Table 5.10.1.1. Table 9.20.16.1. |
43. |
ASTM |
A153 / A153M-09 |
Zinc Coating (Hot-Dip) on Iron and Steel Hardware |
Table 5.10.1.1. Table 9.20.16.1. |
44. |
ASTM |
A182 / A182M-16a |
Forged or Rolled Alloy and Stainless Steel Pipe Flanges, Forged Fittings, and Valves and Parts for High-Temperature Service |
7.2.6.12.(1) 7.2.6.13.(1) |
45. |
ASTM |
A252-10 |
Welded and Seamless Steel Pipe Piles |
4.2.3.8.(1) |
46. |
ASTM |
A269-15a |
Seamless and Welded Austenitic Stainless Steel Tubing for General Service |
7.2.6.14.(1) |
47. |
ASTM |
A283 / A283M-13 |
Low and Intermediate Tensile Strength Carbon Steel Plates |
4.2.3.8.(1) |
48. |
ASTM |
A312 / A312M-17 |
Seamless, Welded, and Heavily Cold Worked Stainless Steel Pipes |
7.2.6.10.(1) |
49. |
ASTM |
A351 / A351M-16 |
Castings, Austenitic, for Pressure-Containing Parts |
7.2.6.13.(1) |
50. |
ASTM |
A403 / A403M-16 |
Wrought Austenitic Stainless Steel Piping Fittings |
7.2.6.11.(1) |
51. |
ASTM |
A518 / A518M-99 |
Corrosion-Resistant High-Silicon Iron Castings |
7.2.8.1.(1) |
52. |
ASTM |
A653 / A653M-13 |
Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process |
Table 5.10.1.1. 9.3.3.2.(1) |
53. |
ASTM |
A792 / A792M-10 |
Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process |
9.3.3.2.(1) |
54. |
ASTM |
A1008 / A1008M-13 |
Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable |
4.2.3.8.(1) |
55. |
ASTM |
A1011 / A1011M-14 |
Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength |
4.2.3.8.(1) |
56. |
ASTM |
B32-08 |
Solder Metal |
7.2.9.2.(1) |
57. |
ASTM |
B42-15a |
Seamless Copper Pipe, Standard Sizes |
7.2.7.1.(1) |
58. |
ASTM |
B43-15 |
Seamless Red Brass Pipe, Standard Sizes |
7.2.7.1.(2) |
59. |
ASTM |
B68 / B68M-11 |
Seamless Copper Tube, Bright Annealed |
7.2.7.4.(3) |
60. |
ASTM |
B88-16 |
Seamless Copper Water Tube |
7.2.7.4.(1) 7.2.7.4.(3) Table 7.2.11.2. |
61. |
ASTM |
B306-13 |
Copper Drainage Tube (DWV) |
7.2.7.4.(1) |
62. |
ASTM |
B813-16 |
Liquid and Paste Fluxes for Soldering of Copper and Copper Alloy Tube |
7.2.9.2.(3) |
63. |
ASTM |
B828-16 |
Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings |
7.3.2.4.(1) |
64. |
ASTM |
C4-04 |
Clay Drain Tile and Perforated Clay Drain Tile |
Table 5.10.1.1. 9.14.3.1.(1) |
65. |
ASTM |
C27-98 |
Fireclay and High-Alumina Refractory Brick |
9.21.3.4.(1) |
66. |
ASTM |
C73-10 |
Calcium Silicate Brick (Sand-Lime Brick) |
Table 5.10.1.1. 9.20.2.1.(1) |
67. |
ASTM |
C126-13 |
Ceramic Glazed Structural Clay Facing Tile, Facing Brick, and Solid Masonry Units |
Table 5.10.1.1. 9.20.2.1.(1) |
68. |
ASTM |
C212-14 |
Structural Clay Facing Tile |
Table 5.10.1.1. 9.20.2.1.(1) |
69. |
ASTM |
C260 / C260M-10a |
Air-Entraining Admixtures for Concrete |
9.3.1.8.(1) |
70. |
ASTM |
C411-11 |
Hot-Surface Performance of High-Temperature Thermal Insulation |
6.2.3.4.(3) 6.2.9.2.(2) |
71. |
ASTM |
C412M-11 |
Concrete Drain Tile (Metric) |
Table 5.10.1.1. 9.14.3.1.(1) |
72. |
ASTM |
C444M-03 |
Perforated Concrete Pipe (Metric) |
Table 5.10.1.1. 9.14.3.1.(1) |
73. |
ASTM |
C494 / C494M-13 |
Chemical Admixtures for Concrete |
9.3.1.8.(1) |
74. |
ASTM |
C553-13 |
Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications |
Table 5.10.1.1. |
75. |
ASTM |
C612-14 |
Mineral Fiber Block and Board Thermal Insulation |
Table 5.10.1.1. |
76. |
ASTM |
C700-13 |
Vitrified Clay Pipe, Extra Strength, Standard Strength and Perforated |
Table 5.10.1.1. 9.14.3.1.(1) |
77. |
ASTM |
C726-12 |
Mineral Wool Roof Insulation Board |
Table 5.10.1.1. 9.25.2.2.(1) |
78. |
ASTM |
C834-10 |
Latex Sealants |
Table 5.10.1.1. 9.27.4.2.(2) |
79. |
ASTM |
C840-18b |
Application and Finishing of Gypsum Board |
3.1.6.6.(2) Table 5.10.1.1. |
80. |
ASTM |
C920-14 |
Elastomeric Joint Sealants |
Table 5.10.1.1. 9.27.4.2.(2) |
81. |
ASTM |
C954-11 |
Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness |
9.24.1.4.(1) |
82. |
ASTM |
C991-08e1 |
Flexible Fibrous Glass Insulation for Metal Buildings |
Table 5.10.1.1. |
83. |
ASTM |
C1002-07 |
Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs |
Table 5.10.1.1. 9.24.1.4.(1) 9.29.5.7.(1) |
84. |
ASTM |
C1053-00 |
Borosilicate Glass Pipe and Fittings for Drain, Waste, and Vent (DWV) Applications |
7.2.8.1.(1) |
85. |
ASTM |
C1177 / C1177M-13 |
Glass Mat Gypsum Substrate for Use as Sheathing |
3.1.5.12.(6) 3.1.5.12A.(4) Table 5.10.1.1. Table 9.23.16.2.A. |
86. |
ASTM |
C1178 / C1178M-13 |
Coated Glass Mat Water-Resistant Gypsum Backing Panel |
3.1.5.12.(6) 3.1.5.12A.(4) Table 5.10.1.1. 9.29.5.2.(1) |
87. |
ASTM |
C1184-13 |
Structural Silicone Sealants |
Table 5.10.1.1. 9.27.4.2.(2) |
88. |
ASTM |
C1311-10 |
Solvent Release Sealants |
Table 5.10.1.1. 9.27.4.2.(2) |
89. |
ASTM |
C1330-02 |
Cylindrical Sealant Backing for Use with Cold Liquid-Applied Sealants |
Table 5.10.1.1. 9.27.4.2.(3) |
90. |
ASTM |
C1396/C1396M-17 |
Gypsum Board |
3.1.5.12.(6) 3.1.5.12A.(4) 3.1.6.6.(2) 3.1.6.15.(1) Table 5.10.1.1. Table 9.23.16.2.A. 9.29.5.2.(1) Table 9.29.5.3. |
91. |
ASTM |
C1658 / C1658M-13 |
Glass Mat Gypsum Panels |
3.1.5.12.(6) Table 5.10.1.1. |
92. |
ASTM |
D323-08 |
Vapor Pressure of Petroleum Products (Reid Method) |
1.4.1.2.(1) of Division A |
93. |
ASTM |
D374-99 |
Thickness of Solid Electrical Insulation |
3.15.4.1.(1) |
94. |
ASTM |
D568-77 |
Rate of Burning and/or Extent and Time of Burning of Flexible Plastics in a Vertical Position |
3.15.4.1.(1) |
95. |
ASTM |
D635-06 |
Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position |
3.15.4.1.(1) |
96. |
ASTM |
D1227-95 |
Emulsified Asphalt Used as a Protective Coating for Roofing |
Table 5.10.1.1. 9.13.2.2.(2) 9.13.3.2.(2) |
97. |
ASTM |
D2178 / D2178M-13a |
Asphalt Glass Felt Used in Roofing and Waterproofing |
Table 5.10.1.1. |
98. |
ASTM |
D2898-10 |
Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing |
3.1.4.8.(3) |
99. |
ASTM |
D3019-08 |
Lap Cement Used with Asphalt Roll Roofing, Non-Fibered, Asbestos-Fibered, and Non-Asbestos-Fibered |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
100. |
ASTM |
D3261-16 |
Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing |
7.2.5.5.(3) |
101. |
ASTM |
D4479 / D4479M-07e1 |
Asphalt Roof Coatings - Asbestos-Free |
Table 5.10.1.1. 9.13.2.2.(2) 9.13.3.2.(2) Table 9.26.2.1.B. |
102. |
ASTM |
D4637 / D4637M-12 |
EPDM Sheet Used In Single-Ply Roof Membrane |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
103. |
ASTM |
D4811 / D4811M-06 |
Nonvulcanized (Uncured) Rubber Sheet Used as Roof Flashing |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
104. |
ASTM |
D5456-10a |
Evaluation of Structural Composite Lumber Products |
3.1.11.7.(4) |
105. |
ASTM |
D6878 / D6878M-11a |
Thermoplastic Polyolefin Based Sheet Roofing |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
106. |
Revoked: O. Reg. 762/20, s. 2. |
|||
107. |
ASTM |
E90-09 |
Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements |
5.8.1.2.(1) 5.8.1.4.(2) 9.11.1.2.(1) |
108. |
ASTM |
E96 / E96M-13 |
Water Vapor Transmission of Materials |
5.5.1.2.(3) 9.13.2.2.(2) 9.25.4.2.(1) 9.25.5.1.(1) |
109. |
ASTM |
E283-04 |
Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen |
5.10.4.4.(2) |
110. |
ASTM |
E331-00 |
Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference |
5.10.4.5.(2) |
111. |
ASTM |
E336-11 |
Measurement of Airborne Sound Attenuation Between Rooms in Buildings |
5.8.1.2.(2) 5.8.1.4.(8) 9.11.1.2.(2) |
112. |
ASTM |
E413-10 |
Classification for Rating Sound Insulation |
5.8.1.2.(1) 5.8.1.2.(2) 5.8.1.4.(8) 5.8.1.5.(4) 9.11.1.2.(1) 9.11.1.2.(2) |
113. |
ASTM |
E547-00 |
Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Cyclic Static Air Pressure Difference |
5.10.4.5.(2) |
114. |
ASTM |
E1300-12ae1 |
Determining Load Resistance of Glass in Buildings |
4.3.6.1.(1) |
115. |
ASTM |
E2178-13 |
Air Permeance of Building Materials |
5.4.1.2.(1) |
116. |
ASTM |
E2190-10 |
Insulating Glass Unit Performance and Evaluation |
Table 5.10.1.1. 9.6.1.2.(1) |
117. |
ASTM |
F476-14 |
Security of Swinging Door Assemblies |
9.7.5.2.(2) |
118. |
ASTM |
F628-12e2 |
Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe With a Cellular Core |
7.2.5.10.(1) 7.2.5.12.(1) 7.2.5.12.(2) |
119. |
ASTM |
F714-13 |
Polyethylene (PE) Plastic Pipe (DR-PR) Based on Outside Diameter |
7.2.5.6.(1) |
120. |
ASTM |
F1667-13 |
Driven Fasteners: Nails, Spikes, and Staples |
9.23.3.1.(1) 9.26.2.3.(1) 9.29.5.6.(1) |
121. |
AWS |
ANSI/AWS A5.8M/ A5.8:2011 |
Filler Metals for Brazing and Braze Welding |
7.2.9.2.(4) |
122. |
AWWA |
ANSI/AWWA C104 / A21.4-2013 |
Cement-Mortar Lining for Ductile-Iron Pipe and Fittings |
7.2.6.4.(2) Table 7.2.11.2. |
123. |
AWWA |
ANSI/AWWA C110 / A21.10-2012 |
Ductile-Iron and Gray-Iron Fittings |
7.2.6.4.(3) Table 7.2.11.2. |
124. |
AWWA |
ANSI/AWWA C111 / A21.11-2012 |
Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings |
7.2.6.4.(4) Table 7.2.11.2. |
125. |
AWWA |
ANSI/AWWA C151 / A21.51-2009 |
Ductile-Iron Pipe, Centrifugally Cast |
7.2.6.4.(1) Table 7.2.11.2. |
126. |
AWWA |
ANSI/AWWA C228-08 |
Stainless-Steel Pipe Flanges For Water Service - Sizes 2 in. through 72 in. (50 mm through 1,800 mm) |
7.2.6.12.(1) |
127. |
BCMOH |
Version 2, 21st Sept, 2007 |
Sewerage System Standard Practice Manual |
8.7.8.3.(2) 8.7.8.3.(3) |
128. |
BNQ |
BNQ 3624-115-2016 |
Polyethylene (PE) Pipe and Fittings - Flexible Pipes for Drainage - Characteristics and Test Methods |
Table 5.10.1.1. 9.14.3.1.(1) |
129. |
BNQ |
CAN/BNQ 3680-600-2009 |
Onsite Residential Wastewater Treatment Technologies |
8.6.2.2.(5) Table 8.6.2.2. |
130. |
CCBFC |
NRCC 38726 1995 |
National Building Code of Canada |
1.3.1.2.(3) of Division A |
131. |
CCBFC |
NRCC 38732 1995 |
National Farm Building Code of Canada |
1.3.1.2.(1) to (5) of Division A |
132. |
CCBFC |
NRCC 56190 2015, including all amendments, revisions and supplements effective to September 28, 2018 |
National Building Code of Canada |
2.4.2.1.(2) of Division C |
133. |
CCBFC |
NRCC 56191 2015 |
National Energy Code of Canada for Buildings |
6.2.1.1.(1) |
134. |
CCBFC |
NRCC 56192 2015, including all amendments, revisions and supplements effective to September 28, 2018 |
National Fire Code of Canada |
3.3.1.2.(1) 3.3.5.2.(1) 6.2.2.5.(1) |
135. |
CCBFC |
NRCC 56193 2015, including all amendments, revisions and supplements effective to September 28, 2018 |
National Plumbing Code of Canada |
2.4.2.1.(2) of Division C |
136. |
CGSB |
CAN/CGSB-1.501-M89 |
Method of Permeance of Coated Wallboard |
5.5.1.2.(2) 9.25.4.2.(5) |
137. |
CGSB |
CAN/CGSB-7.2-94 |
Adjustable Steel Columns |
9.17.3.4.(1) |
138. |
CGSB |
CAN/CGSB-10.3-92 |
Air Setting Refractory Mortar |
9.21.3.4.(2) 9.21.3.9.(1) 9.22.2.2.(2) |
139. |
CGSB |
CAN/CGSB-11.3-M87 |
Hardboard |
Table 5.10.1.1. 9.27.9.1.(2) 9.29.7.1.(1) 9.30.2.2.(1) |
140. |
CGSB |
CAN/CGSB-11.5-M87 |
Hardboard, Precoated, Factory Finished, for Exterior Cladding |
Table 5.10.1.1. 9.27.9.1.(1) |
141. |
CGSB |
CAN/CGSB-12.1-M90 |
Tempered or Laminated Safety Glass |
3.3.1.18.(2) 3.4.6.15.(1) 3.4.6.15.(3) Table 5.10.1.1. 9.6.1.2.(1) 9.6.1.4.(1) 9.8.8.7.(1) |
142. |
CGSB |
CAN/CGSB-12.2-M91 |
Flat, Clear Sheet Glass |
Table 5.10.1.1. 9.6.1.2.(1) |
143. |
CGSB |
CAN/CGSB-12.3-M91 |
Flat, Clear Float Glass |
Table 5.10.1.1. 9.6.1.2.(1) |
144. |
CGSB |
CAN/CGSB-12.4-M91 |
Heat Absorbing Glass |
Table 5.10.1.1. 9.6.1.2.(1) |
145. |
CGSB |
CAN/CGSB-12.5-M86 |
Mirrors, Silvered |
9.6.1.2.(3) |
146. |
CGSB |
CAN/CGSB-12.8-97 |
Insulating Glass Units |
Table 5.10.1.1. 9.6.1.2.(1) |
147. |
CGSB |
CAN/CGSB-12.10-M76 |
Glass, Light and Heat Reflecting |
Table 5.10.1.1. 9.6.1.2.(1) |
148. |
CGSB |
CAN/CGSB-12.11-M90 |
Wired Safety Glass |
3.3.1.18.(2) 3.4.6.15.(1) 3.4.6.15.(3) Table 5.10.1.1. 9.6.1.2.(1) 9.6.1.4.(1) 9.8.8.7.(1) |
149. |
CGSB |
CAN/CGSB-12.20-M89 |
Structural Design of Glass for Buildings |
4.3.6.1.(1) |
150. |
CGSB |
CAN/CGSB-19.22-M89 |
Mildew-Resistant Sealing Compound for Tubs and Tile |
9.29.10.5.(1) |
151. |
CGSB |
37-GP-9Ma-1983 |
Primer, Asphalt, Unfilled, for Asphalt Roofing, Dampproofing and Waterproofing |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.A. |
152. |
CGSB |
CAN/CGSB-37.50-M89 |
Hot-Applied, Rubberized Asphalt for Roofing and Waterproofing |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
153. |
CGSB |
CAN/CGSB-37.51-M90 |
Application for Hot-Applied Rubberized Asphalt for Roofing and Waterproofing |
9.26.15.1.(1) |
154. |
CGSB |
CAN/CGSB-37.54-95 |
Polyvinyl Chloride Roofing and Waterproofing Membrane |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
155. |
CGSB |
37-GP-55M-1979 |
Application of Sheet Applied Flexible Polyvinyl Chloride Roofing Membrane |
9.26.16.1.(1) |
156. |
CGSB |
37-GP-56M-1985 |
Membrane, Modified, Bituminous, Prefabricated, and Reinforced for Roofing |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
157. |
CGSB |
CAN/CGSB-37.58-M86 |
Membrane, Elastomeric, Cold-Applied Liquid, for Non-Exposed Use in Roofing and Waterproofing |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
158. |
CGSB |
CAN/CGSB-41.24-95 |
Rigid Vinyl Siding, Soffits and Fascia |
Table 5.10.1.1. 9.27.12.1.(1) |
159. |
CGSB |
CAN/CGSB-51.25-M87 |
Thermal Insulation, Phenolic, Faced |
Table 9.23.16.2.A. 9.25.2.2.(1) |
160. |
CGSB |
51-GP-27M-1979 |
Thermal Insulation, Polystyrene, Loose Fill |
9.25.2.2.(1) |
161. |
CGSB |
CAN/CGSB-51.32-M77 |
Sheathing, Membrane, Breather Type |
Table 5.10.1.1. 9.20.13.9.(1) 9.26.2.1.(1) 9.27.3.2.(1) Table 9.26.2.1.A. |
162. |
CGSB |
CAN/CGSB-51.33-M89 |
Vapour Barrier, Sheet, Excluding Polyethylene, for Use in Building Construction |
Table 5.10.1.1. 9.25.4.2.(4) |
163. |
CGSB |
CAN/CGSB-51.34-M86 |
Vapour Barrier, Polyethylene Sheet for Use in Building Construction |
Table 5.10.1.1. 9.13.2.2.(1) 9.13.4.3.(1) 9.18.6.2.(1) 9.25.3.2.(2) 9.25.4.2.(3) |
164. |
CGSB |
CAN/CGSB-82.6-M86 |
Doors, Mirrored Glass, Sliding or Folding, Wardrobe |
9.6.1.2.(2) |
165. |
CGSB |
CAN/CGSB-93.1-M85 |
Sheet, Aluminum Alloy, Prefinished, Residential |
Table 5.10.1.1. 9.27.11.1.(4) |
166. |
CGSB |
CAN/CGSB-93.2-M91 |
Prefinished Aluminum Siding, Soffits, and Facsia, for Residential Use |
3.2.3.6.(4) Table 5.10.1.1. 9.27.11.1.(3) |
167. |
CGSB |
CAN/CGSB-93.3-M91 |
Prefinished Galvanized and Aluminum-Zinc Alloy Steel Sheet for Residential Use |
Table 5.10.1.1. 9.27.11.1.(2) |
168. |
CGSB |
CAN/CGSB-93.4-92 |
Galvanized Steel and Aluminum-Zinc Alloy Coated Steel Siding, Soffits and Fascia, Prefinished, Residential |
Table 5.10.1.1. 9.27.11.1.(1) |
169. |
CSA |
CAN/CSA-6.19-01 |
Residential Carbon Monoxide Alarming Devices |
6.2.12.3.(1) 9.33.4.3.(1) |
170. |
CSA |
A23.1-14 |
Concrete Materials and Methods of Concrete Construction |
4.2.3.6.(1) 4.2.3.9.(1) Table 5.10.1.1. 9.3.1.1.(1) 9.3.1.1.(4) 9.3.1.3.(1) 9.3.1.4.(1) 9.39.1.4.(1) |
171. |
CSA |
A23.3-14 |
Design of Concrete Structures |
Table 4.1.8.9. 4.3.3.1.(1) |
172. |
CSA |
A60.1-M1976 |
Vitrified Clay Pipe |
7.2.5.4.(1) |
173. |
CSA |
A60.3-M1976 |
Vitrified Clay Pipe Joints |
7.2.5.4.(2) |
174. |
CSA |
CAN/CSA-A82-14 |
Fire Masonry Brick Made from Clay or Shale |
Table 5.10.1.1. 9.20.2.1.(1) |
175. |
CSA |
CAN/CSA-A82.27-M91 |
Gypsum Board |
3.1.5.12.(6) 3.1.5.12A.(4) 3.1.6.6.(2) 3.1.6.15.(1) 9.29.5.2.(1) |
176. |
CSA |
A82.30-M1980 |
Interior Furring, Lathing and Gypsum Plastering |
9.29.4.1.(1) |
177. |
CSA |
A82.31-M1980 |
Gypsum Board Application |
3.2.3.6.(4) 3.2.3.16.(1) 9.10.12.4.(3) 9.29.5.1.(2) |
178. |
CSA |
CAN3-A93-M82 |
Natural Airflow Ventilators for Buildings |
Table 5.10.1.1. 9.19.1.2.(5) |
179. |
CSA |
A123.1-05 / A123.5-05 |
Asphalt Shingles Made from Organic Felt and Surfaced with Mineral Granules / Asphalt Shingles Made from Glass Felt and Surfaced with Mineral Granules |
Table 5.10.1.1. Table 9.26.2.1.B. |
180. |
CSA |
CAN/CSA-A123.2-03 |
Asphalt-Coated Roofing Sheets |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
181. |
CSA |
A123.3-05 |
Asphalt Saturated Organic Roofing Felt |
Table 5.10.1.1. Table 9.26.2.1.B. |
182. |
CSA |
CAN/CSA-A123.4-04 |
Asphalt for Constructing Built-Up Roof Coverings and Waterproofing Systems |
Table 5.10.1.1. 9.13.2.2.(2) 9.13.3.2.(2) Table 9.26.2.1.B. |
183. |
CSA |
A123.17-05 |
Asphalt Glass Felt Used in Roofing and Waterproofing |
Table 5.10.1.1. 9.13.3.2.(2) Table 9.26.2.1.B. |
184. |
CSA |
A123.21-10 |
Dynamic Wind Uplift Resistance of Membrane-Roofing Systems |
5.2.2.2.(4) |
185. |
CSA |
A123.22-08 |
Self-Adhering Polymer Modified Bituminous Sheet Materials Used as Steep Roofing Underlayment for Ice Dam Protection |
Table 9.26.2.1.B. |
186. |
CSA |
CAN3-A123.51-M85 |
Asphalt Shingle Application on Roof Slopes 1:3 and Steeper |
Table 5.10.1.1. 9.26.1.2.(1) |
187. |
CSA |
CAN3-A123.52-M85 |
Asphalt Shingle Application on Roof Slopes 1:6 to Less than 1:3 |
Table 5.10.1.1. 9.26.1.2.(1) |
188. |
CSA |
A165.1-14 |
Concrete Block Masonry Units |
Table 5.10.1.1. 9.15.2.2.(1) 9.17.5.1.(1) 9.20.2.1.(1) 9.20.2.6.(1) |
189. |
CSA |
A165.2-14 |
Concrete Brick Masonry Units |
Table 5.10.1.1. 9.20.2.1.(1) |
190. |
CSA |
A165.3-14 |
Prefaced Concrete Masonry Units |
Table 5.10.1.1. 9.20.2.1.(1) |
191. |
CSA |
A179-14 |
Mortar and Grout for Unit Masonry |
Table 5.10.1.1. 9.15.2.2.(3) 9.20.3.1.(1) |
192. |
CSA |
CAN/CSA-A220 Series-06 |
Concrete Roof Tiles |
Table 5.10.1.1. Table 9.26.2.1.B. |
193. |
CSA |
CAN/CSA-A220.1-06 |
Installation of Concrete Roof Tiles |
9.26.17.1.(1) |
194. |
CSA |
A257 Series-14 |
Standards for Concrete Pipe and Manhole Sections |
7.2.5.3.(1) |
195. |
CSA |
A257.4-14 |
Precast Reinforced Circular Concrete Manhole Sections, Catch Basins, and Fittings |
7.2.5.3.(5) |
196. |
CSA |
A277-16 |
Procedure for Certification of Prefabricated Buildings, Modules, and Panels |
9.1.1.9.(1) 1.12.1.1.(1) of Division C 3.1.1.1.(2) of Division C 3.2.4.1.(3) of Division C |
197. |
CSA |
CAN/CSA-A324-M88 |
Clay Flue Liners |
9.21.3.3.(1) |
198. |
CSA |
A371-14 |
Masonry Construction for Buildings |
Table 5.10.1.1. 9.15.2.2.(3) 9.20.3.2.(7) 9.20.15.2.(1) |
199. |
CSA |
CAN/CSA-A405-M87 |
Design and Construction of Masonry Chimneys and Fireplaces |
9.21.3.5.(1) 9.22.1.4.(7) 9.22.5.2.(2) |
200. |
CSA |
AAMA/WDMA/CSA 101/I.S.2/A440-11 |
NAFS - North American Fenestration Standard/Specification for Windows, Doors, and Skylights |
5.10.2.2.(1) Table 9.7.3.3. 9.7.4.1.(1) 9.7.4.2.(1) 9.7.4.3.(2) 9.7.5.1.(1) 9.7.5.3.(1) |
201. |
CSA |
A440S1-17 |
Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-11, NAFS - North American Fenestration Standard/Specification for Windows, Doors, and Skylights |
5.10.2.2.(1) 5.10.4.5.(3) 9.7.4.2.(1) 9.7.4.3.(1) |
202. |
CSA |
A440.2-14 |
Fenestration Energy Performance |
12.3.1.2.(1) |
203. |
CSA |
A440.2-14 / A440.3-14 |
Fenestration Energy Performance / User Guide to CSA A440.2-14, Fenestration Energy Performance |
Table 9.7.3.3.
|
204. |
CSA |
CAN/CSA-A440.4-07 |
Window, Door, and Skylight Installation |
9.7.6.1.(1) |
205. |
CSA |
A660-10 |
Certification of Manufacturers of Steel Building Systems |
4.3.4.3.(1) |
206. |
CSA |
A3001-13 |
Cementitious Materials for Use in Concrete |
Table 5.10.1.1. 9.3.1.2.(1) 9.28.2.1.(1) |
207. |
CSA |
CAN/CSA-B45.0-02 |
General Requirements for Plumbing Fixtures |
7.6.4.2.(1) |
208. |
CSA |
B52-13 |
Mechanical Refrigeration Code |
6.2.2.4.(4) |
209. |
CSA |
B64.0-11 |
Definitions, General Requirements, and Test Methods for Vacuum Breakers and Backflow Preventers |
7.2.10.10.(1) |
210. |
CSA |
B64.1.1-11 |
Atmospheric Vacuum Breakers (AVB) |
7.2.10.10.(1) |
211. |
CSA |
B64.1.2-11 |
Pressure Vacuum Breakers (PVB) |
7.2.10.10.(1) |
212. |
CSA |
B64.1.3-11 |
Spill-Resistant Pressure Vacuum Breakers (SRPVB) |
7.2.10.10.(1) |
213. |
CSA |
B64.1.4-11 |
Vacuum Breaker, Air Space Type (ASVB) |
7.2.10.10.(1) |
214. |
CSA |
B64.2-11 |
Hose Connection Vacuum Breakers (HCVB) |
7.2.10.10.(1) |
215. |
CSA |
B64.2.1-11 |
Hose Connection Vacuum Breakers (HCVB) with Manual Draining Feature |
7.2.10.10.(1) |
216. |
CSA |
B64.2.1.1-11 |
Hose Connection Dual Check Vacuum Breakers (HCDVB) |
7.2.10.10.(1) |
217. |
CSA |
B64.2.2-11 |
Hose Connection Vacuum Breakers (HCVB) with Automatic Draining Feature |
7.2.10.10.(1) |
218. |
CSA |
B64.3-11 |
Dual Check Valve Backflow Preventers with Atmospheric Port (DCAP) |
7.2.10.10.(1) 7.6.2.5.(4) |
219. |
CSA |
B64.3.1-11 |
Dual Check Valve Backflow Preventers with Atmospheric Port for Carbonators (DCAPC) |
7.2.10.10.(1) |
220. |
CSA |
B64.4-11 |
Reduced Pressure Principle (RP) Backflow Preventers |
7.2.10.10.(1) |
221. |
CSA |
B64.4.1-11 |
Reduced Pressure Principle Backflow Preventers for Fire Protection Systems (RPF) |
7.6.2.4.(2) Table 7.6.2.4. 7.6.2.4.(4) |
222. |
CSA |
B64.5-11 |
Double Check Valve (DCVA) Backflow Preventers |
7.2.10.10.(1) |
223. |
CSA |
B64.5.1-11 |
Double Check Valve Backflow Preventers for Fire Protection Systems (DCVAF) |
7.6.2.4.(2) Table 7.6.2.4. |
224. |
CSA |
B64.6-11 |
Dual Check Valve (DuC) Backflow Preventers |
7.2.10.10.(1) 7.6.2.6.(3) 7.7.1.1.(3) |
225. |
CSA |
B64.6.1-11 |
Dual Check Valve Backflow Preventers for Fire Protection Systems (DuCF) |
7.6.4.2.(2) Table 7.6.2.4. |
226. |
CSA |
B64.7-11 |
Laboratory Faucet Vacuum Breakers (LFVB) |
7.2.10.10.(1) |
227. |
CSA |
B64.8-11 |
Dual Check Valve Backflow Preventers with Intermediate Vent (DuCV) |
7.2.10.10.(1) |
228. |
CSA |
B64.9-11 |
Single Check Valve Backflow Preventers for Fire Protection Systems (SCVAF) |
7.6.2.4.(2) Table 7.6.2.4. |
229. |
CSA |
B64.10-17 |
Selection and Installation of Backflow Preventers |
7.2.10.10.(1) 7.6.2.3.(1) Table 7.6.2.4. 7.6.2.6.(1) |
230. |
CSA |
B66-10 |
Design, Material, and Manufacturing Requirements for Prefabricated Septic Tanks and Sewage Holding Tanks |
8.2.2.2.(1) 8.2.2.2.(2) 8.2.2.2.(3) 8.2.2.3.(7) 8.2.2.3.(11) |
231. |
CSA |
CAN/CSA-B70-12 |
Cast Iron Soil Pipe, Fittings, and Means of Joining |
7.2.6.1.(1) 7.4.6.4.(2) |
232. |
CSA |
CAN/CSA-B70.1-03 |
Frames and Covers for Maintenance Holes and Catchbasins |
7.2.6.1.(3) |
233. |
CSA |
B111-1974 |
Wire Nails, Spikes and Staples |
9.23.3.1.(1) 9.26.2.3.(1) 9.29.5.6.(1) |
234. |
CSA |
B125.3-12 |
Plumbing Fittings |
7.2.10.6.(1) 7.2.10.10.(2) 7.6.5.2.(2) |
235. |
CSA |
CAN/CSA-B128.1-06 |
Design and Installation of Non-Potable Water Systems |
7.7.2.1.(2) 7.7.4.1.(1) |
236. |
CSA |
B137.1-17 |
Polyethylene (PE) Pipe, Tubing, and Fittings for Cold-Water Pressure Services |
7.2.5.5.(1) Table 7.2.11.2. |
237. |
CSA |
B137.2-17 |
Polyvinylchloride (PVC) Injection-Moulded Gasketed Fittings for Pressure Applications |
7.2.5.8.(1) 7.2.5.10.(1) Table 7.2.11.2. |
238. |
CSA |
B137.3-17 |
Rigid Polyvinylchloride (PVC) Pipe and Fittings for Pressure Applications |
7.2.5.8.(1) 7.2.5.10.(1) Table 7.2.11.2. |
239. |
CSA |
B137.5-17 |
Crosslinked Polyethylene (PEX) Tubing Systems for Pressure Applications |
7.2.5.7.(1) Table 7.2.11.2. |
240. |
CSA |
B137.6-17 |
Chlorinated Polyvinylchloride (CPVC) Pipe, Tubing, and Fittings for Hot- and Cold-Water Distribution Systems |
7.2.5.9.(1) Table 7.2.11.2. |
241. |
CSA |
B137.9-17 |
Polyethylene/Aluminum/Polyethylene (PE-AL-PE) Composite Pressure-Pipe Systems |
7.2.5.13.(1) Table 7.2.11.2. |
242. |
CSA |
B137.10-17 |
Crosslinked Polyethylene/Aluminum/Crosslinked Polyethylene (PEX-AL-PEX) Composite Pressure-Pipe Systems |
7.2.5.13.(4) 7.2.5.14.(1) Table 7.2.11.2. |
243. |
CSA |
B137.11-17 |
Polypropylene (PP-R) Pipe and Fittings for Pressure Applications |
7.2.5.15.(1) |
244. |
CSA |
B158.1-1976 |
Cast Brass Solder Joint Drainage, Waste and Vent Fittings |
7.2.10.1.(1) |
245. |
CSA |
CAN/CSA-B181.1-15 |
Acrylonitrile-Butadiene-Styrene (ABS) Drain, Waste, and Vent Pipe and Pipe Fittings |
7.2.5.10.(1) 7.2.5.11.(1) 7.2.5.12.(1) 7.2.5.12.(2) 7.2.10.1.(2) 7.4.6.4.(2) |
246. |
CSA |
CAN/CSA-B181.2-15 |
Polyvinylchloride (PVC) and Chlorinated Polyvinylchloride (CPVC) Drain, Waste, and Vent Pipe and Pipe Fittings |
7.2.5.10.(1) 7.2.5.11.(1) 7.2.5.12.(1) 7.2.5.12.(2) 7.2.10.1.(3) 7.4.6.4.(2) |
247. |
CSA |
CAN/CSA-B181.3-15 |
Polyolefin and Polyvinylidene Fluoride (PVDF) Laboratory Drainage Systems |
7.2.8.1.(1) |
248. |
CSA |
CAN/CSA-B182.1-15 |
Plastic Drain and Sewer Pipe and Pipe Fittings |
Table 5.10.1.1. 7.2.5.10.(1) 7.2.5.12.(2) 7.4.6.4.(2) 9.14.3.1.(1) |
249. |
CSA |
CAN/CSA-B182.2-15 |
PSM Type Polyvinylchloride (PVC) Sewer Pipe and Fittings |
7.2.5.10.(1) 7.2.5.12.(2) |
250. |
CSA |
CAN/CSA-B182.4-15 |
Profile Polyvinylchloride (PVC) Sewer Pipe and Fittings |
7.2.5.10.(1) |
251. |
CSA |
CAN/CSA-B182.6-15 |
Profile Polyethylene (PE) Sewer Pipe and Fittings for Leak-Proof Sewer Applications |
7.2.5.10.(1) |
252. |
CSA |
CAN/CSA-B182.8-15 |
Profile Polyethylene (PE) Storm Sewer and Drainage Pipe and Fittings |
7.2.5.10.(1) |
253. |
CSA |
B214-16 |
Installation Code for Hydronic Heating Systems |
6.2.1.4.(6) |
254. |
CSA |
B242-05 |
Groove- and Shoulder-Type Mechanical Pipe Couplings |
7.2.10.4.(1) |
255. |
CSA |
B272-93 |
Prefabricated Self-Sealing Roof Vent Flashings |
7.2.10.14.(2) |
256. |
CSA |
B355-09 |
Lifts for Persons with Physical Disabilities |
3.8.3.5.(1) |
257. |
CSA |
CAN/CSA-B356-10 |
Water Pressure Reducing Valves for Domestic Water Supply Systems |
7.2.10.12.(1) |
258. |
CSA |
B365-17 |
Installation Code for Solid-Fuel-Burning Appliances and Equipment |
6.2.1.4.(1) 6.2.1.4.(5) 9.21.1.3.(1) 9.22.10.2.(1) 9.33.1.2.(1) |
259. |
CSA |
B366.1-11 |
Solid-Fuel-Fired Central Heating Appliances |
6.2.1.4.(2) |
260. |
CSA |
B415.1-10 |
Performance Testing of Solid-Fuel-Burning Heating Appliances |
6.2.1.4.(7) 9.33.1.2.(2) |
261. |
CSA |
B481.0-12 |
Material, Design, and Construction Requirements for Grease Interceptors |
7.2.3.2.(4) |
262. |
CSA |
B481.1-12 |
Testing and Rating of Grease Interceptors Using Lard |
7.2.3.2.(3) 8.1.3.1.(8) |
263. |
CSA |
B481.2-12 |
Testing and Rating of Grease Interceptors Using Oil |
7.2.3.2.(3) 8.1.3.1.(8) |
264. |
CSA |
B481.3-12 |
Sizing, Selection, Location, and Installation of Grease Interceptors |
7.2.3.2.(4) |
265. |
CSA |
B481.4-12 |
Maintenance of Grease Interceptors |
8.9.3.3.(1) |
266. |
CSA |
CAN/CSA-B483.1-07 |
Drinking Water Treatment Systems |
7.2.10.17.(1) |
267. |
CSA |
B602-16 |
Mechanical Couplings for Drain, Waste, and Vent Pipe and Sewer Pipe |
7.2.5.3.(2) 7.2.10.4.(2) |
268. |
CSA |
C22.2 No. 0.3-09 |
Test Methods for Electrical Wires and Cables |
3.1.4.3.(1) 3.1.4.3.(2) 3.1.5.18.(1) 3.1.5.18.(2) 3.1.5.21.(1) 3.1.5.21.(2) 3.6.4.3.(1) 9.34.1.5.(1) |
269. |
CSA |
C22.2 No. 113-10 |
Fans and Ventilators |
9.32.3.9.(6) |
270. |
CSA |
C22.2 No. 141-10 |
Emergency Lighting Equipment |
3.2.7.4.(2) 3.4.5.1.(3) 9.9.11.3.(3) 9.9.12.3.(7) |
271. |
CSA |
C22.2 No. 211.0-03 |
General Requirements and Methods of Testing for Nonmetallic Conduit |
3.1.5.20.(1) |
272. |
CSA |
CAN/CSA-C22.2 No. 262-04 |
Optical Fiber Cable and Communication Cable Raceway Systems |
3.1.5.20.(1) |
273. |
CSA |
CAN/CSA-C22.3 No. 1-10 |
Overhead Systems |
3.1.19.1.(2) |
274. |
CSA |
CAN/CSA-C88-M90 |
Power Transformers and Reactors |
3.6.2.7.(10) |
275. |
CSA |
CAN/CSA-C260-M90 |
Rating for the Performance of Residential Mechanical Ventilating Equipment |
9.32.3.9.(1) 9.32.3.9.(2) Table 9.32.3.9. |
276. |
CSA |
C282-15 |
Emergency Electrical Power Supply for Buildings |
3.2.7.5.(1) |
277. |
CSA |
CAN/CSA-C439-09 |
Rating the Performance of Heat/Energy-Recovery Ventilators |
9.32.3.11.(2) |
278. |
CSA |
CAN/CSA-C448.1-13 |
Design and Installation of Earth Energy Systems for Commercial and Institutional Buildings |
6.2.1.4.(4) |
279. |
CSA |
CAN/CSA-C448.2-13 |
Design and Installation of Earth Energy Systems for Residential and Other Small Buildings |
6.2.1.4.(3) |
280. |
CSA |
F280-12 |
Determining the Required Capacity of Residential Space Heating and Cooling Appliances |
6.2.1.1.(1) 9.33.2.2.(3) |
281. |
CSA |
CAN/CSA-F326-M91 |
Residential Mechanical Ventilation Systems |
6.2.1.1.(1) |
282. |
CSA |
CAN/CSA-F379.1-09 |
Packaged Solar Domestic Hot Water Systems (Liquid-to-Liquid Heat Transfer) for All-Season Use |
7.2.10.13.(1) 7.6.2.5.(3) 7.6.2.5.(4) |
283. |
CSA |
CAN/CSA-F383-08 |
Installation of Packaged Solar Domestic Hot Water Systems |
7.6.1.13.(2) |
284. |
CSA |
G30.18-09 |
Carbon Steel Bars for Concrete Reinforcement |
9.3.1.1.(4) 9.39.1.3.(1) |
285. |
CSA |
G40.21-13 |
Structural Quality Steel |
4.2.3.8.(1) Table 5.10.1.1. 9.23.4.3.(2) |
286. |
CSA |
CAN/CSA-G164-M92 |
Hot Dip Galvanizing of Irregularly Shaped Articles |
4.4.4.1.(4) |
287. |
CSA |
CAN/CSA-G401-14 |
Corrugated Steel Pipe Products |
Table 5.10.1.1. 7.2.6.8.(1) 9.14.3.1.(1) |
288. |
CSA |
CAN/CSA-O80 Series-08 |
Wood Preservation |
3.1.4.5.(1) 4.2.3.2.(1) 4.2.3.2.(2) Table 5.10.1.1. |
289. |
CSA |
CAN/CSA-O80.1-08 |
Specification of Treated Wood |
9.3.2.9.(6) |
290. |
CSA |
CAN/CSA-O80.2-08 |
Processing and Treatment |
4.2.3.2.(1) |
291. |
CSA |
CAN/CSA-O80.3-08 |
Preservative Formulations |
4.2.3.2.(1) |
292. |
CSA |
O80.15-97 |
Preservative Treatment of Wood for Building Foundation Systems, Basements, and Crawl Spaces by Pressure Processes |
4.2.3.2.(1) |
293. |
CSA |
O86-14 |
Engineering Design in Wood |
Table 4.1.8.9. 4.3.1.1.(1) |
294. |
CSA |
O118.1-08 |
Western Red Cedar Shakes and Shingles |
Table 5.10.1.1. 9.27.7.1.(1) Table 9.26.2.1.B. |
295. |
CSA |
O118.2-08 |
Eastern White Cedar Shingles |
Table 5.10.1.1. 9.27.7.1.(1) Table 9.26.2.1.B. |
296. |
CSA |
O121-08 |
Douglas Fir Plywood |
Table 5.10.1.1. 9.23.14.2.(1) 9.23.15.2.(1) Table 9.23.16.2.A. 9.27.8.1.(1) 9.30.2.2.(1) Table A-13 Table A-14 Table A-15 |
297. |
CSA |
CAN/CSA-O122-16 |
Structural Glued-Laminated Timber |
Table A-11 Table A-16 |
298. |
CSA |
CAN/CSA-O132.2 Series-90 |
Wood Flush Doors |
9.7.4.3.(4) |
299. |
CSA |
O141-05 |
Softwood Lumber |
Table 5.10.1.1. 9.3.2.6.(1) |
300. |
CSA |
O151-09 |
Canadian Softwood Plywood |
Table 5.10.1.1. 9.23.14.2.(1) 9.23.15.2.(1) Table 9.23.16.2.A. 9.27.8.1.(1) 9.30.2.2.(1) Table A-13 Table A-14 Table A-15 |
301. |
CSA |
O153-13 |
Poplar Plywood |
Table 5.10.1.1. 9.23.14.2.(1) 9.23.15.2.(1) Table 9.23.16.2.A. 9.27.8.1.(1) 9.30.2.2.(1) |
302. |
CSA |
O177-06 |
Qualification Code for Manufacturers of Structural Glued-Laminated Timber |
4.3.1.2.(1) Table A-11 Table A-16 |
303. |
CSA |
O325-07 |
Construction Sheathing |
Table 5.10.1.1. 9.23.14.2.(1) 9.23.14.4.(2) Table 9.23.14.5.B. 9.23.15.2.(1) 9.23.15.3.(2) Table 9.23.15.7.B. Table 9.23.16.2.B. 9.29.9.1.(2) 9.29.9.2.(5) Table A-13 Table A-14 Table A-15 |
304. |
CSA |
O437.0-93 |
OSB and Waferboard |
Table 5.10.1.1. 9.23.14.2.(1) 9.23.14.4.(2) 9.23.15.2.(1) 9.23.15.3.(2) Table 9.23.16.2.A. 9.27.10.1.(1) 9.29.9.1.(2) 9.30.2.2.(1) Table A-13 Table A-14 Table A-15 |
305. |
CSA |
S16-14 |
Design of Steel Structures |
Table 4.1.8.9. 4.3.4.1.(1) |
306. |
CSA |
S37-13 |
Antennas, Towers, and Antenna-Supporting Structures |
4.1.6.15.(1) 4.1.7.11.(1) |
307. |
CSA |
S136-16 |
North American Specification for the Design of Cold-Formed Steel Structural Members (using the Appendix B provisions applicable to Canada) |
4.1.8.1.(5) Table 4.1.8.9. 4.3.4.2.(1) |
308. |
CSA |
CAN/CSA-S157-05 / S157.1-05 |
Strength Design in Aluminum / Commentary on CSA S157-05, Strength Design in Aluminum |
4.3.5.1.(1) |
309. |
CSA |
S304-14 |
Design of Masonry Structures |
Table 4.1.8.9. 4.3.2.1.(1) |
310. |
CSA |
S307-M1980 |
Load Test Procedure for Wood Trusses for Houses and Small Buildings |
9.23.13.11.(5) |
311. |
CSA |
S367-12 |
Air-, Cable-, and Frame-Supported Membrane Structures |
4.4.1.1.(1) |
312. |
CSA |
S406-16 |
Permanent Wood Foundations for Housing and Small Buildings |
9.13.2.7.(1) 9.15.2.4.(1) 9.16.5.1.(1) |
313. |
CSA |
S413-14 |
Parking Structures |
4.4.2.1.(1) |
314. |
CSA |
S478-95 |
Guideline on Durability in Buildings |
5.1.4.2.(3) |
315. |
CSA |
Z32-09 |
Electrical Safety and Essential Electrical Systems in Health Care Facilities |
3.2.7.3.(4) 3.2.7.6.(1) 3.7.5.1.(1) |
316. |
CSA |
CAN/CSA-Z91-02 |
Health and Safety Code for Suspended Equipment Operations |
4.4.4.1.(1) |
317. |
CSA |
Z240 MH Series-09 |
Manufactured Homes |
3.1.1.1.(2) of Division C 3.2.4.1.(3) of Division C |
318. |
CSA |
Z240.2.1-09 |
Structural Requirements for Manufactured Homes |
9.1.1.9.(1) 9.12.2.2.(6) 9.15.1.3.(1) |
319. |
CSA |
Z240.10.1-16 |
Site Preparation, Foundation, and Installation of Buildings |
9.15.1.3.(1) 9.23.6.3.(1) |
320. |
CSA |
CAN/CSA-Z241 Series-03 |
Park Model Trailers |
9.38.1.1.(1) 9.38.2.1.(1) 3.1.1.1.(2) of Division C 3.2.4.1.(3) of Division C |
321. |
CSA |
CAN/CSA-Z317.2-10 |
Special Requirements for Heating, Ventilation, and Air Conditioning (HVAC) Systems in Health Care Facilities |
6.2.1.1.(1) 6.2.3.14.(1) |
322. |
CSA |
CAN/CSA-Z662-15 |
Oil and Gas Pipeline Systems |
3.2.3.21.(1) |
323. |
CSA |
Z7396.1-12 |
Medical Gas Piping Systems - Part 1: Pipelines for Medical Gases, Medical Vacuum, Medical Support Gases, and Anaesthetic Gas Scavenging Systems |
3.7.5.2.(1) |
324. |
CSA / IAPMO |
CSA B45.5-11 / IAPMO Z124-2011 |
Plastic Plumbing Fixtures |
7.2.2.2.(6) |
325. |
CWC |
2014 |
Engineering Guide for Wood Frame Construction |
9.4.1.1.(1) |
326. |
DBR |
Technical Paper No. 194, May 1965 |
Fire Endurance of Protected Steel Columns and Beams |
Table 11.5.1.1.A. Table 11.5.1.1.B. Table 11.5.1.1.C. Table 11.5.1.1.D/E. Table 11.5.1.1.F. |
327. |
DBR |
Technical Paper No. 207, October 1965 |
Fire Endurance of Unit Masonry Walls |
Table 11.5.1.1.A. Table 11.5.1.1.B. Table 11.5.1.1.C. Table 11.5.1.1.D/E. Table 11.5.1.1.F. |
328. |
DBR |
Technical Paper No. 222, June 1966 |
Fire Endurance of Light-Framed and Miscellaneous Assemblies |
Table 11.5.1.1.A. Table 11.5.1.1.B. Table 11.5.1.1.C. Table 11.5.1.1.D/E. Table 11.5.1.1.F. |
329. |
EPA |
625/R-92/016 (1994) |
Radon Prevention in the Design and Construction of Schools and Other Large Buildings |
6.2.1.1.(1) |
330. |
FINA |
2009 |
Rules and Regulations - FINA Facilities Rules 2009-2013 - FR5 Diving Facilities |
3.11.4.1.(17) |
331. |
HI |
2005 |
Hydronics Institute Manuals |
6.2.1.1.(1) |
332. |
HPVA |
ANSI/HPVA HP-1-2009 |
Hardwood and Decorative Plywood |
Table 5.10.1.1. 9.27.8.1.(1) 9.30.2.2.(1) |
333. |
HRAI |
2005 |
Digest |
6.2.1.1.(1) 6.2.3.5.(1) 6.2.4.3.(13) |
334. |
HUD |
Rehabilitation Guidelines 2000 |
Guideline on Fire Ratings of Archaic Materials and Assemblies |
Table 11.5.1.1.A. Table 11.5.1.1.B. Table 11.5.1.1.C. Table 11.5.1.1.D/E. Table 11.5.1.1.F. |
335. |
HVI |
HVI 915-2013 |
Loudness Testing and Rating Procedure |
9.32.3.9.(2) Table 9.32.3.9. |
336. |
HVI |
HVI 916-2013 |
Airflow Test Procedure |
9.32.3.9.(1) |
337. |
IAPMO |
PS 63-2014 |
Plastic Leaching Chambers |
8.7.2.3.(3) |
338. |
ISO |
3864-1: 2011 |
Graphical Symbols - Safety Colours and Safety Signs - Part 1: Design Principles for Safety Signs and Safety Markings |
3.4.5.1.(2) 9.9.11.3.(2) |
339. |
ISO |
7010: 2011 |
Graphical Symbols - Safety Colours and Safety Signs - Registered Safety Signs |
3.4.5.1.(2) 9.9.11.3.(2) |
340. |
ISO |
8201: 1987(E) |
Acoustics - Audible Emergency Evacuation Signal |
3.2.4.20.(2) |
341. |
ISO |
10848:2006 |
Acoustics - Laboratory Measurement of the Flanking Transmission of Airborne and Impact Sound Between Adjoining Rooms |
5.8.1.4.(3) 5.8.1.4.(4) 5.8.1.5.(3) 5.8.1.5.(4) |
342. |
ISO |
15712-1:2005 |
Building Acoustics - Estimation of Acoustic Performance of Buildings From the Performance of Elements - Part 1: Airborne Sound Insulation Between Rooms |
5.8.1.4.(2) 5.8.1.4.(3) 5.8.1.4.(5) 5.8.1.4.(6) 5.8.1.4.(7) 5.8.1.5.(2) 5.8.1.5.(3) 5.8.1.4.(6) 5.8.1.4.(7) |
343. |
ISO |
23599: 2012 |
Assistive Products for Blind and Vision-Impaired Persons - Tactile Walking Surface Indicators |
3.8.3.18.(1) |
344. |
MMAH |
Supplementary Standard SA-1, January 15, 2019 |
Objectives and Functional Statements Attributed to the Acceptable Solutions |
1.2.1.1.(1) of Division A 1.2.1.1.(2) of Division A |
345. |
MMAH |
Supplementary Standard SB-1, January 15, 2019 |
Climatic and Seismic Data |
1.1.2.1.(1) 1.1.2.1.(2) 3.2.6.2.(2) 3.3.1.7.(1) 5.2.1.1.(1) 5.2.1.1.(2) 6.2.1.1.(1) 6.2.1.7.(1) 7.4.10.4.(1) 9.4.1.1.(3) 9.4.2.2.(1) Tables 9.6.1.3.A. to 9.6.1.3.G. Table 9.25.5.2. Table 9.32.3.10.A. 9.33.3.2.(1) |
346. |
MMAH |
Supplementary Standard SB-2, March 31, 2022 |
Fire Performance Ratings |
3.1.5.23.(1) 3.1.6.9.(4) 3.1.6.10.(2) 3.1.7.1.(2) 3.1.8.14.(2) 3.1.9.5.(1) 3.1.12.1.(3) 3.2.3.12.(1) 3.2.3.13.(4) 3.13.2.1.(8) 3.13.3.5.(1) 3.13.3.6.(2) 3.13.4.2.(7) 9.10.3.1.(1) 9.10.3.2.(1) 9.10.5.1.(4) 9.10.9.9.(1) |
347. |
MMAH |
Supplementary Standard SB-3, January 15, 2019 |
Fire and Sound Resistance of Building Assemblies |
5.8.1.3.(1) 5.8.1.3.(2) 9.10.3.1.(1) 9.10.5.1.(4) 9.11.1.3.(1) 9.11.1.3.(2) Table 9.11.1.4. 9.29.5.9.(5) |
348. |
MMAH |
Supplementary Standard SB-4, January 15, 2019 |
Measures for Fire Safety in High Buildings |
3.2.6.2.(1) 3.2.6.2.(6) 3.2.6.5.(3) 3.2.6.9.(1) Table 11.5.1.1.C. Table 11.5.1.1.D/E. Table 11.5.1.1.F. |
349. |
MMAH |
Supplementary Standard SB-6, September 14, 2012 |
Percolation Time and Soil Descriptions |
8.2.1.2.(2) |
350. |
MMAH |
Supplementary Standard SB-7, September 14, 2012 |
Guards for Housing and Small Buildings |
9.8.8.2.(5) |
351. |
MMAH |
Supplementary Standard SB-8, September 14, 2012 |
Design, Construction and Installation of Anchorage Systems for Fixed Access Ladders |
3.6.1.5.(1) |
352. |
MMAH |
Supplementary Standard SB-9, September 14, 2012 |
Requirements for Soil Gas Control |
9.13.4.1.(1) 9.13.4.2.(3) 9.13.4.2.(4) |
353. |
MMA |
Supplementary Standard SB-10, December 22, 2016 |
Energy Efficiency Requirements |
Table 9.7.3.3. 12.2.1.1.(2) 12.2.1.2.(2) 12.2.2.1.(1) 12.2.3.1.(1) |
354. |
MMAH |
Supplementary Standard SB-11, September 14, 2012 |
Construction of Farm Buildings |
1.3.1.2.(4) of Division A |
355. |
MMA |
Supplementary Standard SB-12, July 7, 2016 |
Energy Efficiency for Housing |
Table 9.7.3.3. Table 11.5.1.1.C. 12.2.1.1.(3) 12.2.1.2.(3) |
356. |
MMAH |
Supplementary Standard SB-13, September 14, 2012 |
Glass in Guards |
3.1.20.1.(1) |
357. |
MMAH |
Supplementary Standard SC-1, September 14, 2012 |
Code of Conduct for Registered Code Agencies |
3.7.4.1.(2) of Division C |
358. |
MOE |
PIBS 6879 2008 |
Design Guidelines for Sewage Works |
7.1.5.5.(2) |
359. |
MOE |
PIBS 6881e 2008 |
Design Guidelines for Drinking-Water Systems |
7.1.5.5.(1) |
360. |
NFPA |
2017 Publication |
National Fire Codes |
6.2.1.1.(1) |
361. |
NFPA |
13-2013 |
Installation of Sprinkler Systems |
3.1.9.1.(4) 3.2.4.9.(2) 3.2.4.17.(1) 3.2.5.13.(1) 3.2.8.4.(7) 3.3.2.12.(3) 3.16.1.1.(3) 3.16.1.1.(4) 3.16.1.6.(2) 3.16.1.6.(8) 3.16.1.7.(2) 3.16.2.1.(1) 3.16.2.2.(1) 3.16.3.1.(1) 9.10.9.6.(11) |
362. |
NFPA |
13D-2016 |
Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes |
3.2.5.13.(3) |
363. |
NFPA |
13R-2013 |
Installation of Sprinkler Systems in Low-Rise Residential Occupancies |
3.2.5.13.(2) |
364. |
NFPA |
14-2013 |
Installation of Standpipe and Hose Systems |
3.2.9.2.(1) |
365. |
NFPA |
20-2016 |
Installation of Stationary Pumps for Fire Protection |
3.2.4.10.(4) 3.2.5.19.(1) |
366. |
NFPA |
24-2013 |
Installation of Private Fire Service Mains and Their Appurtenances |
7.2.11.1.(1) |
367. |
NFPA |
68-2013 |
Explosion Protection by Deflagration Venting |
3.3.6.3.(1) 3.3.6.4.(2) 3.3.6.4.(4) |
368. |
NFPA |
72-2016 |
National Fire Alarm and Signaling Code |
3.2.4.22.(13) 9.10.19.1.(2) 9.10.19.3.(4) |
369. |
NFPA |
80-2013 |
Fire Doors and Other Opening Protectives |
3.1.8.5.(2) 3.1.8.10.(2) 3.1.8.14.(1) 3.1.9.1.(5) 3.13.3.1.(2) 9.10.9.6.(13) 9.10.13.1.(1) |
370. |
NFPA |
82-2014 |
Incinerators and Waste and Linen Handling Systems and Equipment |
6.2.6.1.(1) 9.10.10.5.(2) |
371. |
NFPA |
91-2010 |
Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids |
6.2.13.4.(1) |
372. |
NFPA |
96-2014 |
Ventilation Control and Fire Protection of Commercial Cooking Operations |
3.2.4.9.(2) 3.6.3.5.(1) 6.2.2.6.(1) |
373. |
NFPA |
105-2013 |
Smoke Door Assemblies and other Opening Protectives |
3.1.8.5.(3) 3.1.8.5.(6) |
374. |
NFPA |
130-2010 |
Fixed Guideway Transit and Passenger Rail Systems |
3.13.7.1.(1) |
375. |
NFPA |
211-2016 |
Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances |
6.3.1.2.(2) 6.3.1.3.(1) |
376. |
NFPA |
214-2011 |
Water-Cooling Towers |
6.2.3.14.(5) 6.2.3.14A.(4) |
377. |
NFPA |
701-2010 |
Fire Tests for Flame Propagation of Textiles and Films |
3.14.1.6.(1) |
378. |
NFRC |
100-2014 |
Determining Fenestration Product U-Factors |
12.3.1.2.(1) |
379. |
NFRC |
200-2014 |
Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence |
12.3.1.2.(1) |
380. |
NLGA |
2014 |
Standard Grading Rules for Canadian Lumber |
1.4.1.2.(1) of Division A 9.3.2.1.(1) Table 9.3.2.1. Tables A-1 to A-10 |
381. |
NRCan |
January 2005, including all amendments, revisions and supplements effective to May 31, 2006 |
EnerGuide for New Houses: Administrative and Technical Procedures |
12.2.1.1.(3) |
382. |
NSF |
NSF/ANSI 46-2010 |
Evaluation of Components and Devices Used in Wastewater Treatment Systems |
8.6.2.1.(2) |
383. |
NSF |
NSF/ANSI 61-2013 |
Drinking Water System Components - Health Effects |
7.2.10.7.(1) |
384. |
SMACNA |
ANSI/SMACNA 006-2006 |
HVAC Duct Construction Standards - Metal and Flexible |
6.2.4.2.(3) 6.2.4.3.(11) 6.2.4.3.(12) |
385. |
SPRI |
ANSI/GRHC/SPRI VR-1-2011 |
Procedure for Investigating Resistance to Root Penetration on Vegetative Roofs |
5.6.1.2.(4) |
386. |
TPIC |
2014 |
Truss Design Procedures and Specifications for Light Metal Plate Connected Wood Trusses |
9.23.13.11.(6) |
387. |
UL |
ANSI/UL 300-2005 |
Fire Extinguishing Systems for Protection of Commercial Cooking Equipment |
6.2.2.6.(2) |
388. |
UL |
ANSI/UL-1784-04 |
Air Leakage Tests of Door Assemblies and Other Opening Protectives |
3.1.8.4.(4) |
389. |
UL |
UL 2034-2008 |
Single and Multiple Station Carbon Monoxide Alarms |
6.2.12.3.(1) 9.33.4.3.(1) |
390. |
ULC |
CAN/ULC-S101-14 |
Fire Endurance Tests of Building Construction and Materials |
3.1.5.5A.(2) 3.1.5.12.(5) 3.1.5.12.(6) 3.1.5.12A.(3) 3.1.5.12A.(4) 3.1.7.1.(1) 3.1.11.7.(1) 3.2.3.8.(1) 3.2.6.5.(6) 9.10.16.3.(1) |
391. |
ULC |
CAN/ULC-S102-10 |
Test for Surface Burning Characteristics of Building Materials and Assemblies |
3.1.5.25.(1) 3.1.12.1.(1) Table 5.10.1.1. Table 9.23.16.2.A. |
392. |
ULC |
CAN/ULC-S102.2-10 |
Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies |
3.1.12.1.(2) 3.1.13.4.(1) |
393. |
ULC |
CAN/ULC-S102.3-07 |
Fire Test of Light Diffusers and Lenses |
3.1.13.4.(1) |
394. |
ULC |
CAN/ULC-S102.4-10 |
Test for Fire and Smoke Characteristics of Electrical Wiring, Cables and Non-Metallic Raceways |
3.6.4.3.(1) |
395. |
ULC |
CAN/ULC-S104-15 |
Fire Tests of Door Assemblies |
3.1.8.4.(1) 3.2.6.5.(3) |
396. |
ULC |
CAN/ULC-S105-16 |
Fire Door Frames Meeting the Performance Required by CAN/ULC-S104 |
9.10.13.6.(1) |
397. |
ULC |
CAN/ULC-S106-15 |
Fire Tests of Window and Glass Block Assemblies |
3.1.8.4.(1) |
398. |
ULC |
CAN/ULC-S107-10 |
Fire Tests of Roof Coverings |
3.1.15.1.(1) |
399. |
ULC |
CAN/ULC-S109-14 |
Flame Tests of Flame-Resistant Fabrics and Films |
3.1.16.1.(1) |
400. |
ULC |
CAN/ULC-S110-13 |
Test for Air Ducts |
6.2.3.2.(2) 6.2.3.2.(4) |
401. |
ULC |
CAN/ULC-S111-13 |
Fire Tests for Air Filter Units |
6.2.3.13.(1) 6.2.4.14.(1) |
402. |
ULC |
CAN/ULC-S112-10 |
Fire Test of Fire Damper Assemblies |
3.1.8.4.(1) |
403. |
ULC |
CAN/ULC-S112.1-10 |
Leakage Rated Dampers for Use in Smoke Control Systems |
3.1.8.4.(3) 6.2.3.9.(3) |
404. |
ULC |
CAN/ULC-S112.2-07 |
Fire Test of Ceiling Firestop Flap Assemblies |
3.1.9.5.(2) 3.6.4.3.(2) 9.10.13.14.(1) |
405. |
ULC |
CAN/ULC-S113-16 |
Wood Core Doors Meeting the Performance Required by CAN/ULC-S104 for Twenty Minute Fire Rated Closure Assemblies |
9.10.13.2.(1) |
406. |
ULC |
CAN/ULC-S114-05 |
Test for Determination of Non-Combustibility in Building Materials |
1.4.1.2.(1) of Division A |
407. |
ULC |
CAN/ULC-S115-11 |
Fire Tests of Firestop Systems |
3.1.5.16.(3) 3.1.9.1.(1) 3.1.9.1.(2) 3.1.9.1.(3) 3.1.9.3A.(1) 3.1.9.4.(3) 3.1.9.4.(7) 9.10.9.6.(2) 9.10.9.7.(3) |
408. |
ULC |
CAN/ULC-S124-06 |
Test for the Evaluation of Protective Coverings for Foamed Plastic |
3.1.5.12A.(2) |
409. |
ULC |
CAN/ULC-S126-14 |
Test for Fire Spread Under Roof-Deck Assemblies |
3.1.14.1.(1) 3.1.14.2.(1) |
410. |
ULC |
CAN/ULC-S134-13 |
Fire Test of Exterior Wall Assemblies |
3.1.5.5.(1) 3.2.3.7.(3) 3.2.3.7.(6) |
411. |
ULC |
S135-04 |
Test Method for the Determination of Combustibility Parameters of Building Materials Using an Oxygen Consumption Calorimeter (Cone Calorimeter) |
3.1.5.1.(2) |
412. |
ULC |
CAN/ULC-S138-06 |
Test for Fire Growth of Insulated Building Panels in a Full-Scale Room Configuration |
3.1.5.5A.(1) 3.1.5.5A.(3) |
413. |
ULC |
CAN/ULC-S139-12 |
Fire Test for Evaluation of Integrity of Electrical Power, Data and Optical Fibre Cables |
3.2.7.10.(2) 3.2.7.10.(3) |
414. |
ULC |
CAN/ULC-S143-14 |
Fire Tests for Non-Metallic Electrical and Optical Fibre Cable Raceway Systems |
3.1.5.20.(1) |
415. |
ULC |
CAN/ULC-S144-12 |
Fire Resistance Test - Grease Duct Assemblies |
3.6.3.5.(2) |
415.1 |
ULC |
CAN/ULC-S146-19 |
Test for the Evaluation of Encapsulation Materials and Assemblies of Materials for the Protection of Structural Timber Elements |
3.1.6.5.(1) |
416. |
ULC |
S505-1974 |
Fusible Links for Fire Protection Service |
3.1.8.9.(1) |
417. |
ULC |
S513-1978 |
Threaded Couplings for 38 mm and 65 mm Fire Hose |
3.2.9.2.(7) |
418. |
ULC |
CAN/ULC-S524-14 |
Installation of Fire Alarm Systems |
3.1.8.9A.(3) 3.1.8.12.(3) 3.2.4.5.(1) 3.2.4.22.(6) 3.2.4.22.(11) 9.10.19.4.(3) 9.10.19.6.(2) |
419. |
ULC |
CAN/ULC-S531-14 |
Smoke Alarms |
3.2.4.22.(1) 9.10.19.1.(1) |
420. |
ULC |
CAN/ULC-S537-13 |
Verification of Fire Alarm Systems |
3.2.4.5.(2) 3.2.4.22.(6) |
421. |
ULC |
CAN/ULC-S540-13 |
Residential Fire and Life Safety Warning Systems: Installation, Inspection, Testing and Maintenance |
3.2.4.22A.(1) 9.10.19.8.(1) |
422. |
ULC |
CAN/ULC-S543-09 |
Internal Lug Quick Connect Couplings for Fire Hose |
3.2.9.2.(7) |
423. |
ULC |
CAN/ULC-S553-14 |
Installation of Smoke Alarms |
3.2.4.22.(9) 9.10.19.3.(3) |
424. |
ULC |
CAN/ULC-S561-13 |
Installation and Services for Fire Signal Receiving Centres and Systems |
3.2.4.8.(4) 3.13.5.4.(1) |
425. |
ULC |
CAN/ULC-S572-17 |
Photoluminescent and Self-Luminous Exit Signs and Path Marking Systems |
3.4.5.1.(5) 9.9.11.3.(3) |
426. |
ULC |
CAN/ULC-S610-M87 |
Factory-Built Fireplaces |
9.22.8.1.(1) |
427. |
ULC |
S628-93 |
Fireplace Inserts |
9.22.10.1.(1) |
428. |
ULC |
CAN/ULC-S629-16 |
650ºC Factory-Built Chimneys |
9.21.1.2.(1) |
429. |
ULC |
CAN/ULC-S639-M87 |
Steel Liner Assemblies for Solid-Fuel Burning Masonry Fireplaces |
9.22.2.3.(1) |
430. |
ULC |
CAN/ULC-S701.1-17 |
Thermal Insulation, Polystyrene Boards |
Table 5.10.1.1. 9.15.4.1.(1) Table 9.23.16.2.A. 9.25.2.2.(1) 9.25.2.2.(4) |
431. |
ULC |
CAN/ULC-S702-14 |
Mineral Fibre Thermal Insulation for Buildings |
Table 5.10.1.1. Table 9.23.16.2.A. 9.25.2.2.(1) |
431.1 |
ULC |
CAN/ULC -S702.1-14 |
Standard for Mineral Fibre Thermal Insulation for Buildings, Part 1: Material Specification |
3.1.6.3.(4) |
432. |
ULC |
CAN/ULC-S703-09 |
Cellulose Fibre Insulation for Buildings |
Table 5.10.1.1. 9.25.2.2.(1) |
433. |
ULC |
CAN/ULC-S704-11 |
Thermal Insulation, Polyurethane and Polyisocyanurate, Boards, Faced |
Table 5.10.1.1. Table 9.23.16.2.A. 9.25.2.2.(1) |
434. |
ULC |
CAN/ULC-S705.1-15 |
Thermal Insulation - Spray Applied Rigid Polyurethane Foam, Medium Density - Material - Specification |
Table 5.10.1.1. 9.25.2.2.(1) |
435. |
ULC |
CAN/ULC-S705.2-05 |
Thermal Insulation - Spray Applied Rigid Polyurethane Foam, Medium Density - Application |
Table 5.10.1.1. 9.25.2.5.(1) |
436. |
ULC |
CAN/ULC-S706.1-16 |
Wood Fibre Insulating Boards for Buildings |
Table 5.10.1.1. 9.23.15.7.(3) Table 9.23.16.2.A. 9.25.2.2.(1) 9.29.8.1.(1) |
437. |
ULC |
CAN/ULC-S710.1-11 |
Thermal Insulation - Bead-Applied One Component Polyurethane Air Sealant Foam, Part 1: Material Specification |
Table 5.10.1.1. |
438. |
ULC |
CAN/ULC-S711.1-11 |
Thermal Insulation - Bead-Applied Two Component Polyurethane Air Sealant Foam, Part 1: Material Specification |
Table 5.10.1.1. |
439. |
ULC |
CAN/ULC-S716.1-12 |
Exterior Insulation and Finish Systems (EIFS) - Materials and Systems |
5.10.3.1.(1) 9.27.13.1.(1) 9.27.13.2.(1) |
440. |
ULC |
CAN/ULC-S716.2-12 |
Exterior Insulation and Finish Systems (EIFS) - Installation of EIFS Components and Water Resistive Barrier |
9.27.13.3.(2) |
441. |
ULC |
CAN/ULC-S716.3-12 |
Exterior Insulation and Finish Systems (EIFS) - Design Application |
9.27.13.3.(1) |
442. |
ULC |
CAN/ULC-S741-08 |
Air Barrier Materials - Specification |
5.4.1.2.(1) |
443. |
ULC |
CAN/ULC-S1001-11 |
Integrated Systems Testing of Fire Protection and Life Safety Systems |
3.2.10.1.(1) 9.10.18.10.(1) |
444. |
ULC |
ULC/ORD-C199P-2002 |
Combustible Piping for Sprinkler Systems |
3.2.5.14.(2) 3.2.5.14.(5) |
445. |
ULC |
ULC/ORD-C263.1-99 |
Sprinkler-Protected Window Systems |
3.1.8.18.(1) |
446. |
ULC |
ULC/ORD-C1254.6-1995 |
Fire Testing of Restaurant Cooking Area Fire Extinguishing System Units |
6.2.2.6.(2) |
447. |
USDA |
October 1993 |
Soil Survey Manual |
8.2.1.2.(2) |
448. |
WT |
October 20, 2016 |
Port Lands Flood Protection and Enabling Infrastructure Due Diligence Report |
1.3.3.6.(4) of Division C |
Notes to Table 1.3.1.2.:
(1) Some titles have been abridged to omit superfluous wording.
1.3.2. Abbreviations
1.3.2.1. Abbreviations of Proper Names
(1) In this Code, an abbreviation of proper names listed in Column 1 of Table 1.3.2.1. has the meaning assigned opposite it in Column 2.
Table 1.3.2.1.
Abbreviations of Proper Names
Item |
Column 1 Abbreviation |
Column 2 Meaning |
1. |
ACGIH |
American Conference of Governmental Industrial Hygienists |
2. |
AISI |
American Iron and Steel Institute |
3. |
ANSI |
American National Standards Institute |
3.1 |
APA |
The Engineered Wood Association |
4. |
APHA |
American Public Health Association |
4.1 |
ASCE |
American Society of Civil Engineers |
5. |
ASHRAE |
American Society of Heating, Refrigerating and Air-Conditioning Engineers |
6. |
ASME |
The American Society of Mechanical Engineers |
7. |
ASPE |
American Society of Plumbing Engineers |
8. |
ASSE |
American Society of Sanitary Engineering |
9. |
ASTM |
American Society for Testing and Materials |
11. |
AWS |
American Welding Society |
12. |
AWWA |
American Water Works Association |
13. |
BCMOH |
British Columbia Ministry of Health |
14. |
BNQ |
Bureau de Normalisation du Québec |
15. |
CAN |
National Standard of Canada designation The number or name following the CAN designation represents the agency under whose auspices the standard is issued. CAN1 designates CGA, CAN2 designates CGSB, CAN3 designates CSA, and CAN4 designates ULC. |
16. |
CCBFC |
Canadian Commission on Building and Fire Codes |
17. |
CGSB |
Canadian General Standards Board |
18. |
CSA |
Canadian Standards Association |
19. |
CWC |
Canadian Wood Council |
20. |
DBR |
Division of Building Research, known as the Institute for Research in Construction since 1985 |
21. |
EPA |
Environmental Protection Agency |
22. |
FINA |
Fédération Internationale de Natation |
22.1 |
GRHC |
Green Roofs for Healthy Cities |
23. |
HI |
Hydronics Institute |
23.1 |
HPVA |
Hardware Plywood & Veneer Association |
24. |
HRAI |
Heating, Refrigerating and Air-Conditioning Institute of Canada |
25. |
HUD |
U.S. Department of Housing and Urban Development |
26. |
HVI |
Home Ventilating Institute |
27. |
IAPMO |
International Association of Plumbing and Mechanical Officials |
28. |
IESNA |
Illuminating Engineering Society of North America |
29. |
ISO |
International Organization for Standardization |
29.1 |
MMA |
Ontario Ministry of Municipal Affairs |
30. |
MMAH |
Ontario Ministry of Municipal Affairs and Housing |
31. |
MOE |
Ontario Ministry of the Environment |
32. |
NFPA |
National Fire Protection Association |
33. |
NLGA |
National Lumber Grades Authority |
34. |
NRCan |
Natural Resources Canada |
35 |
NSF |
NSF International, formerly called National Sanitation Federation |
35.1 |
SEI |
Structural Engineering Institute |
36. |
SMACNA |
Sheet Metal and Air Conditioning Contractors National Association Inc. |
36.1 |
SPRI |
Single Ply Roofing Industry |
37. |
TC |
Transport Canada |
38. |
TPIC |
Truss Plate Institute of Canada |
39. |
UL |
Underwriters Laboratories Inc. |
40. |
ULC |
Underwriters’ Laboratories of Canada |
41. |
USDA |
United States Department of Agriculture |
42. |
WEF |
World Environment Federation |
43. |
WT |
Waterfront Toronto |
O. Reg. 332/12, Division B, Part 1; O. Reg. 332/12, Sentence 4.2.1.1.(2); O. Reg. 361/13, s. 3 (1-9, 11-19), 4; O. Reg. 191/14, ss. 3 (2), 5-7; O. Reg. 139/17, ss. 7, 8; O. Reg. 388/18, ss. 1, 2; O. Reg. 88/19, s. 3, 4; O. Reg. 762/20, s. 2, 3; O. Reg. 451/22, s. 2, 3; O. Reg. 30/23, s. 4; O. Reg. 89/23, s. 2.
Part 2
(Reserved)
Part 3
Fire Protection, Occupant Safety and Accessibility
Section |
3.1. |
General |
|
3.1.1. |
Scope |
|
3.1.2. |
Classification of Buildings or Parts of Buildings by Major Occupancy |
|
3.1.3. |
Multiple Occupancy Requirements |
|
3.1.4. |
Combustible Construction |
|
3.1.5. |
Noncombustible Construction |
|
3.1.6. |
Reserved |
|
3.1.6. |
Encapsulated Mass Timber Construction |
|
3.1.7. |
Fire-Resistance Ratings |
|
3.1.8. |
Fire Separations and Closures |
|
3.1.9. |
Penetrations in Fire Separations and Fire-Rated Assemblies |
|
3.1.10. |
Firewalls |
|
3.1.11. |
Fire Blocks in Concealed Spaces |
|
3.1.12. |
Flame-Spread Rating and Smoke Developed Classification |
|
3.1.13. |
Interior Finish |
|
3.1.14. |
Roof Assemblies |
|
3.1.15. |
Roof Covering |
|
3.1.16. |
Fabrics |
|
3.1.17. |
Occupant Load |
|
3.1.18. |
Drainage and Grades |
|
3.1.19. |
Above Ground Electrical Conductors |
|
3.1.20. |
Glass in Guards |
|
|
|
Section |
3.2. |
Building Fire Safety |
|
3.2.1. |
General |
|
3.2.2. |
Building Size and Construction Relative to Occupancy |
|
3.2.3. |
Spatial Separation and Exposure Protection |
|
3.2.4. |
Fire Alarm and Detection Systems |
|
3.2.5. |
Provisions for Firefighting |
|
3.2.6. |
Additional Requirements for High Buildings |
|
3.2.7. |
Lighting and Emergency Power Systems |
|
3.2.8. |
Mezzanines and Openings through Floor Assemblies |
|
3.2.9. |
Standpipe Systems |
|
3.2.10. |
Testing of Integrated Fire Protection and Life Safety Systems |
|
|
|
Section |
3.3. |
Safety Within Floor Areas |
|
3.3.1. |
All Floor Areas |
|
3.3.2. |
Assembly Occupancy |
|
3.3.3. |
Care, Care and Treatment or Detention Occupancy |
|
3.3.4. |
Residential Occupancy |
|
3.3.5. |
Industrial Occupancy |
|
3.3.6. |
Design of Hazardous Areas |
|
|
|
Section |
3.4. |
Exits |
|
3.4.1. |
General |
|
3.4.2. |
Number and Location of Exits from Floor Areas |
|
3.4.3. |
Width and Height of Exits |
|
3.4.4. |
Fire Separation of Exits |
|
3.4.5. |
Exit Signs |
|
3.4.6. |
Types of Exit Facilities |
|
3.4.7. |
Fire Escapes |
|
|
|
Section |
3.5. |
Vertical Transportation |
|
3.5.1. |
General |
|
3.5.2. |
Elevator Requirements |
|
3.5.3. |
Fire Separations |
|
3.5.4. |
Dimensions and Signs |
|
|
|
Section |
3.6. |
Service Facilities |
|
3.6.1. |
General |
|
3.6.2. |
Service Rooms |
|
3.6.3. |
Vertical Service Spaces and Service Facilities |
|
3.6.4. |
Horizontal Service Spaces and Service Facilities |
|
|
|
Section |
3.7. |
Health Requirements |
|
3.7.1. |
Height and Area of Rooms |
|
3.7.2. |
Windows |
|
3.7.3. |
Reserved |
|
3.7.4. |
Plumbing Facilities |
|
3.7.5. |
Health Care Facility Systems |
|
3.7.6. |
Food Premises |
|
|
|
Section |
3.8. |
Barrier-Free Design |
|
3.8.1. |
General |
|
3.8.2. |
Occupancy Requirements |
|
3.8.3. |
Design Standards |
|
|
|
Section |
3.9. |
Portable Classrooms |
|
3.9.1. |
Scope |
|
3.9.2. |
Interior Finish |
|
3.9.3. |
Application |
|
|
|
Section |
3.10. |
Self-Service Storage Buildings |
|
3.10.1. |
Scope |
|
3.10.2. |
Requirements for All Buildings |
|
3.10.3. |
Additional Requirements for Buildings Containing more than 1 Storey |
|
3.10.4. |
Additional Requirements for 1 Storey Buildings |
|
|
|
Section |
3.11. |
Public Pools |
|
3.11.1. |
General |
|
3.11.2. |
Designations of Public Pools |
|
3.11.3. |
Pool and Pool Deck Design and Construction Requirements for All Class A and Class B Pools |
|
3.11.4. |
Public Pools Equipped with Diving Boards or Diving Platforms |
|
3.11.5. |
Ramps into Public Pools in Group B, Division 2 or 3, Major Occupancies |
|
3.11.5. |
Ramps into Public Pools |
|
3.11.6. |
Modified Pools |
|
3.11.7. |
Wave Action Pools |
|
3.11.8. |
Recirculation for Public Pools |
|
3.11.9. |
Dressing Rooms, Locker Facilities and Plumbing Facilities for All Public Pools |
|
3.11.10. |
Emergency Provisions for All Public Pools |
|
3.11.11. |
Service Rooms and Storage for All Public Pools |
|
|
|
Section |
3.12. |
Public Spas |
|
3.12.1. |
General |
|
3.12.2. |
Public Spa and Deck Design and Construction Requirements |
|
3.12.3. |
Ramps into Public Spas |
|
3.12.3. |
Ramps and Access into Public Spas |
|
3.12.4. |
Water Circulation for Public Spas |
|
3.12.5. |
Emergency Provisions for All Public Spas |
|
3.12.6. |
Service Rooms and Storage for All Public Spas |
|
|
|
Section |
3.13. |
Rapid Transit Stations |
|
3.13.1. |
Scope and Definitions |
|
3.13.2. |
Construction Requirements |
|
3.13.3. |
Safety Requirements Within Stations |
|
3.13.4. |
Means of Egress |
|
3.13.5. |
Fire Safety Provisions |
|
3.13.6. |
Required Sanitary Facilities |
|
3.13.7. |
Emergency Ventilation |
|
3.13.8. |
Barrier-Free Design |
|
|
|
Section |
3.14. |
Tents and Air-Supported Structures |
|
3.14.1. |
Tents |
|
3.14.2. |
Air-Supported Structures |
|
|
|
Section |
3.15. |
Signs |
|
3.15.1. |
Scope |
|
3.15.2. |
Alterations |
|
3.15.3 |
Structural Requirements |
|
3.15.4. |
Plastic Sign Facing Materials |
|
3.15.5 |
Location Restrictions |
|
|
|
Section |
3.16. |
Shelf and Rack Storage Systems |
|
3.16.1. |
Scope |
|
3.16.2. |
Storage of Class I, II, III and IV Commodities |
|
3.16.3. |
Storage of Group A, B and C Plastics and Rubber Tires |
|
|
|
Section |
3.16A. |
Demountable Stages and Demountable Support Structures |
|
3.16A.1. |
Scope |
|
3.16A.1.1. |
Application |
|
3.16A.2. |
Construction |
|
3.16A.2.1. |
Occupant Load |
|
3.16A.2.2. |
Means of Egress |
|
3.16A.2.3. |
Guards |
|
3.16A.2.4. |
Clearance to Other Structures |
|
3.16A.2.5. |
Flame Resistance |
|
3.16A.2.6. |
Provision for Firefighting |
|
3.16A.2.7. |
Electrical Systems |
|
3.16A.2.8. |
Structural Provisions |
|
3.16A.2.9. |
Barrier-Free Design |
|
|
|
Section |
3.17. |
Additional Requirements for Existing Buildings |
|
3.17.1. |
Scope |
|
3.17.2. |
Additional Construction |
Section 3.1. General
3.1.1. Scope
3.1.1.1. Scope
(1) The scope of this Part shall be as described in Subsection 1.1.2. of Division A.
3.1.1.2. Radon
(1) In addition to all other requirements, a building in the following designated areas shall be designed and constructed so that the annual average concentration of radon 222 does not exceed 200 Bq/m3 of air and the annual average concentration of the short lived daughters of radon 222 does not exceed 0.02 working levels inside the building:
(a) the City of Elliot Lake in the Territorial District of Algoma,
(b) the Township of Faraday in the County of Hastings, and
(c) the geographic Township of Hyman in the Territorial District of Sudbury.
3.1.1.3. Building in Flood Plains
(1) Buildings constructed on flood plains shall,
(a) be designed and constructed in accordance with good engineering practice to withstand anticipated vertical and horizontal hydrostatic pressures acting on the structure, and
(b) incorporate floodproofing measures that will preserve the integrity of exits and means of egress during times of flooding.
3.1.2. Classification of Buildings or Parts of Buildings by Major Occupancy
3.1.2.1. Classification of Buildings
(1) Except as provided by Articles 3.1.2.3. to 3.1.2.7., every building or part of it shall be classified according to its major occupancy as belonging to one of the Groups or Divisions described in Table 3.1.2.1.
(2) A building intended for use by more than one major occupancy shall be classified according to all major occupancies for which it is used or intended to be used.
Table 3.1.2.1.
Major Occupancy Classification
Forming Part of Sentences 3.1.2.1.(1), 3.1.2.2.(1) and 3.11.2.1.(3)
Item |
Column 1 Group |
Column 2 Division |
Column 3 Description of Major Occupancies |
1. |
A |
1 |
Assembly occupancies intended for the production and viewing of the performing arts |
2. |
A |
2 |
Assembly occupancies not elsewhere classified in Group A |
3. |
A |
3 |
Assembly occupancies of the arena type |
4. |
A |
4 |
Assembly occupancies in which occupants are gathered in the open air |
5. |
B |
1 |
Detention occupancies |
6. |
B |
2 |
Care and treatment occupancies |
7. |
B |
3 |
Care occupancies |
8. |
C |
--- |
Residential occupancies |
9. |
D |
--- |
Business and personal services occupancies |
10. |
E |
--- |
Mercantile occupancies |
11. |
F |
1 |
High hazard industrial occupancies |
12. |
F |
2 |
Medium hazard industrial occupancies |
13. |
F |
3 |
Low hazard industrial occupancies |
3.1.2.2. Occupancies of the Same Classification
(1) Any building is deemed to be occupied by a single major occupancy, notwithstanding its use for more than one major occupancy, provided that all occupancies are classified as belonging to the same Group classification or, where the Group is divided into Divisions, as belonging to the same Division classification described in Table 3.1.2.1.
3.1.2.3. Arena Type Buildings
(1) An arena type building intended for occasional use for trade shows and similar exhibition purposes shall be classified as Group A, Division 3 occupancy.
3.1.2.4. Police Stations
(1) A police station with detention quarters is permitted to be classified as a Group B, Division 2 major occupancy provided the station is not more than 1 storey in building height and 600 m2 in building area.
3.1.2.5. Group B, Division 3 Occupancies
(1) Group B, Division 3 occupancies are permitted to be classified as Group C major occupancies provided,
(a) the occupants live as a single housekeeping unit in a suite with sleeping accommodation for not more than 10 persons, and
(b) not more than two occupants require assistance in evacuation in case of an emergency.
3.1.2.6. Restaurants
(1) A restaurant is permitted to be classified as a Group E major occupancy provided the restaurant is designed to accommodate not more than 30 persons consuming food or drink.
3.1.2.7. Storage of Combustible Fibres
(1) Buildings or parts of them used for the storage of baled combustible fibres shall be classified as medium hazard industrial occupancies.
3.1.3. Multiple Occupancy Requirements
3.1.3.1. Separation of Major Occupancies
(1) Except as provided by Sentences (2) to (5), major occupancies shall be separated from adjoining major occupancies by fire separations having fire-resistance ratings conforming to Table 3.1.3.1.
Table 3.1.3.1.
Major Occupancy Fire Separations(1)
Forming Part of Sentence 3.1.3.1.(1)
Item |
Column 1 |
Col. 2 |
Col. 3 |
Col. 4 |
Col. 5 |
Col. 6 |
Col. 7 |
Col. 8 |
Col. 9 |
Col. 10 |
Col. 11 |
Col. 12 |
Col. 13 |
Col. 14 |
|
Major Occupancy |
Minimum Fire-Resistance Rating of Fire Separation, h (1) |
|
|
|
|
|
|||||||
Adjoining Major Occupancy |
|
|
|
|
|
|
|
|
|
|||||
A-1 |
A-2 |
A-3 |
A-4 |
B-1 |
B-2 |
B-3 |
C |
D |
E |
F-1 |
F-2 |
F-3 |
||
1. |
A-1 |
N/A |
1 |
1 |
1 |
2 |
2 |
2 |
1 |
1 |
2 |
N/A |
2 |
1 |
2. |
A-2 |
1 |
N/A |
1 |
1 |
2 |
2 |
2 |
1(2) |
1(3) |
2 |
N/A |
2 |
1 |
3. |
A-3 |
1 |
1 |
N/A |
1 |
2 |
2 |
2 |
1 |
1 |
2 |
N/A |
2 |
1 |
4. |
A-4 |
1 |
1 |
1 |
N/A |
2 |
2 |
2 |
1 |
1 |
2 |
N/A |
2 |
1 |
5. |
B-1 |
2 |
2 |
2 |
2 |
N/A |
2 |
2 |
2 |
2 |
2 |
N/A |
2 |
2 |
6. |
B-2 |
2 |
2 |
2 |
2 |
2 |
N/A |
1 |
2 |
2 |
2 |
N/A |
2 |
2 |
7. |
B-3 |
2 |
2 |
2 |
2 |
2 |
1 |
N/A |
2 |
2 |
2 |
N/A |
2 |
2 |
8. |
C |
1 |
1(2) |
1 |
1 |
2 |
2 |
2 |
N/A |
1 |
2(4) |
N/A |
2 |
1 |
9. |
D |
1 |
1(3) |
1 |
1 |
2 |
2 |
2 |
1 |
N/A |
N/A |
3 |
N/A |
N/A |
10. |
E |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2(4) |
N/A |
N/A |
3 |
N/A |
N/A |
11. |
F-1 |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
3 |
3 |
N/A |
2 |
2 |
12. |
F-2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
N/A |
N/A |
2 |
N/A |
N/A |
13. |
F-3 |
1 |
1 |
1 |
1 |
2 |
2 |
2 |
1 |
N/A |
N/A |
2 |
N/A |
N/A |
Notes to Table 3.1.3.1.:
(1) Section 3.3. contains requirements for the separation of occupancies and tenancies that are in addition to the requirements for the separation of major occupancies.
(2) See Sentence 3.1.3.1.(3).
(3) See Sentence 3.1.3.1.(4).
(4) See Sentence 3.1.3.1.(2).
(2) In a building not more than 3 storeys in building height, if not more than two dwelling units are contained together with a Group E major occupancy, the fire-resistance rating of the fire separation between the two major occupancies need not be more than 1 h.
(3) In a building within the scope of Article 3.2.2.42A. or Article 3.2.2.43A., a fire separation with a 2 h fire-resistance rating is required between the Group C and Group A, Division 2 major occupancies.
(4) In a building within the scope of Article 3.2.2.49A. or Article 3.2.2.50A., a fire separation with a 2 h fire-resistance rating is required between the Group D and Group A, Division 2 major occupancies.
(4.1) In a building within the scope of Article 3.2.2.42A., a fire separation with a 2 h fire-resistance rating is required between the Group C major occupancy and storage garage.
(4.2) In a building within the scope of Article 3.2.2.49A., a fire separation with a 1 h fire-resistance rating is required between the Group D and Group E or Group F, Division 2 or 3 major occupancies.
(5) The fire separations required between major occupancies in Sentence (1) are permitted to be penetrated by floor openings protected in conformance with Subsection 3.2.8., except for fire separations for Group F, Division 1 major occupancies and for mezzanines described in Sentence 3.2.8.2.(1).
3.1.3.2. Prohibition of Occupancy Combinations
(1) No major occupancy of Group F, Division 1 shall be contained within a building with any occupancy classified as Group A, B or C.
(2) Except as provided in Sentence (4) and Sentence 3.10.2.4.(9), not more than one suite of residential occupancy shall be contained within a building classified as a Group F, Division 2 major occupancy.
(3) A sleeping room or sleeping area shall not open directly into a room or area where food is intended to be stored, prepared, processed, distributed, served, sold or offered for sale.
(4) A Group F, Division 2 major occupancy is permitted in a building containing only live/work units if the occupancy is for the exclusive use of the occupants of the live/work units.
(5) A building within the scope of Article 3.2.2.43A. or 3.2.2.50A. shall not contain,
(a) a Group A, Division 1 or 3, Group B, or Group F, Division 1 or 2 major occupancy,
(b) a Group A, Division 2 or a Group E major occupancy above the second storey,
(b.1) a retirement home, or
(c) except as permitted by Sentence (6), a Group F, Division 3 major occupancy.
(6) A storage garage below the third storey is permitted in a building within the scope of Article 3.2.2.43A. or 3.2.2.50A.
3.1.4. Combustible Construction
3.1.4.1. Combustible Materials Permitted
(1) Except as required by this Part, a building permitted to be of combustible construction is permitted to be constructed of combustible materials, with or without noncombustible components.
3.1.4.2. Protection of Foamed Plastics
(1) Except as permitted in Sentence (3), foamed plastics that form part of a wall or ceiling assembly in combustible construction shall be protected from adjacent spaces in the building, other than adjacent concealed spaces within attic or roof spaces, crawl spaces, and wall and ceiling assemblies, by any of the following:
(a) one of the interior finishes described in Subsections 9.29.4. to 9.29.9.,
(b) provided the building does not contain a Group A, Group B or Group C major occupancy, sheet metal that,
(i) is mechanically fastened to the supporting assembly independent of the insulation,
(ii) is not less than 0.38 mm thick, and
(iii) has a melting point not less than 650°C, or
(c) any thermal barrier that meets the requirements of Sentence 3.1.5.12A.(2).
(2) The flame-spread rating on any exposed surface of combustible insulation, or any surface that would be exposed by cutting through it in any direction, shall be not more than 500.
(3) A walk-in cooler or freezer consisting of factory-assembled wall, floor or ceiling panels containing foamed plastics is permitted to be used in a building permitted to be of combustible construction, provided the panels,
(a) are protected on both sides by sheet metal not less than 0.38 mm thick having a melting point not less than 650°C,
(b) do not contain an air space, and
(c) when a sample panel with an assembled joint typical of field installation is subjected to the applicable test described in Subsection 3.1.12., have a flame-spread rating not more than that permitted for the space in which they are located, the space that they bound, or the walls of the building to which the cooler or freezer is attached, as applicable.
(4) The flame-spread rating of doors containing foamed plastics shall comply with Sentences 3.1.13.2.(1) to (3).
3.1.4.3. Wires and Cables
(1) Except as permitted by Sentences (2) and (3), optical fibre cables and electrical wires and cables with combustible insulation, jackets or sheathes installed in a building permitted to be of combustible construction shall,
(a) not convey flame or continue to burn for more than 1 min when tested in conformance with the Vertical Flame Test in Clause 4.11.1. of CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables” (FT1 Rating), or
(b) be located in,
(i) totally enclosed noncombustible raceways,
(ii) concealed spaces in walls,
(iii) concrete slabs, or
(iv) totally enclosed nonmetallic raceways conforming to Clause 3.1.5.20(1)(b).
(2) The requirement in Clause (1)(a) is considered to be met where the wires and cables,
(a) exhibit a vertical char of not more than 1.5 m when tested in conformance with the Vertical Flame Test – Cables in Cabletrough in Clause 4.11.4. of CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables” (FT4 Rating), or
(b) exhibit a flame-spread of not more than 1.5 m, a smoke density of not more than 0.5 at peak optical density and a smoke density not more than 0.15 at average optical density when tested in conformance with the Flame and Smoke Test in the Appendix to CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables” (FT6 Rating).
(3) Service-entrance cables for communication and community antennae distribution systems need not conform to Sentence (1) provided,
(a) the service-entrance cables are located in a building permitted to be of combustible construction and are not more than 3 m in length from the point of entry into the building or from the point of leaving protection as required in Clause (1)(b), or
(b) the service-entrance cables enter into an electrical or telephone service room separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
3.1.4.4. Nonmetallic Raceways
(1) Totally enclosed nonmetallic raceways used in a plenum in a building permitted to be of combustible construction shall meet the requirements of Clause 3.1.5.20.(1)(a).
3.1.4.5. Fire-Retardant Treated Wood
(1) If fire-retardant treated wood is specified in this Part, the wood shall,
(a) be pressure impregnated with fire-retardant chemicals in conformance with CAN/CSA-O80 Series, “Wood Preservation”, and
(b) have a flame-spread rating not more than 25.
3.1.4.6. Heavy Timber Construction Alternative
(1) If combustible construction is permitted and is not required to have a fire-resistance rating more than 45 min, heavy timber construction is permitted to be used.
(2) If heavy timber construction is permitted, it shall conform to Article 3.1.4.7.
3.1.4.7. Heavy Timber Construction
(1) Wood elements in heavy timber construction shall be arranged in heavy solid masses and with essentially smooth flat surfaces to avoid thin sections and sharp projections.
(2) Except as permitted by Sentences (3) to (6) and (12), the minimum dimensions of wood elements in heavy timber construction shall conform to Table 3.1.4.7.
Table 3.1.4.7.
Heavy Timber Dimensions
Forming Part of Sentence 3.1.4.7.(2)
Item |
Column 1 Supported Assembly |
Column 2 Structural Element |
Column 3 Solid Sawn (width × depth), mm × mm |
Column 4 Glued-Laminated (width × depth), mm × mm |
Column 5 Round (diam), mm |
1. |
Roofs only |
Columns |
140 × 191 |
130 × 190 |
180 |
|
|
Arches supported on the tops of walls or abutments |
89 × 140 |
80 × 152 |
--- |
|
|
Beams, girders and trusses |
89 × 140 |
80 × 152 |
--- |
|
|
Arches supported at or near the floor line |
140 × 140 |
130 × 152 |
--- |
2. |
Floors, floors plus roofs |
Columns |
191 × 191 |
175 × 190 |
200 |
|
|
Beams, girders, trusses and arches |
140 × 241 or 191 × 191 |
130 × 228 or 175 × 190 |
--- |
(3) Where splice plates are used at splices of roof arches supported on the tops of walls or abutments, roof trusses, roof beams and roof girders in heavy timber construction, they shall be not less than 64 mm thick.
(4) Floors in heavy timber construction shall be of glued-laminated or solid sawn plank not less than,
(a) 64 mm thick, splined or tongued and grooved, or
(b) 38 mm wide and 89 mm deep set on edge and well-spiked together.
(5) Floors in heavy timber construction shall be laid,
(a) so that no continuous line of end joints will occur except at points of support, and covered with,
(i) tongued and grooved flooring not less than 19 mm thick laid cross-wise or diagonally, or
(ii) tongued and grooved phenolic-bonded plywood, strandboard or waferboard not less than 12.5 mm thick, and
(b) not closer than 15 mm to the walls to provide for expansion, with the gap covered at the top or bottom.
(6) Roofs in heavy timber construction shall be of tongued and grooved phenolic-bonded plywood, strandboard or waferboard not less than 28 mm thick, or glued-laminated or solid sawn plank that is,
(a) not less than 38 mm thick, splined or tongued and grooved, or
(b) not less than 38 mm wide and 64 mm deep set on edge and laid so that no continuous line of end joints will occur except at the points of support.
(7) Wood columns in heavy timber construction shall be continuous or superimposed throughout all storeys.
(8) Superimposed wood columns in heavy timber construction shall be connected by,
(a) reinforced concrete or metal caps with brackets,
(b) steel or iron caps with pintles and base plates, or
(c) timber splice plates fastened to the columns by metal connectors housed within the contact faces.
(9) Where beams and girders in heavy timber construction enter masonry, wall plates, boxes of the self-releasing type or hangers shall be used.
(10) Wood girders and beams in heavy timber construction shall be closely fitted to columns, and adjoining ends shall be connected by ties or caps to transfer horizontal loads across the joints.
(11) In heavy timber construction, intermediate wood beams used to support a floor shall be supported on top of the girders or on metal hangers into which the ends of the beams are closely fitted.
(12) Roof arches supported on the tops of walls or abutments, roof trusses, roof beams and roof girders in heavy timber construction are permitted to be not less than 64 mm wide provided,
(a) where two or more spaced members are used, the intervening spaces are,
(i) blocked solidly throughout, or
(ii) tightly closed by a continuous wood cover plate not less than 38 mm thick secured to the underside of the members, or
(b) the space below the roof deck or sheathing is sprinklered.
3.1.4.8. Cladding
(1) Except as provided in Sentence (2), not less than 90% of the exterior cladding on each exterior wall of buildings conforming to Article 3.2.2.43A. or 3.2.2.50A. shall consist of,
(a) noncombustible cladding, or
(b) a wall assembly that satisfies the criteria of Clause 3.1.5.5.(1)(b).
(2) Where a building is considered to face one street in accordance with Clause 3.2.2.10.(3)(b), the exterior cladding on each exterior wall of buildings conforming to Article 3.2.2.43A. or 3.2.2.50A. shall consist of,
(a) noncombustible cladding, or
(b) a wall assembly that satisfies the criteria of Clause 3.1.5.5.(1)(b).
(3) A wall assembly conforming to Clause (1)(b) or (2)(b) that includes combustible cladding made of fire-retardant-treated wood shall be tested for fire exposure after the cladding has been subjected to the accelerated weathering test specified in ASTM D2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing”.
3.1.4.9. Revoked: O. Reg. 89/23, s. 4.
3.1.5. Noncombustible Construction
3.1.5.1. Noncombustible Materials
(1) Except as permitted by Sentences (2) to (4) and Articles 3.1.5.2. to 3.1.5.25., 3.1.13.4. and 3.2.2.16., a building or part of a building required to be of noncombustible construction, shall be constructed with noncombustible materials.
(2) Notwithstanding the definition for noncombustible materials stated in Article 1.4.1.2. of Division A, a material is permitted to be used in noncombustible construction provided that, when tested in accordance with ULC S135, “Test Method for the Determination of Combustibility Parameters of Building Materials Using an Oxygen Consumption Calorimeter (Cone Calorimeter)”, at a heat flux of 50 kW/m2,
(a) its average total heat release is not more than 3 MJ/m2,
(b) its average total smoke extinction area is not more than 1.0 m2, and
(c) the test duration is extended beyond the time stipulated in the referenced standard until it is clear that there is no further release of heat or smoke.
(3) If a material referred to in Sentence (2) consists of a number of discrete layers and testing reveals that the surface layer or layers protect the underlying layers such that the complete combustion of the underlying layers does not occur, the test shall be repeated by removing the outer layers sequentially until all layers have been exposed during testing, or until complete combustion has occurred.
(4) The acceptance criteria for a material tested in accordance with Sentence (3) shall be based on the cumulative emissions from all layers, which must not exceed the criteria stated in Clauses (2)(a) and (b).
3.1.5.2. Minor Combustible Components
(1) The following minor combustible components are permitted in a building required to be of noncombustible construction:
(a) paint,
(b) self-adhesive tapes, mastics and caulking materials applied to provide flexible seals between the major components of exterior wall construction,
(c) fire stops conforming to Sentence 3.1.9.1.(1) and fire blocks conforming to Article 3.1.11.7.,
(d) tubing for pneumatic controls provided it has an outside diameter not more than 10 mm,
(e) adhesives, vapour barriers and sheathing papers,
(f) electrical outlet and junction boxes,
(g) wood blocking within wall assemblies intended for the attachment of handrails, fixtures, and similar items mounted on the surface of the wall, and
(h) similar minor components.
3.1.5.3. Combustible Roofing Materials
(1) Combustible roof covering that has an A, B or C classification determined in conformance with Subsection 3.1.15. is permitted on a building required to be of noncombustible construction.
(2) Combustible roof sheathing and roof sheathing supports installed above a concrete deck are permitted on a building required to be of noncombustible construction provided,
(a) the concrete deck is not less than 50 mm thick,
(b) the height of the roof space above the deck is not more than 1 000 mm,
(c) the roof space is divided into compartments by fire blocks in conformance with Article 3.1.11.5.,
(d) openings through the concrete deck, other than for noncombustible roof drains and plumbing piping, are protected by masonry or concrete shafts,
(i) constructed as fire separations having a fire-resistance rating not less than 1 h, and
(ii) extending from the concrete deck to not less than 150 mm above the adjacent roof sheathing,
(e) the perimeter of the roof is protected by a noncombustible parapet extending from the concrete deck to not less than 150 mm above the adjacent sheathing, and
(f) except as permitted by Clause (d), the roof space does not contain any building services.
(3) Combustible cant strips, roof curbs, nailing strips and similar components used in the installation of roofing are permitted on a building required to be of noncombustible construction.
(4) Wood nailer facings to parapets, not more than 600 mm high, are permitted on a building required to be of noncombustible construction, if the facings and any roof membranes covering the facings are protected by sheet metal.
3.1.5.4. Combustible Glazing and Skylights
(1) Combustible skylight assemblies are permitted in a building required to be of noncombustible construction if the assemblies have a flame-spread rating not more than,
(a) 150, provided the assemblies,
(i) have an individual area not more than 9 m2,
(ii) have an aggregate horizontal projected area of the openings through the ceiling not more than 25% of the area of the ceiling of the room or space in which they are located, and
(iii) are spaced not less than 2 500 mm from adjacent assemblies and 1 200 mm from required fire separations, or
(b) 75, provided the assemblies,
(i) have an individual area not more than 27 m2,
(ii) have an aggregate horizontal projected area of the openings through the ceiling not more than 33% of the area of the ceiling of the room or space in which they are located, and
(iii) are spaced not less than 1 200 mm from adjacent assemblies and from required fire separations.
(2) Combustible vertical glazing installed no higher than the second storey is permitted in a building required to be of noncombustible construction.
(3) Except as permitted by Sentence (4), the combustible vertical glazing permitted by Sentence (2) shall have a flame-spread rating not more than 75.
(4) The flame-spread rating of combustible glazing in Sentence (2) is permitted to be not more than 150 if the aggregate area of glazing is not more than 25% of the wall area of the storey in which it is located, and,
(a) the glazing is installed in a building not more than 1 storey in building height,
(b) the glazing in the first storey is separated from the glazing in the second storey in accordance with the requirements of Article 3.2.3.17. for opening protection, or
(c) sprinklers are installed in,
(i) any storey with combustible glazing, and
(ii) the storey immediately above the storey with combustible glazing.
(5) Combustible window sashes and frames are permitted in a building required to be of noncombustible construction provided,
(a) each window in an exterior wall face is an individual unit separated by a wall of noncombustible construction from every other opening in the exterior wall,
(b) windows in exterior walls in contiguous storeys are separated by not less than 1 000 mm of noncombustible construction, and
(c) the aggregate area of openings in an exterior wall face of a fire compartment is not more than 40% of the area of the wall face.
3.1.5.5. Combustible Components for Exterior Walls
(1) Except as provided in Sentences (2) and (4), combustible components are permitted to be used for an exterior non-loadbearing wall assembly in a building required to be of noncombustible construction, provided that,
(a) the building is,
(i) not more than 3 storeys in building height, or
(ii) not more than 6 storeys in building height if sprinklered,
(b) when tested in accordance with CAN/ULC-S134, "Fire Test of Exterior Wall Assemblies", the wall assembly satisfies the following criteria for testing and conditions of acceptance:
(i) flaming on or in the wall assembly does not spread more than 5 m above the opening, and
(ii) the heat flux during the flame exposure on the wall assembly is not more than 35 kW/m2 measured at 3.5 m above the opening, and
(c) the interior surfaces of the wall assembly are protected by a thermal barrier conforming to Sentence 3.1.5.12.(5).
(2) Except as permitted by Articles 3.2.3.10. and 3.2.3.11., where the limiting distance in Tables 3.2.3.1.B. to 3.2.3.1.E. permits an area of unprotected openings of not more than 10% of the exposing building face, the construction requirements of Table 3.2.3.7. shall be met.
(3) A wall assembly permitted by Sentence (1) that includes combustible cladding of fire-retardant treated wood shall be tested for fire exposure after the cladding has been subjected to an accelerated weathering test as specified in ASTM D2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing”.
(4) The requirements of this Article do not apply where foamed plastic insulation is used in an exterior wall assembly of a building and the insulation is protected in conformance with Sentences 3.2.3.8.(1) and (2).
3.1.5.5A. Factory-Assembled Panels
(1) Except as permitted in Sentence (2), factory-assembled wall and ceiling panels containing foamed plastic insulation with a flame-spread rating not more than 500 are permitted to be used in a building required to be of noncombustible construction, provided that,
(a) the building,
(i) is sprinklered,
(ii) is not more than 18 m high, measured from grade to the underside of the roof, and
(iii) does not contain a Group A, Group B or Group C major occupancy, and
(b) the panels,
(i) do not contain an air space,
(ii) when tested in accordance with CAN/ULC-S138, “Test for Fire Growth of Insulated Building Panels in a Full-Scale Room Configuration”, meet the criteria set out in that document, and
(iii) when a sample panel with an assembled joint typical of field installation is subjected to the applicable test described in Subsection 3.1.12., have a flame-spread rating not more than that permitted for the room or space that they bound.
(2) Factory-assembled exterior wall panels containing thermosetting foamed plastic insulation are permitted to be used in a building required to be of noncombustible construction, provided that,
(a) the building,
(i) is not more than 18 m high, measured from grade to the underside of the roof, and
(ii) does not contain a Group B or Group C major occupancy, and
(b) the wall panels,
(i) do not contain an air space,
(ii) are protected on both sides by sheet steel not less than 0.38 mm thick,
(iii) remain in place for not less than 10 min when tested in accordance with CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials”, where the exposed surface includes typical vertical and horizontal joints, and
(iv) when a sample panel with an assembled joint typical of field installation is subjected to the applicable test described in Subsection 3.1.12., have a flame-spread rating not more than that permitted for the room or space that they bound.
(3) A walk-in cooler or freezer consisting of factory-assembled wall, floor or ceiling panels containing foamed plastic insulation with a flame-spread rating not more than 500 is permitted to be used in a building required to be of noncombustible construction, provided that,
(a) the building is sprinklered,
(b) the panels,
(i) are protected on both sides by sheet metal not less than 0.38 mm thick with a melting point not less than 650°C,
(ii) do not contain an air space,
(iii) when tested in accordance with CAN/ULC-S138, “Test for Fire Growth of Insulated Building Panels in a Full-Scale Room Configuration”, meet the criteria set out in that document, and
(iv) when a sample panel with an assembled joint typical of field installation is subjected to the applicable test described in Subsection 3.1.12., have a flame-spread rating not more than that permitted for the space in which they are located, the space that they bound, or the walls of the building to which the cooler or freezer is attached, as applicable.
3.1.5.6. Nailing Elements
(1) Wood nailing elements attached directly to or set into a continuous noncombustible backing for the attachment of interior finishes, are permitted in a building required to be of noncombustible construction provided the concealed space created by the wood elements is not more than 50 mm thick.
3.1.5.7. Combustible Millwork
(1) Combustible millwork, including interior trim, doors and door frames, show windows together with their frames, aprons and backing, handrails, shelves, cabinets and counters, is permitted in a building required to be of noncombustible construction.
3.1.5.8. Combustible Flooring Elements
(1) Combustible stage flooring supported on noncombustible structural members is permitted in a building required to be of noncombustible construction.
(2) Wood members more than 50 mm but not more than 375 mm high applied directly to or set into a noncombustible floor slab are permitted for the construction of a raised platform in a building required to be of noncombustible construction provided the concealed spaces created are divided into compartments by fire blocks in conformance with Sentence 3.1.11.3.(2).
(3) The floor system for the raised platform referred to in Sentence (2) is permitted to include combustible subfloor and combustible finished flooring.
(4) Combustible finished flooring is permitted in a building required to be of noncombustible construction.
3.1.5.9. Combustible Stairs in Dwelling Units
(1) Combustible stairs are permitted in a dwelling unit in a building required to be of noncombustible construction.
3.1.5.10. Combustible Interior Finish
(1) Except as provided in Sentences (2) and (3), combustible interior wall and ceiling finishes described in Clause 3.1.13.1.(1)(b) that are not more than 1 mm thick are permitted in a building required to be of noncombustible construction.
(2) Combustible interior wall finishes, other than foamed plastics, that are not more than 25 mm thick are permitted in a building required to be of noncombustible construction, provided they have a flame-spread rating not more than 150 on any exposed surface or any surface that would be exposed by cutting through the material in any direction.
(3) Except as provided in Sentence (4), combustible interior ceiling finishes, other than foamed plastics, that are not more than 25 mm thick are permitted in a building required to be of noncombustible construction, provided that,
(a) they have a flame-spread rating not more than 25 on any exposed surface or on any surface that would be exposed by cutting through the material in any direction, and
(b) not more than 10% of the ceiling area within each fire compartment where such finishes are installed has a flame-spread rating not more than 150.
(4) Combustible interior ceiling finishes made of fire-retardant treated wood are permitted in a building required to be of noncombustible construction, provided they are not more than 25 mm thick or are exposed fire-retardant treated wood battens.
3.1.5.11. Gypsum Board
(1) Gypsum board with a tightly adhering paper covering not more than 1 mm thick is permitted in a building required to be of noncombustible construction provided the flame-spread rating of the surface is not more than 25.
3.1.5.12. Combustible Insulation
(1) Foamed plastic insulation shall conform to Article 3.1.5.12A.
(2) Combustible insulation with a flame-spread rating not more than 25 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, is permitted in a building required to be of noncombustible construction.
(3) Combustible insulation is permitted to be installed above roof decks, outside of foundation walls below ground level and beneath concrete slabs-on-ground of buildings required to be of noncombustible construction.
(4) Except as provided in Sentences (5) and (6), combustible insulation with a flame-spread rating more than 25 but not more than 500 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, is permitted in a building required to be of noncombustible construction, provided the insulation is protected from adjacent space in the building, other than adjacent concealed spaces within wall assemblies, by a thermal barrier consisting of,
(a) not less than 12.7 mm thick gypsum board mechanically fastened to a supporting assembly independent of the insulation,
(b) lath and plaster, mechanically fastened to a supporting assembly independent of the insulation,
(c) masonry, or
(d) concrete.
(5) Combustible insulation with a flame-spread rating more than 25 but not more than 500 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, is permitted in the exterior walls of a building required to be of noncombustible construction, that is not sprinklered and is more than 18 m high, measured from grade to the underside of the roof, provided the insulation is protected from adjacent space in the building, other than adjacent concealed spaces within wall assemblies, by a thermal barrier that,
(a) consists of gypsum board not less than 12.7 mm thick, mechanically fastened to a supporting assembly independent of the insulation and with all joints either backed or taped and filled,
(b) consists of lath and plaster, mechanically fastened to a supporting assembly independent of the insulation,
(c) consists of masonry or concrete not less than 25 mm thick, or
(d) when tested in conformance with CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials”, does not develop an average temperature rise more than 140°C or a maximum temperature rise more than 180°C at any point on its unexposed face within 10 min.
(6) Combustible insulation with a flame-spread rating more than 25 but not more than 500 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, is permitted in the interior walls, within ceilings and within roof assemblies of a building required to be of noncombustible construction, that is not sprinklered and is more than 18 m high, measured from grade to the underside of the roof, provided the insulation is protected from adjacent space in the building, other than adjacent concealed spaces within wall assemblies, by a thermal barrier that,
(a) consists of Type X gypsum board not less than 15.9 mm thick, mechanically fastened to a supporting assembly independent of the insulation and with all joints either backed or taped and filled, conforming to,
(i) ASTM C1177 / C1177M, “Glass Mat Gypsum Substrate for Use as Sheathing”,
(ii) ASTM C1178 / C1178M, “Coated Glass Mat Water-Resistant Gypsum Backing Panel”,
(iii) ASTM C1396 / C1396M, “Gypsum Board”,
(iv) ASTM C1658 / C1658M, “Glass Mat Gypsum Panels”, or
(v) CAN/CSA-A82.27-M, “Gypsum Board”,
(b) consists of non-loadbearing masonry or concrete not less than 50 mm thick,
(c) consists of loadbearing masonry or concrete not less than 75 mm thick, or
(d) when tested in conformance with CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials”,
(i) does not develop an average temperature rise more than 140°C or a maximum temperature rise more than 180°C at any point on its unexposed face within 20 min, and
(ii) remains in place for not less than 40 min.
3.1.5.12A. Foamed Plastic Insulation
(1) Foamed plastic insulation is permitted to be installed above roof decks, outside of foundation walls below ground level and beneath concrete slabs-on-ground of a building required to be of noncombustible construction.
(2) Except as provided in Sentences (3) and (4), foamed plastic insulation with a flame-spread rating not more than 500 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, is permitted in a building required to be of noncombustible construction, provided the insulation is protected from adjacent space in the building, other than adjacent concealed spaces within wall assemblies, by a thermal barrier that,
(a) consists of not less than 12.7 mm thick gypsum board mechanically fastened to a supporting assembly independent of the insulation,
(b) consists of lath and plaster, mechanically fastened to a supporting assembly independent of the insulation,
(c) consists of masonry,
(d) consists of concrete, or
(e) meets the requirements of classification B when tested in conformance with CAN/ULC-S124, “Test for the Evaluation of Protective Coverings for Foamed Plastic”.
(3) Foamed plastic insulation with a flame-spread rating more than 25 but not more than 500 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, is permitted in the exterior walls of a building required to be of noncombustible construction, that is not sprinklered and is more than 18 m high, measured from grade to the underside of the roof, provided the insulation is protected from adjacent space in the building, other than adjacent concealed spaces within wall assemblies, by a thermal barrier that,
(a) consists of gypsum board not less than 12.7 mm thick, mechanically fastened to a supporting assembly independent of the insulation and with all joints either backed or taped and filled,
(b) consists of lath and plaster, mechanically fastened to a supporting assembly independent of the insulation,
(c) consists of masonry or concrete not less than 25 mm thick, or
(d) when tested in conformance with CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials”, does not develop an average temperature rise more than 140°C or a maximum temperature rise more than 180°C at any point on its unexposed face within 10 min.
(4) Foamed plastic insulation with a flame-spread rating more than 25 but not more than 500 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, is permitted in the interior walls, within ceilings and within roof assemblies of a building required to be of noncombustible construction, that is not sprinklered and is more than 18 m high, measured from grade to the underside of the roof, provided the insulation is protected from adjacent space in the building, other than adjacent concealed spaces within wall assemblies, by a thermal barrier that,
(a) consists of Type X gypsum board not less than 15.9 mm thick, mechanically fastened to a supporting assembly independent of the insulation and with all joints either backed or taped and filled, conforming to,
(i) ASTM C1177 / C1177M, “Glass Mat Gypsum Substrate for Use as Sheathing”,
(ii) ASTM C1178 / C1178M, “Coated Glass Mat Water-Resistant Gypsum Backing Panel”,
(iii) ASTM C1396 / C1396M, “Gypsum Board”, or
(iv) CAN/CSA-A82.27-M, “Gypsum Board”,
(b) consists of non-loadbearing masonry or concrete not less than 50 mm thick,
(c) consists of loadbearing masonry or concrete not less than 75 mm thick, or
(d) when tested in conformance with CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials”,
(i) does not develop an average temperature rise more than 140°C or a maximum temperature rise more than 180°C at any point on its unexposed face within 20 min, and
(ii) remains in place for not less than 40 min.
3.1.5.13. Combustible Elements in Partitions
(1) Except as permitted by Sentence (2), solid lumber partitions not less than 38 mm thick and wood framing in partitions located in a fire compartment not more than 600 m2 in area are permitted to be used in a building required to be of noncombustible construction in a floor area that is not sprinklered provided the partitions,
(a) are not required fire separations, and
(b) are not located in a care, care and treatment or detention occupancy or in a retirement home.
(2) Partitions installed in a building required to be of noncombustible construction are permitted to contain wood framing provided,
(a) the building is not more than 3 storeys in building height,
(b) the partitions are not located in a care, care and treatment or detention occupancy or in a retirement home, and
(c) the partitions are not installed as enclosures for exits or vertical service spaces.
(3) Solid lumber partitions not less than 38 mm thick and partitions that contain wood framing are permitted to be used in a building required to be of noncombustible construction provided,
(a) the floor area containing the partitions is sprinklered, and
(b) the partitions are not,
(i) located in a care, care and treatment or detention occupancy or in a retirement home,
(ii) installed as enclosures for exits or vertical service spaces, or
(iii) used to satisfy the requirements of Clause 3.2.8.1.(1)(a).
3.1.5.14. Storage Lockers in Residential Buildings
(1) Except in a retirement home, storage lockers in storage rooms are permitted to be constructed of wood in a building of residential occupancy required to be of noncombustible construction.
3.1.5.15. Combustible Ducts
(1) Except as required by Sentence 3.6.4.3.(1), combustible ducts, including plenums and duct connectors, are permitted to be used in a building required to be of noncombustible construction provided these ducts and duct connectors are used only in horizontal runs.
(2) Combustible duct linings, duct coverings, duct insulation, vibration isolation connectors, duct tape, pipe insulation and pipe coverings are permitted to be used in a building required to be of noncombustible construction provided they conform to the appropriate requirements of Part 6.
(3) In a building required to be of noncombustible construction, combustible ducts need not comply with the requirements of Part 6 provided the ducts are,
(a) part of a duct system conveying only ventilation air, and
(b) contained entirely within a dwelling unit.
3.1.5.16. Combustible Piping Materials
(1) Except as permitted by Sentences (2) and (3) and by Clause 3.1.5.2.(1)(d) and Article 3.1.5.22., combustible piping and tubing and associated adhesives are permitted to be used in a building required to be of noncombustible construction provided that, except when concealed in a wall or concrete floor slab, they,
(a) have a flame-spread rating not more than 25, and
(b) if used in a building described in Subsection 3.2.6., have a smoke developed classification not more than 50.
(2) Combustible sprinkler piping is permitted to be used within a sprinklered floor area in a building required to be of noncombustible construction.
(3) Polypropylene pipes and fittings are permitted to be used for drain, waste and vent piping for the conveyance of highly corrosive materials and for piping used to distribute distilled or dialyzed water in laboratory and hospital facilities in a building required to be of noncombustible construction, provided,
(a) the building is sprinklered,
(b) the piping is not located in a vertical shaft, and
(c) piping that penetrates a fire separation is sealed at the penetration by a fire stop that has an FT rating not less than the fire-resistance rating of the fire separation when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems”, with a pressure differential of 50 Pa between the exposed and unexposed sides, with the higher pressure on the exposed side.
3.1.5.17. Combustible Plumbing Fixtures
(1) Combustible plumbing fixtures are permitted in a building required to be of noncombustible construction if they are constructed of material having a flame-spread rating and smoke developed classification permitted in Subsection 3.1.13.
3.1.5.18. Wires and Cables
(1) Except as permitted by Sentence (2) and Articles 3.1.5.19. and 3.1.5.21., optical fibre cables and electrical wires and cables with combustible insulation, jackets or sheathes are permitted in a building required to be of noncombustible construction, provided,
(a) the wires and cables exhibit a vertical char of not more than 1.5 m when tested in conformance with the Vertical Flame Test – Cables in Cabletrough in Clause 4.11.4. of CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables”, (FT4 Rating),
(b) the wires and cables are located in,
(i) totally enclosed noncombustible raceways,
(ii) concealed spaces in walls,
(iii) concrete slabs,
(iv) a service room separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h, or
(v) totally enclosed nonmetallic raceways conforming to Clause 3.1.5.20.(1)(b), or
(c) the wires and cables are communication cables used at the service entry to a building and are not more than 3 m long.
(2) The requirement in Clause (1)(a) is considered to be met where the wires and cables exhibit a flame-spread of not more than 1.5 m, a smoke density of not more than 0.5 at peak optical density and a smoke density not more than 0.15 at average optical density when tested in conformance with the Flame and Smoke Test in the Appendix to CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables”, (FT6 Rating).
3.1.5.19. Combustible Travelling Cables for Elevators
(1) Combustible travelling cables are permitted on elevating devices in a building required to be of noncombustible construction.
3.1.5.20. Nonmetallic Raceways
(1) Except as provided by Subclause 3.6.4.3.(1)(a)(iv) and subject to limits on size for penetrations of fire separations as required by Sentence 3.1.9.3.(2), within a fire compartment of a building required to be of noncombustible construction, totally enclosed nonmetallic raceways not more than 175 mm in outside diameter, or an equivalent rectangular area, are permitted to be used to enclose optical fibre cables and electrical wires and cables, provided, where,
(a) the wires and cables in the raceways meet or exceed the requirements of Clause 3.1.5.18.(1)(a), the nonmetallic raceways meet the requirements for at least an FT4 rating in,
(i) CAN/CSA-C22.2 No. 262, “Optical Fiber Cable and Communication Cable Raceway Systems”, or
(ii) CAN/ULC-S143, “Fire Tests for Non-Metallic Electrical and Optical Fibre Cable Raceway Systems”, and
(b) the wires and cables in the raceways do not meet or exceed the requirements of Clause 3.1.5.18.(1)(a), the nonmetallic raceways exhibit a vertical char not more than 1.5 m when tested in conformance with the Vertical Flame Test (FT4) – Conduit or Tubing on Cable Tray in Clause 6.16 of CSA C22.2 No. 211.0, “General Requirements and Methods of Testing for Nonmetallic Conduit”.
3.1.5.21. Wires in Computer Room Floors
(1) Optical fibre cables and electrical wires and cables with combustible insulation, jackets or sheathes, located in the space below a raised floor in a computer room, are permitted in a building required to be of noncombustible construction provided they do not convey flame or continue to burn for more than 1 min when tested in conformance with the Vertical Flame Test in Clause 4.11.1. of CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables”, (FT1 Rating).
(2) The requirement in Sentence (1) is considered to be met where the wires and cables,
(a) exhibit a vertical char of not more than 1.5 m when tested in conformance with the Vertical Flame Test – Cables in Cabletrough in Clause 4.11.4. of CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables”, (FT4 Rating), or
(b) exhibit a flame-spread of not more than 1.5 m, a smoke density of not more than 0.5 at peak optical density and a smoke density not more than 0.15 at average optical density when tested in conformance with the Flame and Smoke Test in the Appendix to CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables”, (FT6 Rating).
3.1.5.22. Combustible Components in Public Pools and Public Spas
(1) Combustible fittings and components in a public pool or public spa, including main drains, piping, skimmers, return inlets, steps, ladder rungs and liners, are permitted in a building required to be of noncombustible construction.
3.1.5.23. Marquees Having Combustible Elements
(1) Except as permitted in Sentence (2), exterior marquees, not greater than 7.5 m from ground level to the top of the marquee, having combustible elements, other than fabrics or films conforming to Sentence 3.1.16.1.(1), are permitted on a building required to be of noncombustible construction, provided every opening in the exposed wall of the building above the marquee is protected with wired glass in accordance with MMAH Supplementary Standard SB-2, “Fire Performance Ratings” where these openings are within,
(a) 4.5 m horizontally of the marquee, and
(b) 9 m vertically above the marquee.
(2) The protection required by Sentence (1) is permitted to be waived if the building is sprinklered.
3.1.5.24. Combustible Mezzanines
(1) In a building required to be of noncombustible construction, a mezzanine located within a live/work unit is permitted to be of combustible construction, provided the area of the mezzanine is not more than 25% of the floor area of the live/work unit or 20 m2, whichever is less, and has no obstructions more than 1 070 mm above the floor.
3.1.5.25. Wood Decorative Cladding
(1) Wood decorative cladding is permitted to be used on exterior marquee fascias, of a storey having direct access to a street or access route, of a building required to be of noncombustible construction, provided the cladding is fire-retardant treated wood that, before testing to CAN/ULC-S102, “Test for Surface Burning Characteristics of Building Materials and Assemblies”, has been conditioned in conformance with ASTM D2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing”.
3.1.5.26. Combustible Solar Collector Systems
(1) A combustible solar collector system is permitted to be installed above the roof of a building required to be of noncombustible construction.
3.1.6. Encapsulated Mass Timber Construction
3.1.6.1. Application
(1) Encapsulated mass timber construction permitted in this Part shall conform to this Subsection.
3.1.6.2. Noncombustible Construction
(1) Except as otherwise provided in this Part and Sentence 6.2.8.1.(1), materials used in a building or part of a building permitted to be of encapsulated mass timber construction shall conform to Subsection 3.1.5.
3.1.6.3. Structural Mass Timber Elements
(1) Except as otherwise provided in this Subsection and Articles 3.2.2.16. and 3.2.3.19., a building or part of a building permitted to be of encapsulated mass timber construction is permitted to include structural mass timber elements, including beams, columns, arches and wall, floor and roof assemblies, provided they comply with Sentences (2) and (3).
(2) Structural mass timber elements referred to in Sentence (1) shall,
(a) except as provided in Sentence (4), be arranged in heavy solid masses containing no concealed spaces,
(b) have essentially smooth flat surfaces with no thin sections or sharp projections, and
(c) except as provided in Sentence 3.1.6.17.(1), conform to the minimum dimensions stated in Table 3.1.6.3.
Table 3.1.6.3.
Minimum Dimensions of Structural Mass Timber Elements in Encapsulated Mass Timber Construction
Forming Part of Sentences 3.1.6.3.(2), 3.1.6.8.(1) and 3.1.6.17.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
1. |
Walls that are not fire separations or exterior walls (1-sided fire exposure) |
96 |
N/A |
2. |
Walls that require a fire-resistance rating, but are not fire separations (2-sided fire exposure) |
192 |
N/A |
3. |
Floors and roofs (1-sided fire exposure) |
96 |
N/A |
4. |
Beams, columns and arches (2- or 3-sided fire exposure) |
N/A |
192 x 192 |
5. |
Beams, columns and arches (4-sided fire exposure) |
N/A |
224 x 224 |
(3) Adhesives used in structural mass timber elements referred to in Sentence (1) that are constructed of cross-laminated timber shall conform to the elevated temperature performance requirements in ANSI/APA PRG 320, “Standard for Performance-Rated Cross-Laminated Timber”.
(4) Concealed spaces are permitted within structural mass timber elements referred to in Sentence (2) and need not conform to Sentence 3.1.6.4.(1) provided the concealed spaces are,
(a) sprinklered and divided into compartments by fire blocks in conformance with Subsection 3.1.11.,
(b) completely filled with rocks or slag fibre insulation conforming to CAN/ULC-S702.1 “Standard for Mineral Fibre Thermal Insulation for Buildings, Part 1: Material Specification” and having a density not less than 32 kg/m3,
(c) if horizontal, lined with not less than a single layer of 12.7 mm thick Type X gypsum board or noncombustible material providing an encapsulation rating of not less than 25 min, or
(d) if vertical, lined with not less than a single layer of 12.7 mm thick Type X gypsum board or noncombustible material providing an encapsulation rating of not less than 25 min and vertically divided into compartments by fire blocks in conformance with Subsection 3.1.11.
3.1.6.4. Encapsulation of Mass Timber Elements
(1) Except as provided in Sentences (3) to (6), Sentence 3.1.6.3.(4), Articles 3.1.6.7. and 3.1.6.12. and Sentences 3.1.6.16.(2) and 3.1.6.17.(2), the exposed surfaces of structural mass timber elements conforming to Article 3.1.6.3. shall be protected from adjacent spaces in the building, including adjacent concealed spaces within wall, floor and roof assemblies, by a material or assembly of materials conforming to Sentence (2) that provides an encapsulation rating of not less than 50 min.
(2) Except as provided in Sentence 3.1.6.11.(1), the material or assembly of materials referred to Sentence (1) shall consist of,
(a) gypsum board,
(b) gypsum concrete,
(c) noncombustible materials,
(d) materials that conform to Sentences 3.1.5.1.(2) to (4), or
(e) any combination of materials listed in Clauses (a) to (d).
(3) Except as provided in Sentence (5), the exposed surfaces of mass timber beams, columns and arches within a suite or fire compartment need not be protected in accordance with Sentence (1), provided,
(a) the aggregate surface area does not exceed 10% of the total wall area of the perimeter of the suite or fire compartment in which they are located, and
(b) the flame-spread rating on any exposed surface is not more than 150.
(4) Except as provided in Sentences (5) and (6), the exposed surfaces of mass timber walls within a suite need not be protected in accordance with Sentence (1), provided,
(a) each exposed surface faces the same direction, and
(b) the flame-spread rating on any exposed surface is not more than 150.
(5) The aggregate exposed surface area of mass timber elements within a suite permitted in Sentences (3) and (4) shall not exceed 35% of the total wall area of the perimeter of the suite.
(6) The exposed surfaces of mass timber ceilings within a suite need not be protected in accordance with Sentence (1), provided the aggregate area of the exposed surfaces does not exceed,
(a) 10% of the total ceiling area of the suite, where the exposed surfaces have a flame-spread rating not more than 150, or
(b) 25% of the total ceiling area of the suite, where,
(i) the suite contains no mass timber walls with exposed surfaces, and
(ii) the exposed surfaces of the mass timber ceiling have a flame-spread rating not more than 75.
3.1.6.5. Determination of Encapsulation Ratings
(1) Except as provided in Article 3.1.6.6., the rating of a material or assembly of materials that is required to have an encapsulation rating shall be determined on the basis of the results of the tests conducted in conformance with CAN/ULC-S146, “Test for the Evaluation of Encapsulation Materials and Assemblies of Materials for the Protection of Structural Timber Elements”.
3.1.6.6. Encapsulation Materials
(1) Gypsum-concrete topping and concrete not less than 38 mm thick are deemed to have an encapsulation rating of 50 min when installed on the upper side of a mass timber floor or roof assembly.
(2) Two layers of Type X gypsum board each not less than 12.7 mm thick are deemed to have an encapsulation rating of 50 min when installed on a mass timber element, provided they,
(a) are fastened with a minimum of two rows of screws in each layer,
(i) directly to the mass timber element with screws of sufficient length to penetrate not less than 20 mm into the mass timber element that are spaced not more than 400 mm o.c. and 20 mm to 38 mm from the boards’ edges, or
(ii) to wood furring or resilient metal or steel furring channels not more than 25 mm thick spaced not more than 400 mm o.c. on the mass timber element,
(b) are installed with the joints in each layer staggered from those in the adjacent layer,
(c) are installed in conformance with ASTM C840, “Standard Specification for Application and Finishing of Gypsum Board”, except that their joints need not be taped and finished, and
(d) conform to,
(i) ASTM C1396/C1396M, “Gypsum Board”, or
(ii) CAN/CSA A82.27-M, “Gypsum Board”.
3.1.6.7. Combustible Roofing Materials
(1) Wood roof sheathing and roof sheathing supports that do not conform to Articles 3.1.6.3. and 3.1.6.4. are permitted in a building or part of a building permitted to be of encapsulated mass timber construction, provided they are installed,
(a) above a concrete deck in accordance with Clauses 3.1.5.3.(2)(a) to (f), or
(b) above a deck of encapsulated mass timber construction, where,
(i) the deck is permitted to be encapsulated between the roof sheathing supports by a material or assembly of materials conforming to Sentence 3.1.6.4.(2) that provides an encapsulation rating of not less than 50 min,
(ii) the height of the roof space is not more than 1 m,
(iii) the roof space is divided into compartments by fire blocks in conformance with Article 3.1.11.5.,
(iv) openings through the deck other than for noncombustible roof drains and plumbing piping are protected by shafts constructed as fire separations having a fire-resistance rating not less than 1 h that extend from the deck to not less than 150 mm above the adjacent sheathing, and
(v) except as permitted by Subclause (iv), the roof space does not contain any building services.
(2) Combustible cant strips, roof curbs, nailing strips and similar components used in the installation of roofing are permitted on a building or part of a building permitted to be of encapsulated mass timber construction.
(3) Wood nailer facings to parapets that are not more than 610 mm high are permitted on a building or part of a building permitted to be of encapsulated mass timber construction, provided the facings and any roof membranes covering the facings are protected by sheet metal.
3.1.6.8. Combustible Window Sashes and Frames
(1) Combustible window sashes and frames are permitted in a building or part of a building permitted to be of encapsulated mass timber construction, provided,
(a) each window in an exterior wall face is an individual unit separated from every other opening in the wall by noncombustible wall construction or mass timber wall construction conforming to the dimensions stated in Table 3.1.6.3.,
(b) windows in exterior walls in contiguous storeys are separated by not less than 1 m of noncombustible wall construction or mass timber wall construction conforming to the dimensions stated in Table 3.1.6.3., and
(c) the aggregate area of openings in an exterior wall face of a fire compartment is not more than 40% of the area of the wall face.
3.1.6.9. Exterior Cladding
(1) Except as provided in Sentences (2), (3) and (6), cladding on an exterior wall assembly of a building or part of a building permitted to be of encapsulated mass timber construction shall be noncombustible.
(2) Except as provided in Sentences (3) to (5), cladding on an exterior wall assembly of a building or part of a building permitted to be of encapsulated mass timber construction is permitted to consist of,
(a) combustible cladding that,
(i) is not contiguous over more than 4 storeys,
(ii) represents not more than 10% of the cladding on each exterior wall of each storey,
(iii) is not more than 1.2 m in width,
(iv) has a flame-spread rating not more than 75 on any exposed surface, or any surface that would by exposed by cutting through the material in any direction,
(v) is separated from other portions of combustible cladding on adjacent storeys by a horizontal distance of not less than 2.4 m, and
(vi) is separated from other portions of combustible cladding by a horizontal distance of not less than 1.2 m,
(b) combustible cladding that,
(i) is not contiguous across adjacent storeys,
(ii) represents not more than 10% of the cladding on each exterior wall of each storey,
(iii) has a flame-spread rating not more than 75 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, and
(iv) is separated from other portions of combustible cladding on adjacent storeys by a horizontal distance of not less than 2.4 m,
(c) combustible cladding representing up to 100% of the cladding on exterior walls of the first storey, provided all portions of the cladding can be directly accessed and are located not more than 15 m from a street or access route conforming to Article 3.2.5.6., measured horizontally from the face of the building,
(d) except as provided in Sentence (4), a wall assembly that satisfies the criteria described in Clause 3.1.5.5.(1)(b), or
(e) a combination of noncombustible cladding and the cladding described in Clauses (a) to (d).
(3) The permitted area of combustible cladding referred to in Clause (2)(a) or (b) shall not exceed 5% of the cladding on each exterior wall of each storey where firefighting facilities cannot reach the building within 10 min of the alarm being received.
(4) An exterior wall assembly constructed in conformance with Section 6 of MMAH Supplementary Standard SB-2, “Fire Performance Ratings” is deemed to satisfy the criteria of Clause (2)(d).
(5) Except as provided in Article 3.2.3.10., where the limiting distance in Table 3.2.3.1.D. or Table 3.2.3.1.E. permits an area of unprotected openings of not more than 10% of the exposing building face, the construction requirements of Table 3.2.3.7. shall be met.
(6) A wall assembly conforming to Clause (2)(d) that includes combustible cladding made of fire-retardant-treated wood shall be tested for fire exposure after the cladding has been subjected to the accelerated weathering test specified in ASTM D2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing”.
(7) Where combustible cladding conforming to Clause (2)(a) or (b) on an exterior wall of a fire compartment is exposed to combustible cladding conforming to Clause (2)(a) or (b) on an exterior wall of the same fire compartment or of another fire compartment, and the planes of the two walls are parallel or at an angle less than 135° measured from the exterior of the building, the different portions of combustible cladding shall,
(a) be separated by a horizontal distance of not less than 3 m, and
(b) not be contiguous over more than 2 storeys.
3.1.6.10. Combustible Components in Exterior Walls
(1) Except as provided in Sentence (2), combustible components, other than those permitted by Article 3.1.6.9., are permitted to be used in an exterior wall assembly of a building or part of a building permitted to be of encapsulated mass timber construction provided the wall assembly meets the requirements of Clause 3.1.6.9.(2)(d).
(2) An exterior wall assembly constructed in conformance with Section 6 in MMAH Supplementary Standard SB-2, “Fire Performance Ratings” is deemed to satisfy the criteria of Sentence (1).
(3) Non-loadbearing wood elements permitted in Article 3.1.5.5. need not conform to Article 3.1.6.3. in a building or part of a building permitted to be of encapsulated mass timber construction.
3.1.6.11. Nailing Elements
(1) Wood nailing elements are permitted to be used for the attachment of a material or assembly of materials to provide an encapsulation rating in a building or part of a building permitted to be of encapsulated mass timber construction, provided the concealed space created by the wood nailing elements is not more than 25 mm deep.
(2) Except as permitted by Sentence 3.1.6.16.(2) and Article 3.1.6.6., wood nailing elements are permitted to be used for the attachment of interior finishes in a building or part of a building permitted to be of encapsulated mass timber construction, provided the concealed space created by the wood nailing elements is not more than 50 mm deep and,
(a) exposed surfaces in the concealed space have a flame-spread rating not more than 25, or
(b) the concealed space is filled with noncombustible insulation.
3.1.6.12. Combustible Flooring Elements
(1) Wood members that are more than 50 mm but not more than 300 mm high are permitted to be used for the construction of a raised platform in a building or part of a building permitted to be of encapsulated mass timber construction, and they need not conform to Articles 3.1.6.3. and 3.1.6.4., provided,
(a) the concealed spaces created by the wood members are divided into compartments by fire blocks in conformance with Sentence 3.1.11.3.(4), and
(b) the wood members are,
(i) applied directly to or set into a noncombustible floor slab, or
(ii) applied directly to a mass timber floor assembly that conforms to the requirements of Article 3.1.6.3.
(2) The upper surface of the mass timber floor assembly referred to in Subclause (1)(b)(ii) is permitted to be encapsulated only between the wood members by a material or assembly of materials conforming to Sentences 3.1.6.4.(1) and (2).
(3) The floor system for the raised platform referred to in Sentence (1) is permitted to include a combustible subfloor and combustible finished flooring.
3.1.6.13. Combustible Stairs
(1) Wood stairs and landings conforming to the requirements for floor assemblies in Article 3.1.6.3. and Sentences 3.1.6.4.(1) and (2) are permitted in an exit stairwell in a building or part of a building permitted to be of encapsulated mass timber construction.
(2) Wood stairs in a suite in a building or part of a building permitted to be of encapsulated mass timber construction need not conform to Articles 3.1.6.3. and 3.1.6.4.
3.1.6.14. Combustible Interior Finishes
(1) Except as provided in Sentences (2) and (3), combustible interior wall and ceiling finishes referred to in Clause 3.1.13.1.(1)(b) that are not more than 1 mm thick are permitted in a building or part of a building permitted to be of encapsulated mass timber construction.
(2) Except as provided in Sentences 3.1.6.4.(3) and (4), combustible interior wall finishes, other than foamed plastics, that are not more than 25 mm thick are permitted in a building or part of a building permitted to be of encapsulated mass timber construction, provided they have a flame-spread rating not more than 150 on any exposed surface or any surface that would be exposed by cutting through the material in any direction.
(3) Except as provided in Sentences (4) and 3.1.6.4.(3) and (6), combustible interior ceiling finishes, other than foamed plastics, are permitted in a building or part of a building permitted to be of encapsulated mass timber construction, provided that,
(a) they have a flame-spread rating not more than 25 on any exposed surface or any surface that would be exposed by cutting through the material in any direction, and
(b) not more than 10% of the ceiling area within each fire compartment is permitted to have a flame-spread rating not more than 150.
(4) Combustible interior ceiling finishes made of fire-retardant-treated wood are permitted in a building or part of a building permitted to be of encapsulated mass timber construction, provided they are not more than 25 mm thick or are exposed fire-retardant-treated wood battens.
3.1.6.15. Combustible Elements in Partitions
(1) Solid lumber partitions not less than 38 mm thick and partitions containing wood framing that do not conform to Article 3.1.6.3. are permitted in a building or part of a building permitted to be of encapsulated mass timber construction, provided the partitions are,
(a) protected on each face with not less than,
(i) a single layer of 12.7 mm thick Type X gypsum board, with all joints either backed or taped and filled, conforming to ASTM C1396/C1396M, “Standard Specification for Gypsum Board”, or CAN/CSA A82.27-M, “Gypsum Board”,
(ii) a single layer of 19 mm thick fire-retardant-treated wood, on solid lumber partitions, or
(iii) a single layer of 19mm thick fire-retardant-treated wood, on partitions containing wood framing, with wood stud cavities filled with noncombustible insulation, and
(b) not installed as enclosures for exits or vertical service spaces.
3.1.6.16. Exposed Construction Materials and Components in Concealed Spaces
(1) Except as provided in Sentence (2) and Article 3.1.11.7., and except as otherwise provided in this Subsection, only construction materials and components permitted in noncombustible construction shall be permitted to have exposed surfaces in concealed spaces within floor, roof and wall assemblies permitted in a building or part of a building permitted to be of encapsulated mass timber construction.
(2) Exposed surfaces are permitted in a concealed space created by the attachment of a material or assembly of materials conforming to Sentence 3.1.6.4.(1), provided the concealed space is not more than 25 mm deep.
3.1.6.17. Penetration by Outlet Boxes
(1) The minimum dimensions stated in Table 3.1.6.3. need not apply at cutouts in vertical or horizontal structural mass timber elements where outlet boxes are installed in accordance with Article 3.1.9.3A.
(2) The exposed surfaces of the cutouts described in Sentence (1) need not be protected in accordance with Sentence 3.1.6.4.(1).
(3) Outlet boxes on opposite sides of a structural mass timber element having a fire-resistances rating shall be separated by a distance of not less than 600 mm.
3.1.7. Fire-Resistance Ratings
3.1.7.1. Determination of Ratings
(1) Except as permitted by Sentence (2) and Articles 3.1.7.2. and 3.6.3.5, the rating of a material, assembly of materials or a structural member that is required to have a fire-resistance rating, shall be determined on the basis of the results of tests conducted in conformance with CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials”.
(2) A material, assembly of materials or a structural member is permitted to be assigned a fire-resistance rating on the basis of MMAH Supplementary Standard SB-2, “Fire Performance Ratings”.
3.1.7.2. Exception for Exterior Walls
(1) The limit on the rise of temperature on the unexposed surface of an assembly as required by the tests referred to in Sentence 3.1.7.1.(1) shall not apply to an exterior wall that has a limiting distance of 1.2 m or more, provided correction is made for radiation from the unexposed surface in accordance with Sentence 3.2.3.1.(9).
3.1.7.3. Exposure Conditions for Rating
(1) Floor, roof and ceiling assemblies shall be rated for exposure to fire on the underside.
(2) Firewalls and interior vertical fire separations shall be rated for exposure to fire on each side.
(3) Exterior walls shall be rated for exposure to fire from inside the building.
3.1.7.4. Minimum Fire-Resistance Rating
(1) The use of materials or assemblies having a greater fire-resistance rating than required shall impose no obligation to exceed in whole or in part the minimum fire-resistance ratings required by this Part.
3.1.7.5. Rating of Supporting Construction
(1) Except as permitted by Sentence (2) and by Articles 3.2.2.20. to 3.2.2.83. for mixed types of construction, all loadbearing walls, columns and arches in the storey immediately below a floor or roof assembly required to have a fire-resistance rating shall have a fire-resistance rating not less than that required for the supported floor or roof assembly.
(2) Loadbearing walls, columns and arches supporting a service room or service space need not conform to Sentence (1).
(3) Except as provided in Sentence (4) and for noncombustible roof assemblies required by Subclauses 3.2.2.43A.(2)(c)(i) and 3.2.2.50A.(2)(c)(i), if an assembly is required to be of noncombustible construction and have a fire-resistance rating, it shall be supported by noncombustible construction.
(4) Except for parts of a building constructed in accordance with Article 3.2.2.7. that are required to be of noncombustible construction, assemblies of noncombustible construction in buildings or parts of buildings permitted to be of encapsulated mass timber construction are permitted to be supported by encapsulated mass timber construction.
3.1.8. Fire Separations and Closures
3.1.8.1. General Requirements
(1) Any wall, partition or floor assembly required to be a fire separation shall,
(a) except as permitted by Sentence (2), be constructed as a continuous element, and
(b) as required in this Part, have a fire-resistance rating as specified.
(2) Openings in a fire separation shall be protected with closures, shafts or other means in conformance with Articles 3.1.8.4. to 3.1.8.18. and Subsections 3.1.9. and 3.2.8.
3.1.8.2. Combustible Construction Support
(1) Combustible construction that abuts on or is supported by a noncombustible fire separation shall be constructed so that its collapse under fire conditions will not cause the collapse of the fire separation.
3.1.8.3. Continuity of Fire Separations
(1) Except as permitted by Sentence 3.6.4.2.(2), a horizontal service space or other concealed space located above a required vertical fire separation, including the walls of a vertical shaft, shall be divided at the fire separation by an equivalent fire separation within the service space.
(2) The fire separation required by Sentence (1) shall terminate so that smoke-tight joints are provided where it abuts on or intersects,
(a) a floor,
(b) a roof slab, or
(c) a roof deck.
(3) Except as required by Subsection 3.6.3. for a shaft penetrating a roof assembly, a shaft, including an exit enclosure, that penetrates a fire separation, shall,
(a) extend through any horizontal service space or any other concealed space, and
(b) terminate so that smoke-tight joints are provided where the shaft abuts on or intersects,
(i) a floor,
(ii) a roof slab, or
(iii) a roof deck.
(4) The continuity of a fire separation shall be maintained where it abuts another fire separation, a floor, a ceiling, or an exterior wall assembly.
3.1.8.4. Determination of Ratings
(1) Except as permitted by Sentences (2) and 3.1.8.14.(1), the fire-protection rating for a closure shall be determined in accordance with,
(a) CAN/ULC-S104, “Fire Tests of Door Assemblies”,
(b) CAN/ULC-S106, “Fire Tests of Window and Glass Block Assemblies”, or
(c) CAN/ULC-S112, “Fire Test of Fire Damper Assemblies”.
(2) Except as permitted by Sentence 3.1.8.10.(1), the fire-protection rating of a closure shall conform to Table 3.1.8.4. for the required fire-resistance rating of the fire separation.
(3) The leakage rate of smoke dampers and combination smoke and fire dampers shall,
(a) be determined in accordance with the applicable provisions in CAN/ULC-S112.1, “Leakage Rated Dampers for Use in Smoke Control Systems”, and
(b) conform to Class I, II or III of that standard.
(4) The leakage rate of a door assembly shall be determined in accordance with ANSI/UL-1784, “Air Leakage Tests of Door Assemblies and Other Opening Protectives”.
Table 3.1.8.4.
Fire-Protection Rating of Closure
Forming Part of Sentence 3.1.8.4.(2) and Clause 3.1.9.1.(1)(a)
Item |
Column 1 Fire-Resistance Rating of Fire Separation |
Column 2 Required Fire-Protection Rating of Closure |
1. |
30 min |
20 min |
2. |
45 min |
45 min |
3. |
1 h |
45 min |
4. |
1.5 h |
1 h |
5. |
2 h |
1.5 h |
6. |
3 h |
2 h |
7. |
4 h |
3 h |
3.1.8.5. Installation of Closures
(1) Except where fire dampers, window assemblies and glass block are used as closures, closures of the same fire-protection rating installed on opposite sides of the same opening are deemed to have a fire-protection rating equal to the sum of the fire-protection ratings of the closures.
(2) Except as otherwise specified in this Part, every door, fire damper, window assembly or glass block used as a closure in a required fire separation,
(a) shall be installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives”, and
(b) where required to have a fire-protection rating, shall have labels or classification marks to identify the testing laboratory.
(3) Except as otherwise specified in this Part, every smoke damper used as a closure in a required fire separation shall be installed in conformance with NFPA 105, “Smoke Door Assemblies and Other Opening Protectives”.
(4) If a door is installed so that it could damage the integrity of a fire separation if its swing is unrestricted, door stops shall be installed to prevent the damage.
(5) A leakage-rated door assembly rated in accordance with Sentence 3.1.8.4.(4) shall,
(a) be installed in fire separations in protected floor areas described in Clause 3.3.1.7.(1)(b),
(b) be installed in fire separations in care or care and treatment occupancies referred to in Sentence 3.3.3.5.(4) and installed in fire separations in retirement homes referred to in Sentence 3.3.4.11.(4),
(c) except as provided in Sentence (7), be installed in fire separations of public corridors serving dwelling units in storeys that are not sprinklered, and
(d) be installed in firewalls that are a horizontal exit referred to in Sentence 3.3.3.5.(3).
(6) Leakage-rated door assemblies required by Sentence (5) shall conform to NFPA 105, “Smoke Door Assemblies and Other Opening Protectives”.
(7) A leakage-rated door assembly need not be installed where a dwelling unit served by a public corridor has,
(a) a second and separate means of egress, or
(b) an open-air balcony that is sized to accommodate the number of occupants for which the dwelling unit is intended.
3.1.8.6. Maximum Openings
(1) The size of an opening in an interior fire separation required to be protected with a closure shall be not more than 11 m2, with no dimension more than 3.7 m, if a fire compartment on either side of the fire separation is not sprinklered.
(2) The size of an opening in an interior fire separation required to be protected with a closure shall be not more than 22 m2, with no dimension more than 6 m, provided the fire compartments on both sides of the fire separation are sprinklered.
3.1.8.7. Location of Fire Dampers and Smoke Dampers
(1) Except as provided in Article 3.1.8.8., a fire damper having a fire-protection rating conforming to Sentence 3.1.8.4.(2) shall be installed in conformance with Article 3.1.8.9. in ducts or air-transfer openings that penetrate an assembly required to be a fire separation.
(2) Except as provided in Article 3.1.8.8A., a smoke damper or a combination smoke and fire damper shall be installed in conformance with Article 3.1.8.9A. in ducts or air-transfer openings that penetrate an assembly required to be a fire separation, where the fire separation,
(a) separates a public corridor,
(b) contains an egress door referred to in Sentence 3.4.2.4.(2),
(c) serves an assembly, care, care and treatment, detention or residential occupancy, or
(d) is installed to meet the requirements of Clause 3.3.1.7.(1)(b) or Sentence 3.3.3.5.(4) or 3.3.4.11.(4).
3.1.8.8. Fire Dampers Waived
(1) Except as permitted in Sentences (2) to (4), the requirement for fire dampers described in Sentence 3.1.8.7.(1) is permitted to be waived for,
(a) ducts that serve commercial cooking equipment,
(b) continuous noncombustible ducts having a melting point above 760°C that penetrate a vertical fire separation required by Sentence 3.3.1.1.(1) between suites of assembly, mercantile, low hazard industrial, medium hazard industrial or high hazard industrial occupancy,
(c) ducts or air-transfer openings that penetrate a vertical fire separation not required to have a fire-resistance rating, and
(d) noncombustible ducts or air-transfer openings that penetrate a horizontal fire separation not required to have a fire-resistance rating.
(2) The requirement for fire dampers described in Sentence 3.1.8.7.(1) is permitted to be waived for noncombustible branch ducts having a melting point above 760°C that penetrate a fire separation,
(a) provided the ducts,
(i) have a cross-sectional area not more than 130 cm2 and serve only air-conditioning units or combined air-conditioning and heating units discharging air not more than 1.2 m above the floor, or
(ii) extend not less than 500 mm inside exhaust duct risers that are under negative pressure and in which the airflow is upward as required by Article 3.6.3.4., or
(b) provided the fire separation separates a vertical service space from the remainder of the building and provided each individual duct exhausts directly to the outdoors at the top of the vertical service space.
(3) In elementary and secondary schools, a continuous noncombustible duct having a melting point above 760°C that pierces a fire separation having a fire-resistance rating of 30 min need not be equipped with a fire damper at the fire separation.
(4) In a Group B, Division 3 occupancy which contains sleeping accommodation for not more than 10 persons, which has not more than six occupants who require assistance in evacuation in case of an emergency and which is equipped with a fire alarm system, a duct need not be equipped with a fire damper at a fire separation, provided duct-type smoke detectors have been installed to control smoke circulation as described in Article 3.2.4.13.
3.1.8.8A. Smoke Dampers Waived
(1) Except as permitted in Sentence (2), the requirement for smoke dampers or combination smoke and fire dampers described in Sentence 3.1.8.7.(2) is permitted to be waived for ducts,
(a) that serve commercial cooking equipment,
(b) in which all inlet and outlet openings serve not more than one fire compartment,
(c) that penetrate a vertical fire separation referred to in Clause 3.3.1.7.(1)(b) or in Sentence 3.3.3.5.(4), provided,
(i) the movement of air is continuous, and
(ii) the configuration of the air-handling system prevents the recirculation of exhaust or return air under fire emergency conditions, or
(d) that penetrate a vertical fire separation not required to have a fire-resistance rating and located within the fire compartment required in Sentence 3.3.3.5.(2).
(2) The requirement for smoke dampers or combination smoke and fire dampers described in Sentence 3.1.8.7.(2) is permitted to be waived for noncombustible branch ducts having a melting point above 760°C that penetrate a fire separation,
(a) provided the ducts,
(i) have a cross-sectional area not more than 130 cm² and serve only air-conditioning units or combined air-conditioning and heating units discharging air not more than 1.2 m above the floor,
(ii) extend not less than 500 mm inside exhaust duct risers that are under negative pressure and in which the airflow is upward as required by Article 3.6.3.4., or
(iii) are required to function as part of an air handling system used to provide make-up air in accordance with Sentence 3.2.6.2.(5.1), or any other system used to limit smoke movement, or,
(b) provided the fire separation separates a vertical service space from the remainder of the building and provided each individual duct exhausts directly to the outdoors at the top of the vertical service space.
3.1.8.9. Installation of Fire Dampers
(1) A fire damper shall be arranged to close automatically upon the operation of a fusible link conforming to ULC-S505, “Fusible Links for Fire Protection Service”, or other heat-actuated or smoke-actuated device.
(2) A heat-actuated device referred to in Sentence (1) shall,
(a) be located where it is readily affected by an abnormal rise of temperature in the duct, and
(b) have a temperature rating approximately 30°C above the maximum temperature that would exist in the system either with the system in operation or shut down.
(3) A fire damper shall be installed in the plane of the fire separation so as to stay in place should the duct be dislodged during a fire.
(4) A fire damper shall be installed in the vertical or horizontal position in which it was tested.
(5) A tightly fitted access door shall be installed for each fire damper to provide access for the inspection of the damper and the resetting of the release device.
3.1.8.9A. Installation of Smoke Dampers
(1) Where smoke dampers are used as a closure in an air-transfer opening, they shall be installed in the plane of the fire separation.
(2) Where combination smoke and fire dampers are used as a closure in a duct, they shall be installed within 610 mm of the plane of the fire separation, provided there is no inlet or outlet opening between the fire separation and the damper.
(3) Except as required by a smoke control system, smoke dampers and combination smoke and fire dampers shall be configured so as to close automatically upon a signal from an adjacent smoke detector located as described in CAN/ULC-S524, “Installation of Fire Alarm Systems”, within 1.5 m horizontally of the duct or air-transfer opening in the fire separation,
(a) on both sides of the air-transfer opening, or
(b) in the duct downstream of the smoke damper or combination smoke and fire damper.
(4) Smoke dampers or combination smoke and fire dampers shall be installed in the vertical or horizontal position in which they were tested.
(5) A tightly fitted access door shall be installed for each smoke damper and combination smoke and fire damper to provide access for their inspection and the resetting of the release device.
3.1.8.10. Twenty-Minute Closures
(1) A door assembly having a fire-protection rating not less than 20 min is permitted to be used as a closure in,
(a) a fire separation not required to have a fire-resistance rating more than 1 h, located between,
(i) a public corridor and a suite,
(ii) a corridor and adjacent sleeping rooms, or
(iii) a corridor and adjacent classrooms, offices and libraries in Group A, Division 2 major occupancies, or
(b) a fire separation not required to have a fire-resistance rating more than 45 min, located in a building not more than 3 storeys in building height.
(2) The requirements for noncombustible sills and combustible floor coverings in NFPA 80, “Fire Doors and Other Opening Protectives”, do not apply to a door described in Sentence (1).
(3) A door described in Sentence (1) shall have a clearance not more than 6 mm at the bottom and not more than 3 mm at the sides and top.
(4) In elementary and secondary schools, a door assembly conforming to Articles 9.10.13.2. and 9.10.13.3. is permitted to be used as a closure in a fire separation having a fire-resistance rating of 30 min.
3.1.8.11. Self-Closing Devices
(1) Except as provided in Sentences (2) to (5) and 3.3.3.2.(5), every door in a fire separation shall be equipped with a self-closing device designed to return the door to the closed position after each use.
(2) Self-closing devices need not be provided on doors to freight elevators and dumbwaiters.
(3) In a building that is not more than 3 storeys in building height, a self-closing device is not required on a door that is located between a classroom and a corridor providing access to exit from the classroom, except that a self-closing device is required on a door between a hazardous classroom and the corridor in an elementary or secondary school.
(4) In a building that is not more than 3 storeys in building height, a self-closing device is not required on a door between a public corridor and an adjacent room or suite of business and personal services occupancy if the door is not located in,
(a) a dead-end portion of the corridor, or
(b) a corridor that serves a hotel.
(5) Within a fire compartment in a hospital or long-term care home that complies with the requirements of Article 3.3.3.5., a self-closing device is not required on a door that is located between,
(a) a patient’s or resident’s sleeping room and a corridor serving the patient’s or resident’s sleeping room, or
(b) a patient’s or resident’s sleeping room and an adjacent room that serves the patient’s or resident’s sleeping room.
3.1.8.12. Hold-Open Devices
(1) Except as provided in Sentences 3.1.8.9.(1) and 3.1.8.9A.(3), a hold-open device is permitted to be used on a closure in a required fire separation, other than on an exit stair door in a building more than 3 storeys in building height and on a door for a vestibule required by Article 3.3.5.7., provided the device is designed to release the closure in conformance with this Article.
(2) Except as provided in Sentences (5) and (6), where the building is provided with a fire alarm system, a hold-open device permitted by Sentence (1) shall release,
(a) in a single-stage system, upon any signal from the fire alarm system, and
(b) in a two-stage system,
(i) upon any alert signal from the fire alarm system, or
(ii) upon actuation of any adjacent smoke detectors.
(3) Where the building is provided with a fire alarm system, a hold-open device permitted by Sentence (1) shall release upon a signal from a smoke detector connected to the fire alarm system and located as described in CAN/ULC-S524, “Installation of Fire Alarm Systems”, where the hold-open device is used on,
(a) an exit door,
(b) a door opening into a public corridor,
(c) an egress door referred to in Sentence 3.4.2.4.(2),
(d) a door serving an assembly, care, care and treatment, detention, or residential occupancy,
(e) a door in a fire separation referred to in Clause 3.3.1.7.(1)(b) or in Sentence 3.3.3.5.(4) or 3.3.4.11.(4), or
(f) a door required to function as part of a smoke control system.
(4) Where the building is not provided with a fire alarm system, a hold-open device permitted by Sentence (1) shall release upon a signal from a smoke alarm located on either side of the fire separation at ceiling level within 1.5 m horizontally of the closure opening in the fire separation, where the hold-open device is used on closures described in Clauses (3)(a) to (e).
(5) Where a hold-open device is used on closures other than those described in Sentences (3) and (4), it is permitted to be released upon actuation of a heat-actuated device.
(6) A hold-open device used on a door located between a corridor used by the public and an adjacent sleeping room in a care and treatment occupancy need not release automatically as described in Sentence (2).
3.1.8.13. Door Latches
(1) Except as permitted by Sentence 3.3.3.2.(5) and Article 3.3.3.5., a swing-type door in a fire separation shall be equipped with a positive latching mechanism designed to hold the door in the closed position after each use.
3.1.8.14. Wired Glass and Glass Block
(1) Except as permitted by Articles 3.1.8.16. and 3.1.8.17. for the separation of exits, an opening in a fire separation having a fire-resistance rating not more than 1 h is permitted to be protected with fixed wired glass assemblies or glass blocks installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives”.
(2) Wired glass assemblies permitted by Sentence (1) and described in MMAH Supplementary Standard SB-2, “Fire Performance Ratings”, are permitted to be used as closures in vertical fire separations without being tested in accordance with Sentence 3.1.8.4.(1).
(3) Glass blocks permitted by Sentence (1) shall be installed in accordance with Subsection 4.3.2. and reinforced with steel reinforcement in each horizontal joint.
3.1.8.15. Temperature Rise Limit for Doors
(1) Except as permitted by Article 3.1.8.17., the maximum temperature rise on the opaque portion of the unexposed side of a door used as a closure in a fire separation in a location shown in Table 3.1.8.15., shall conform to the Table when tested in conformance with Sentence 3.1.8.4.(1).
Table 3.1.8.15.
Restrictions on Temperature Rise and Glazing for Closures
Forming Part of Articles of 3.1.8.15. and 3.1.8.16.
Item |
Column 1 Location |
Column 2 Minimum Required Fire-Protection Rating of Door |
Column 3 Maximum Temperature Rise on Opaque Portion of Unexposed Side of Door, °C |
Column 4 Maximum Area of Wired Glass in Door, m2 |
Column 5 Maximum Aggregate Area of Glass Block and Wired Glass Panels not in Door, m2 |
1. |
Between a dead-end corridor and an adjacent occupancy where the corridor provides the only access to exit and is required to have a fire-resistance rating |
Less than 45 min |
No limit |
No limit |
No limit |
45 min |
250 after 30 min |
0.0645 |
0.0645 |
||
2. |
Between an exit enclosure and the remainder of the floor area in buildings not more than 3 storeys in building height |
All ratings |
No limit |
0.8 |
0.8 |
3. |
Between an exit enclosure and the remainder of the floor area (except as permitted above) |
45 min |
250 after 30 min |
0.0645 |
0.0645 |
|
1.5 h |
250 after 1 h |
0.0645 |
0.0645 |
|
|
2 h |
250 after 1 h |
0.0645 |
0.0645 |
|
4. |
In a firewall |
1.5 h |
250 after 30 min |
0.0645 |
0 |
|
|
3 h |
250 after 1 h |
0 |
0 |
3.1.8.16. Area Limits for Wired Glass and Glass Block
(1) Except as permitted by Article 3.1.8.17., the maximum area of wired glass in a door used in the locations shown in Table 3.1.8.15. shall conform to the Table.
(2) Except as permitted by Article 3.1.8.17., the maximum area of glass block and wired glass panels not in a door, used in the locations shown in Table 3.1.8.15., shall conform to the Table.
3.1.8.17. Temperature Rise and Area Limits Waived
(1) The temperature rise limits and glass area limits required by Articles 3.1.8.15. and 3.1.8.16. are waived for a closure between an exit enclosure and an enclosed vestibule or corridor provided,
(a) the vestibule or corridor is separated from the remainder of the floor area by a fire separation having a fire-resistance rating not less than 45 min,
(b) the fire separation required by Clause (a) contains no wired glass or glass block within 3 m of the closure into the exit enclosure, and
(c) the vestibule or corridor contains no occupancy.
3.1.8.18. Sprinkler Protected Glazed Wall Assembly
(1) A sprinkler protected glazed wall assembly shall be constructed in accordance with the requirements of ULC/ORD C263.1, “Sprinkler-Protected Windows Systems”.
(2) A sprinkler protected glazed wall assembly shall not be installed in,
(a) fire separations requiring a fire-resistance rating of more than two hours,
(b) a firewall,
(c) a high hazard industrial occupancy, or
(d) any part of an exit serving,
(i) a floor area subject to the requirements of Subsection 3.2.6.,
(ii) a care occupancy,
(iii) a care and treatment occupancy,
(iv) a detention occupancy, or
(v) a residential occupancy.
(3) Where a sprinkler protected glazed wall assembly is installed in an exit fire separation permitted in Sentence (2),
(a) the building shall be sprinklered, and
(b) the exits protected with the sprinkler protected glazed wall assemblies shall not comprise more than one-half of the required number of exits from any floor area.
3.1.9. Penetrations in Fire Separations and Fire-Rated Assemblies
3.1.9.1. Fire Stops
(1) Except as provided in Sentences (2) to (5) and Article 3.1.9.3A., penetrations of a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating shall be,
(a) sealed by a fire stop that, when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems”, has an F rating not less than the fire-protection rating required for closures in the fire separation in conformance with Table 3.1.8.4., or
(b) tightly fitted.
(2) Penetrations of a firewall or a horizontal fire separation that is required to have a fire-resistance rating in conformance with Article 3.2.1.2. shall be sealed at the penetration by a fire stop that, when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems”, has an FT rating not less than the fire-resistance rating required for the fire separation.
(3) Penetrations of a fire separation in conformance with Sentence 3.6.4.2.(2) shall be sealed by a fire stop that, when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems”, has an FT rating not less than the fire-resistance rating required for the fire separation of the assembly.
(4) Sprinklers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the fire stop requirements of Sentence (1), (2) or (3), provided the annular space created by the penetration of a fire sprinkler is covered by a metal escutcheon plate in accordance with NFPA 13, “Installation of Sprinkler Systems”.
(5) Unless specifically designed with a fire stop, fire dampers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the fire stop requirements of Sentence (1), (2) or (3), provided the fire damper is installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives”.
3.1.9.2. Combustibility of Service Penetrations
(1) Except as permitted by Articles 3.1.9.3. and 3.1.9.4., pipes, ducts, electrical outlet boxes, totally enclosed raceways or other similar service equipment that penetrate an assembly required to have a fire-resistance rating shall be noncombustible unless the assembly has been tested incorporating that service equipment.
3.1.9.3. Penetration by Wires, Cables and Outlet Boxes
(1) Optical fibre cables and electrical wires and cables in totally enclosed noncombustible raceways are permitted to penetrate an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2.
(2) Except as permitted by Sentence (3), totally enclosed nonmetallic raceways conforming to Article 3.1.5.20., optical fibre cables, and electrical wires and cables, single or grouped, with combustible insulation, jackets or sheathes that conform to the requirements of Clause 3.1.5.18.(1)(a) and that are not installed in totally enclosed noncombustible raceways are permitted to penetrate an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2., provided the overall diameter of the single or grouped wires or cables, or the raceways is not more than 25 mm.
(3) Single conductor metal sheathed cables with combustible jacketing that are more than 25 mm in overall diameter are permitted to penetrate a fire separation required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2., provided the cables are not grouped and are spaced a minimum of 300 mm apart.
(4) Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2., provided the concrete cover between the raceway and the bottom of the slab is not less than 50 mm.
(5) Combustible electrical outlet boxes are permitted in an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2., provided the opening through the membrane into the box is not more than 160 cm2.
(6), (7) Revoked: O. Reg. 762/20, s. 4.
3.1.9.3A. Penetration by Outlet Boxes
(1) Except as provided in Sentences (2) and (3), outlet boxes are permitted to penetrate the membrane of an assembly required to have a fire-resistance rating, provided they are sealed at the penetration by a fire stop that has an FT rating not less than the fire-resistance rating of the fire separation when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems”.
(2) Except as provided in Sentences 3.1.9.1.(2) and (3), noncombustible outlet boxes that penetrate a vertical fire separation or a membrane forming part of an assembly required to have a fire-resistance rating need not conform to Sentence (1), provided,
(a) they do not exceed,
(i) 160 cm² in area, and
(ii) an aggregate area of 650 cm² in any 9.3 m² of surface area, and
(b) the annular space between the membrane and noncombustible electrical outlet boxes does not exceed 3 mm.
(3) In addition to the requirements of Sentence (2), outlet boxes on opposite sides of a vertical fire separation having a fire-resistance rating shall be separated by,
(a) a horizontal distance of not less than 600 mm, or
(b) a fire block conforming to Article 3.1.11.7.
3.1.9.4. Combustible Piping Penetrations
(1) Except as permitted by Sentences (3) to (8), combustible piping shall not be used if any part of the piping system penetrates,
(a) a fire separation required to have a fire-resistance rating, or
(b) a membrane that forms part of an assembly required to have a fire-resistance rating.
(2) Combustible piping that is part of a system described in Sentence (1) shall not be located in a vertical service space.
(3) Except as provided by Sentences (4) to (7), combustible piping is permitted to penetrate a fire separation required to have a fire-resistance rating or is permitted to penetrate a membrane that forms part of an assembly required to have a fire-resistance rating, provided the piping is sealed at the penetration by a fire stop that has an F rating not less than the fire-resistance rating required for the fire separation when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems”, with a pressure differential of 50 Pa between the exposed and unexposed sides, with the higher pressure on the exposed side.
(4) Except as required by Sentence (7), combustible drain piping is permitted to penetrate a horizontal fire separation, provided it leads directly from a noncombustible water closet through a concrete floor slab and the piping is sealed at the penetration by a fire stop in conformance with Clause 3.1.9.1.(1)(a).
(5) Except as required by Sentence (7), combustible piping is permitted to penetrate a vertical or horizontal fire separation, provided the fire compartments on each side of the fire separation are sprinklered and the piping is sealed at the penetration by a fire stop in conformance with Clause 3.1.9.1.(1)(a).
(6) Except as required by Sentence (7), combustible piping not more than 25 mm in diameter containing chlorine gas is permitted to penetrate a fire separation between a chlorine gas service room built in conjunction with a public pool or public spa and the remainder of the building, provided the piping is sealed at the penetration by a fire stop in conformance with Clause 3.1.9.1.(1)(a).
(7) Where combustible piping penetrates a firewall or a horizontal fire separation described in Sentence 3.2.1.2.(1), the piping shall be sealed at the penetration by a fire stop that has an FT rating not less than the fire-resistance rating required for the firewall or horizontal fire separation when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems”, and,
(a) the fire stop shall have been tested with a pressure differential of 50 Pa between the exposed and unexposed sides, with the higher pressure on the exposed side, or
(b) the fire compartments on each side of the firewall or horizontal fire separation shall be sprinklered.
(8) Combustible piping for central vacuum cleaning systems is permitted to penetrate a fire separation, provided the installation conforms to the requirements that apply to combustible piping specified in Sentence (3).
3.1.9.5. Openings through a Membrane Ceiling
(1) A membrane ceiling forming part of an assembly assigned a fire-resistance rating on the basis of MMAH Supplementary Standard SB-2, “Fire Performance Ratings”, is permitted to be penetrated by openings leading into ducts within the ceiling space provided,
(a) the ducts are sheet steel, and
(b) the amount of openings and their protection conform to the requirements of MMAH Supplementary Standard SB-2, “Fire Performance Ratings”.
(2) Fire stop flaps in ceiling membranes required in Sentence (1) shall conform to CAN/ULC-S112.2, “Fire Test of Ceiling Firestop Flap Assemblies”.
3.1.9.6. Plenums
(1) A ceiling assembly used as a plenum shall conform to Article 3.6.4.3.
3.1.10. Firewalls
3.1.10.1. Prevention of Firewall Collapse
(1) Except as permitted by Sentence (2), the connections and supports for structural framing members that are connected to or supported on a firewall and have a fire-resistance rating less than that required for the firewall, shall be designed so that the failure of the framing systems during a fire will not affect the integrity of the firewall during the fire.
(2) Sentence (1) does not apply to a firewall consisting of two separate wall assemblies each tied to its respective building frame but not to each other, provided each wall assembly is,
(a) a fire separation having one-half of the fire-resistance rating required for the firewall by Sentences 3.1.10.2.(1) and (2), and
(b) designed so that the collapse of one wall assembly will not cause the collapse of the other.
(3) A firewall is permitted to be supported on the structural frame of a building of noncombustible construction provided the supporting frame has a fire-resistance rating not less than that required for the firewall.
(4) Piping, ducts and totally enclosed noncombustible raceways shall be installed so that their collapse will not cause the collapse of the firewall.
3.1.10.2. Rating of Firewalls
(1) A firewall that separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2 major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h, except that where the upper portion of a firewall separates floor areas containing other than Group E or Group F, Division 1 or 2 major occupancies, the fire-resistance rating of the upper portion of the firewall is permitted to be not less than 2 h.
(2) A firewall that separates a building or buildings with floor areas containing major occupancies other than Group E or Group F, Division 1 or 2 shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 2 h.
(3) Except as permitted by Sentence (4), the required fire-resistance rating of a firewall, except for closures, shall be provided by masonry or concrete.
(4) A firewall permitted to have a fire-resistance rating not more than 2 h need not be constructed of masonry or concrete provided,
(a) the assembly providing the fire-resistance rating is protected against damage that would compromise the integrity of the assembly,
(b) the design conforms to Article 4.1.5.17.,
(c) the level of performance of the firewall is not less than of masonry or concrete in the areas of,
(i) performance during fire conditions,
(ii) mechanical damage during the normal use of the building, and
(iii) resistance to damage from moisture,
(d) the firewall separates buildings or buildings with floor areas that do not contain,
(i) a Group B, Division 1 major occupancy, or
(ii) a Group B, Division 2 major occupancy, and
(e) the firewall does not separate a building regulated by the provisions of Subsection 3.2.6. or a building within the scope of Article 3.2.2.43A. or 3.2.2.50A. from another building unless the buildings on both sides of the firewall are sprinklered.
3.1.10.3. Continuity of Firewalls
(1) A firewall shall extend from the ground continuously through, or adjacent to, all storeys of a building or buildings so separated, except that a firewall located above a basement storage garage conforming to Article 3.2.1.2. is permitted to commence at the floor assembly immediately above the storage garage.
(2) A firewall is permitted to terminate on the underside of a reinforced concrete roof slab provided,
(a) the roof slab on both sides of the firewall has a fire-resistance rating not less than,
(i) 1 h if the firewall is required to have a fire-resistance rating not less than 2 h, or
(ii) 2 h if the firewall is required to have a fire-resistance rating not less than 4 h, and
(b) there are no concealed spaces within the roof slab in that portion immediately above the firewall.
3.1.10.4. Parapets
(1) Except as permitted by Sentences (2) and 3.1.10.3.(2), a firewall shall extend above the roof surface to form a parapet not less than,
(a) 150 mm high for a firewall required to have a fire-resistance rating not less than 2 h, and
(b) 900 mm high for a firewall required to have a fire-resistance rating not less than 4 h.
(2) A firewall that separates two buildings with roofs at different elevations need not extend above the upper roof surface to form a parapet, provided the difference in elevation between the roofs is more than 3 m.
3.1.10.5. Maximum Openings
(1) Openings in a firewall shall conform to the size limits described in Article 3.1.8.6. and the aggregate width of openings shall be not more than 25% of the entire length of the firewall.
3.1.10.6. Exposure Protection for Adjacent Walls
(1) The requirements of Article 3.2.3.14. shall apply to the external walls of two buildings that meet at a firewall at an angle less than 135°.
3.1.10.7. Combustible Projections
(1) Combustible material shall not extend across the end of a firewall but is permitted to extend across a roof above a firewall that is terminated in conformance with Sentence 3.1.10.3.(2).
(2) If buildings are separated by a firewall, combustible projections on the exterior of one building, including balconies, platforms, canopies, eave projections and stairs, that extend outward beyond the end of the firewall, shall not be permitted within 2.4 m of combustible projections and window or door openings of the adjacent building.
3.1.11. Fire Blocks in Concealed Spaces
3.1.11.1. Separation of Concealed Spaces
(1) Concealed spaces in interior wall, ceiling and crawl spaces shall be separated from concealed spaces in exterior walls and attic or roof spaces by fire blocks conforming to Article 3.1.11.7.
3.1.11.2. Fire Blocks in Wall Assemblies
(1) Except as permitted by Sentence (2), fire blocks conforming to Article 3.1.11.7. shall be provided to block off concealed spaces within a wall assembly,
(a) at every floor level,
(b) at every ceiling level where the ceiling forms part of an assembly required to have a fire-resistance rating, and
(c) so that the maximum horizontal dimension is not more than 20 m and the maximum vertical dimension is not more than 3 m.
(2) Fire blocks conforming to Sentence (1) are not required provided,
(a) the wall space is filled with insulation,
(b) the exposed construction materials and any insulation within the wall space are noncombustible,
(c) the exposed materials within the wall space, including insulation but not including wiring, piping or similar services, have a flame-spread rating not more than 25 on any exposed surface, or on any surface that would be exposed by cutting through the material in any direction, and fire blocks are installed so that the vertical distance between them is not more than 10 m, or
(d) the insulated wall assembly contains not more than one concealed air space and the horizontal thickness of that air space is not more than 25 mm.
3.1.11.3. Fire Blocks between Nailing and Supporting Elements
(1) In a building required to be of noncombustible construction, a concealed space in which there is an exposed ceiling finish with a flame-spread rating more than 25, shall be provided with fire blocks conforming to Article 3.1.11.7. between wood nailing elements, so that the maximum area of the concealed space is not more than 2 m2.
(2) In a building required to be of noncombustible construction, fire blocks conforming to Article 3.1.11.7. shall be provided in the concealed spaces created by the wood members permitted by Sentence 3.1.5.8.(2), so that the maximum area of a concealed space is not more than 10 m2.
(3) In a building or part of a building permitted to be of encapsulated mass timber construction, a concealed space in which there is an exposed ceiling finish with a flame-spread rating more than 25 shall be provided with fire blocks conforming to Article 3.1.11.7. between wood nailing elements so that the maximum area of the concealed space is not more than 2 m2.
(4) In a building or part of a building permitted to be of encapsulated mass timber construction, fire blocks conforming to Article 3.1.11.7. shall be provided in the concealed spaces created by the wood members permitted by Sentence 3.1.6.12.(1) so that the maximum area of a concealed space is not more than 10 m2.
3.1.11.4. Fire Blocks between Vertical and Horizontal Spaces
(1) Fire blocks conforming to Article 3.1.11.7. shall be provided,
(a) at all interconnections between concealed vertical and horizontal spaces in interior coved ceilings, drop ceilings and soffits in which the exposed construction materials within the space have a flame‑spread rating more than 25, and
(b) at the end of each run and at each floor level in concealed spaces between stair stringers in which the exposed construction materials within the space have a flame‑spread rating more than 25.
3.1.11.5. Fire Blocks in Horizontal Concealed Spaces
(1) Except for a crawl space conforming to Sentence 3.1.11.6.(1), a horizontal concealed space within a floor assembly or roof assembly of combustible construction, in which sprinklers are not installed, shall be separated by construction conforming to Article 3.1.11.7. into compartments not more than,
(a) 600 m2 in area with no dimension more than 60 m, if the exposed construction materials within the space have a flame-spread rating not more than 25, and
(b) 300 m2 in area with no dimension more than 20 m, if the exposed construction materials within the space have a flame-spread rating more than 25.
(2) A concealed space in an exterior cornice, a mansard style roof, a balcony or a canopy in which exposed construction materials within the space have a flame‑spread rating more than 25, shall be separated by construction conforming to Article 3.1.11.7.,
(a) at locations where the concealed space extends across the ends of required vertical fire separations, and
(b) so that the maximum dimension in the concealed space is not more than 20 m.
(3) Except as provided by Sentence (4), a horizontal concealed space within a floor assembly or roof assembly of combustible construction in a building within the scope of Article 3.2.2.43A. or 3.2.2.50A. shall be separated by construction conforming to Article 3.1.11.7. into compartments not more than,
(a) 600 m2 in area with no dimension more than 60 m, if the exposed construction materials within the space have a flame-spread rating not more than 25, and
(b) 300 m2 in area with no dimension more than 20 m, if the exposed construction materials within the space have a flame-spread rating more than 25.
(3.1) Except for crawl spaces conforming to Sentence 3.1.11.6.(1) and except as provided in Sentence (4), in buildings or parts of buildings conforming to Article 3.2.2.42A. or 3.2.2.49A., horizontal concealed spaces within a floor assembly or roof assembly of encapsulated mass timber construction shall be separated by construction conforming to Article 3.1.11.7. into compartments that are not more than,
(a) 600 m2 in area with no dimension more than 60 m, if the exposed construction materials within the space have a flame-spread rating not more than 25, and
(b) 300 m2 in area with no dimension more than 20 m, if the exposed construction materials within the space have a flame-spread rating not more than 25.
(4) Sentences (3) and (3.1) do not apply if the horizontal concealed space within the floor assembly or roof assembly is entirely filled with noncombustible insulation such that any air gap between the top of the insulation and the underside of the floor or roof deck does not exceed 50 mm.
3.1.11.6. Fire Blocks in Crawl Spaces
(1) A crawl space that is not considered as a basement by Article 3.2.2.9. and in which sprinklers are not installed, shall be separated by construction conforming to Article 3.1.11.7. into compartments not more than 600 m2 in area with no dimension more than 30 m.
3.1.11.7. Fire Block Materials
(1) Except as permitted by Sentences (2) to (4) and (7) fire blocks shall remain in place and prevent the passage of flames for not less than 15 min when subjected to the standard fire exposure in CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials”.
(2) Gypsum board not less than 12.7 mm thick and sheet steel not less than 0.38 mm thick need not be tested in conformance with Sentence (1) provided all joints have continuous support.
(3) In a building required to be of noncombustible construction, wood nailing elements described in Article 3.1.5.6. need not be tested in conformance with Sentence (1).
(3.1) In a building or part of a building permitted to be of encapsulated mass timber construction, wood nailing elements referred to in Article 3.1.6.11. need not be tested in conformance with Sentence (1).
(4) In a building permitted to be of combustible construction, in a combustible roof system permitted by Sentences 3.1.5.3.(2) and 3.1.6.7.(1), and in a raised platform permitted by Sentence 3.1.5.8.(2) or 3.1.6.12.(1), fire blocks are permitted to be,
(a) solid lumber or a structural composite lumber product conforming to ASTM D5456, “Evaluation of Structural Composite Lumber Products”, not less than 38 mm thick,
(b) phenolic bonded plywood, OSB or waferboard not less than 12.5 mm thick with joints supported, or
(c) two thicknesses of lumber or a structural composite lumber product conforming to ASTM D5456, “Evaluation of Structural Composite Lumber Products”, each not less than 19 mm thick with joints staggered, where the width or height of the concealed space requires more than one piece of lumber or structural composite lumber product not less than 38 mm thick to block off the space.
(5) Openings through fire blocks shall be protected to maintain the integrity of the construction.
(6) Where fire blocks are penetrated by construction elements or by service equipment, a fire stop shall be used to seal the penetration.
(7) In a building permitted to be of combustible construction, semi-rigid fibre insulation board, produced from glass, rock or slag, is permitted to be used to block the vertical space in a double wythe wall assembly formed at the intersection of the floor assembly and the walls, provided the insulation board,
(a) has a density not less than 45 kg/m3,
(b) is securely fastened to one set of studs,
(c) extends from below the bottom of the top plates in the lower storey to above the top of the bottom plate in the upper storey, and
(d) completely fills the portion of the vertical space between the headers and between the wall plates.
3.1.12. Flame-Spread Rating and Smoke Developed Classification
3.1.12.1. Determination of Ratings
(1) Except as required by Sentence (2) and as permitted by Sentence (3), the flame-spread rating and smoke developed classification of a material, assembly, or structural member shall be determined on the basis of no fewer than three tests conducted in conformance with CAN/ULC-S102, “Test for Surface Burning Characteristics of Building Materials and Assemblies”.
(2) The flame-spread rating and smoke developed classification of a material or assembly shall be determined on the basis of no fewer than three tests conducted in conformance with CAN/ULC-S102.2, “Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies”, if the material or assembly,
(a) is designed for use in a relatively horizontal position with only its top surface exposed to air,
(b) cannot be tested in conformance with Sentence (1) without the use of supporting material that is not representative of the intended installation, or
(c) is thermoplastic.
(3) A material, assembly, or structural member is permitted to be assigned a flame-spread rating and smoke developed classification on the basis of MMAH Supplementary Standard SB-2, “Fire Performance Ratings”.
3.1.13. Interior Finish
3.1.13.1. Interior Finish Description
(1) Interior finish material shall include any material that forms part of the interior surface of a floor, wall, partition or ceiling, including,
(a) interior cladding of plaster, wood or tile,
(b) surfacing of fabric, paint, plastic, veneer or wallpaper,
(c) doors, windows and trim,
(d) lighting elements, such as light diffusers and lenses forming part of the finished surface of the ceiling, and
(e) carpet material that overlies a floor that is not intended as the finished floor.
3.1.13.2. Flame-Spread Rating
(1) Except as otherwise required or permitted by this Subsection, the flame-spread rating of interior wall and ceiling finishes, including glazing and skylights, shall be not more than 150 and shall conform to Table 3.1.13.2.
Table 3.1.13.2.
Flame-Spread Ratings
Forming Part of Sentence 3.1.13.2.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
|
Occupancy, Location or Element |
Maximum Flame-Spread Rating for Walls and Ceilings |
|
|
|
Sprinklered |
Not Sprinklered |
1. |
Group A, Division 1 occupancies, including doors, skylights, glazing and light diffusers and lenses |
150 |
75 |
2. |
Group B occupancies |
150 |
75 (2) |
3. |
Exits(1) |
25 |
25 |
4. |
Lobbies described in Sentence 3.4.4.2.(2) |
25 |
25 |
5. |
Covered vehicular passageways, except for roof assemblies of heavy timber construction in such passageways |
25 |
25 |
6. |
Vertical service spaces |
25 |
25 |
Notes to Table 3.1.13.2.:
(1) See Articles 3.1.13.8. and 3.1.13.10.
(2) Group B occupancies are required to be sprinklered. See Part 11 for renovations of existing non-sprinklered Group B occupancies.
(2) Except as permitted by Sentence (3), doors, other than those in Group A, Division 1 occupancies, need not conform to Sentence (1) provided they have a flame-spread rating not more than 200.
(3) Doors within a dwelling unit need not conform to Sentences (1) and (2).
(4) Up to 10% of the total wall area and 10% of the total ceiling area of a wall or ceiling finish that is required by Sentence (1) to have a flame-spread rating less than 150 is permitted to have a flame-spread rating not more than 150, except that up to 25% of the total wall area of lobbies described in Sentence 3.4.4.2.(2) is permitted to have a flame-spread rating not more than 150.
(5) Except in the case of Group A, Division 1 occupancies, combustible doors, skylights, glazing and light diffusers and lenses shall not be considered in the calculation of wall and ceiling areas described in Sentence (4).
3.1.13.3. Plumbing Fixtures and Bathrooms Finishes
(1) The flame-spread rating of interior wall and ceiling finishes for a bathroom in a suite of residential occupancy shall be not more than 200.
(2) Plumbing fixtures shall have a flame-spread rating not more than 200.
3.1.13.4. Light Diffusers and Lenses
(1) The flame-spread rating of combustible light diffusers and lenses in all occupancies other than Group A, Division 1 is permitted to be more than the flame-spread rating limits required elsewhere in this Subsection, provided the light diffusers and lenses,
(a) have a flame-spread rating not more than 250 and a smoke developed classification not more than 600 when tested in conformance with CAN/ULC-S102.2, “Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies”,
(b) fall to the bottom of the test apparatus before igniting when tested in conformance with ULC-S102.3, “Fire Test of Light Diffusers and Lenses”,
(c) are not prevented from falling from the ceiling by construction located beneath the elements, and
(d) are not used in a corridor that is required to be separated from the remainder of the building by a fire separation or in an exit shaft unless individual diffusers or lenses are not more than 1 m2 in area and are not less than 1.2 m apart.
3.1.13.5. Skylights
(1) Individual combustible skylights in a corridor that is required to be separated from the remainder of the storey by a fire separation shall be not more than 1 m2 in area and not less than 1.2 m apart.
3.1.13.6. Corridors
(1) Except as permitted by Sentences (2) and (3), the flame-spread rating shall be not more than 75 for the interior wall finish of,
(a) a public corridor,
(b) a corridor used by the public in,
(i) an assembly occupancy, or
(ii) a care, care and treatment or detention occupancy,
(c) a corridor serving classrooms, or
(d) a corridor serving sleeping rooms in a care, care and treatment or detention occupancy.
(2) The flame-spread rating limit specified in Sentence (1) does not apply to corridors referred to in Sentence (1) provided the flame-spread rating is not more than,
(a) 25 on the upper half of the wall, and
(b) 150 on the lower half of the wall.
(3) The flame-spread rating limits specified in Sentences (1) and (2) for corridors referred to in Sentence (1) do not apply to a corridor in which the flame-spread rating is not more than 150 provided the floor area is sprinklered.
(4) The flame-spread rating limits specified in Sentences (1) to (3) apply to occupancies in the corridor as well as to the corridor itself.
(5) Except in a floor area that is sprinklered and as permitted in Sentence (6), the interior ceiling finish of corridors and occupancies referred to in Sentences (1) and (4) shall have a flame-spread rating not more than 25.
(6) The flame-spread rating limits specified in Sentence (5) do not apply to a corridor in which the flame-spread rating is not more than 150 provided the floor area is sprinklered.
3.1.13.7. High Buildings
(1) Except as permitted by Sentences (2) and (3), the interior wall, ceiling and floor finishes in a building regulated by the provisions of Subsection 3.2.6. shall conform to the flame-spread rating requirements in Articles 3.1.13.2. to 3.1.13.6. and to the flame-spread rating and smoke developed classification values in Table 3.1.13.7.
Table 3.1.13.7.
Flame-Spread Rating and Smoke Developed Classification in a High Building
Forming Part of Sentences 3.1.13.7.(1) and (2)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
Column 5 |
Column 6 |
Column 7 |
|
Location or Element |
Maximum Flame-Spread Rating |
Maximum Smoke Developed Classification |
||||
|
|
Wall Surface |
Ceiling Surface (1) |
Floor Surface |
Wall Surface |
Ceiling Surface (1) |
Floor Surface |
1. |
Exit stairways, vestibules to exit stairs and lobbies described in Sentence 3.4.4.2.(2) |
25 |
25 |
25 |
50 |
50 |
50 |
2. |
Corridors not within suites |
(2) |
(2) |
300 |
100 |
50 |
500 |
3. |
Elevator cars |
75 |
75 |
300 |
450 |
450 |
450 |
4. |
Elevator vestibules |
25 |
25 |
300 |
100 |
100 |
300 |
5. |
Service spaces and service rooms |
25 |
25 |
25 |
50 |
50 |
50 |
6. |
Other locations and elements |
(2) |
(2) |
No limit |
300 |
50 |
No limit |
Notes to Table 3.1.13.7.:
(1) See Sentence 3.1.13.4.(1) for lighting elements.
(2) Other requirements of this Part apply.
(2) Except for a building of Group B major occupancy and elevator cars, the flame-spread rating and smoke developed classification of interior wall, floor and ceiling finishes need not conform to the values in Table 3.1.13.7., provided the building is sprinklered and the sprinkler system is electrically supervised in conformance with Sentences 3.2.4.10.(3) and 3.2.4.17.(1).
(3) Trim, millwork and doors in an exit stairway, a vestibule to an exit stairway, a lobby described in Sentence 3.4.4.2.(2), or a corridor not within a suite need not conform to the flame-spread rating and smoke developed classification requirements of Sentence (1), provided they have,
(a) a flame-spread rating not more than 150,
(b) a smoke developed classification not more than 300, and
(c) an aggregate area not more than 10% of the area of the wall or ceiling on which they occur.
(4) Except as permitted in Sentences (5) to (7), plumbing fixtures in a building regulated by the provisions of Subsection 3.2.6. shall have a smoke developed classification not more than 300.
(5) A plumbing fixture that is not located in a Group B occupancy need not comply with Sentence (4) if the building is sprinklered.
(6) A plumbing fixture may have a smoke developed classification more than 300 but not more than 500 if,
(a) it is in a room where the wall surfaces have a smoke developed classification not more than 200, and
(b) it is located in,
(i) a Group C occupancy, or
(ii) a Group B occupancy and the building is sprinklered.
(7) A therapeutic bathing system in a Group B occupancy need not comply with Sentence (4) if the room in which it is located,
(a) does not open directly into patients’ or residents’ sleeping rooms, and
(b) is sprinklered.
3.1.13.8. Noncombustible Construction
(1) In a building required to be of noncombustible construction,
(a) the flame-spread ratings required by Subsection 3.1.5. shall apply in addition to the requirements in this Subsection, and
(b) the flame-spread ratings for exits in this Subsection shall also apply to any surface in the exit that would be exposed by cutting through the material in any direction, except that this requirement does not apply to doors, heavy timber construction in a sprinklered building and fire-retardant treated wood.
3.1.13.9. Underground Walkways
(1) Except for paint, the interior wall and ceiling finishes of an underground walkway shall be of noncombustible materials.
3.1.13.10. Exterior Exit Passageway
(1) The wall and ceiling finishes of an exterior exit passageway that provides the only means of egress from the rooms or suites it serves, including the soffit beneath and the guard on the passageway, shall have a flame-spread rating not more than 25, except that a flame-spread rating not more than 150 is permitted for up to 10% of the total wall area and for up to 10% of the total ceiling area.
3.1.13.11. Elevator Cars
(1) The wall and ceiling surfaces of elevator cars shall have a flame-spread rating not more than 75.
(2) The wall, ceiling and floor surfaces of elevator cars shall have a smoke developed classification not more than 450.
3.1.13.12. Encapsulated Mass Timber Construction
(1) In a building or part of a building permitted to be of encapsulated mass timber construction,
(a) the flame-spread ratings required by Subsection 3.1.6. shall apply in addition to the requirements in this Subsection, and
(b) the flame-spread ratings for exits required by this Subsection shall also apply to any surface in the exit that would be exposed by cutting through the material in any direction, except that this requirement does not apply to doors, structural mass timber elements conforming to Sentence 3.1.6.4.(3), heavy timber construction and fire-retardant-treated wood.
3.1.14. Roof Assemblies
3.1.14.1. Fire-Retardant Treated Wood Roof Systems
(1) If a fire-retardant treated wood roof system is used to comply with the requirements of Subsection 3.2.2., the roof deck assembly shall meet the conditions of acceptance of CAN/ULC-S126, “Test for Fire Spread Under Roof-Deck Assemblies”.
(2) Supports for the roof deck assembly referred to in Sentence (1) shall consist of,
(a) fire-retardant treated wood,
(b) heavy timber construction,
(c) noncombustible construction, or
(d) a combination of the items described in Clauses (a) to (c).
3.1.14.2. Metal Roof Deck Assemblies
(1) Except as permitted by Sentence (2), a metal roof deck assembly shall meet the conditions of acceptance of CAN/ULC-S126, “Test for Fire Spread Under Roof-Deck Assemblies”, if,
(a) it supports a combustible material above the deck that could propagate a fire beneath the roof deck assembly, and
(b) the deck is used to comply with the requirements of Sentences 3.2.2.25.(2), 3.2.2.32.(2), 3.2.2.53.(2), 3.2.2.59.(2), 3.2.2.70.(2) and 3.2.2.76.(2) for noncombustible construction.
(2) The requirements of Sentence (1) are waived provided,
(a) the combustible material above the roof deck is protected,
(i) by not less than 12.7 mm thick gypsum board, mechanically fastened to a supporting assembly if located beneath the roof deck, or
(ii) by a thermal barrier conforming to Clause 3.1.5.12.(4)(c) or (d) that is located on the underside of the combustible material or beneath the roof deck,
(b) the building is sprinklered, or
(c) the roof assembly has a fire-resistance rating not less than 45 min.
3.1.15. Roof Covering
3.1.15.1. Roof Covering Classification
(1) A roof covering classification shall be determined in conformance with CAN/ULC-S107, “Fire Tests of Roof Coverings”.
3.1.15.2. Roof Coverings
(1) Except as provided in Sentences (2) to (5), every roof covering shall have a Class A, B or C classification as determined in accordance with Article 3.1.15.1.
(2) A roof covering is not required to have a Class A, B or C classification for,
(a) a tent,
(b) an air-supported structure,
(c) a building of Group A, Division 2 occupancy not more than 2 storeys in building height and not more than 1 000 m2 in building area, provided the roof covering is underlaid with noncombustible material, or
(d) a steel building system described in Article 4.3.4.3., provided the roof covering consists of metal sheets, metal shingles or other noncombustible roofing materials.
(3) Except as provided in Sentence (5), roof coverings on buildings within the scope of Article 3.2.2.43A. or 3.2.2.50A. shall have a Class A classification if the roof height is greater than 25 m measured from the floor of the first storey to the highest point of the roof.
(4) Except as provided in Sentence (5), roof coverings in buildings or parts of buildings permitted to be of encapsulated mass timber construction shall have a Class A classification if the roof height is greater than 25 m measured from the floor of the first storey to the highest point of the roof.
(5) Where buildings or parts of a building conforming to Article 3.2.2.42A., 3.2.2.43A., 3.2.2.49A or 3.2.2.50A include non-contiguous roof assemblies at different elevations, the roof coverings referred to in Sentences (3) and (4) are permitted to be evaluated separately to determine the roof covering classification required.
3.1.16. Fabrics
3.1.16.1. Fabric Awnings, Canopies and Marquees
(1) Fabrics used as part of an awning, canopy or marquee that is located within or attached to a building of any type of construction shall conform to CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics and Films”.
3.1.17. Occupant Load
3.1.17.1. Occupant Load Determination
(1) The occupant load of a floor area or part of a floor area, or of a building or part of a building not having a floor area, shall be based on,
(a) the number of seats in an assembly occupancy having fixed seats,
(b) two persons per sleeping room or sleeping area in a dwelling unit or suite, or
(c) the number of persons,
(i) for which the area is designed, or
(ii) determined from Table 3.1.17.1. for occupancies other than those described in Clauses (a) and (b).
Table 3.1.17.1.
Occupant Load
Forming Part of Article 3.1.17.1.
Item |
Column 1 Type of Use of Building or Floor Area or Part of Floor Area |
Column 2 Area per Person, m2 |
1. |
Assembly uses |
|
|
space with fixed seats |
See Clause (1)(a) |
|
space with non-fixed seats |
0.75 |
|
stages for theatrical performances |
0.75 |
|
space with non-fixed seats and tables |
0.95 |
|
standing space |
0.40 |
|
stadia and grandstands |
0.60 |
|
bowling alleys, pool and billiard rooms |
9.30 |
|
classrooms |
1.85 |
|
school shops and vocational rooms |
9.30 |
|
reading or writing rooms or lounges |
1.85 |
|
dining, alcoholic beverage and cafeteria space |
1.10 |
|
laboratories in schools |
4.60 |
|
exhibition halls other than those classified in Group E |
2.80 |
2. |
Care, care and treatment or detention uses |
|
|
B-1 : detention quarters |
11.60 |
|
B-2 : treatment and sleeping room areas |
10.00 |
|
B-3 : sleeping room areas |
10.00 |
|
(See also Article 3.7.1.3.) |
|
3. |
Residential uses |
|
|
dwelling units |
See Clause (1)(b) |
|
dormitories |
4.60 |
4. |
Business and personal services uses |
|
|
personal service shops |
4.60 |
|
offices |
9.30 |
5. |
Mercantile uses |
|
|
basements and first storeys |
3.70 |
|
second storeys having a principal entrance from a pedestrian |
3.70 |
|
thoroughfare or a parking area |
|
|
dining, alcoholic beverage and cafeteria space |
1.10 |
|
other storeys |
5.60 |
6. |
Industrial uses |
|
|
manufacturing or process rooms |
4.60 |
|
storage garages |
46.00 |
|
storage spaces (warehouse) |
28.00 |
|
aircraft hangars |
46.00 |
7. |
Other uses |
|
|
cleaning and repair of goods |
4.60 |
|
kitchens |
9.30 |
|
storage |
46.00 |
|
public corridors intended for occupancies in addition to pedestrian travel |
3.70 |
(2) If a floor area or part of it has been designed for an occupant load other than that determined from Table 3.1.17.1., a permanent sign indicating that occupant load shall be posted in a conspicuous location.
(3) For the purposes of this Article, mezzanines, tiers and balconies shall be regarded as part of the floor area.
(4) If a room or group of rooms is intended for different occupancies at different times, the value to be used from Table 3.1.17.1. shall be the value that gives the greatest number of persons for the occupancies concerned.
(5) Except as provided by Sentence (6) or (7), in dining, alcoholic beverage and cafeteria spaces the occupant load shall be determined from Table 3.1.17.1.
(6) The occupant load in Sentence (5) is permitted to be the number of persons for which the space is designed.
(7) The occupant load in Sentence (6) shall be not more than that determined by using an area of 0.6 m2 per person.
3.1.17.2. Dance Floor
(1) The occupant load of a room in which a dance floor is situated shall be calculated in respect of that portion of the room that is not occupied by the dance floor.
3.1.17.3. Public Pools
(1) The occupant load of a public pool, except a wave action pool, shall be determined by the following formula:
where,
D = the water surface area in square metres of the part of the pool that is deeper than 1 350 mm; and
S = the water surface area in square metres of the part of the pool that is 1 350 mm in depth or less.
(2) The occupant load of a wave action pool shall be determined by the following formula:
where,
D = the water surface area in square metres of the part of the pool where the still water depth is greater than 1 000 mm; and
S = the water surface area in square metres of the part of the pool where the still water depth is 1 000 mm or less.
3.1.18. Drainage and Grades
3.1.18.1. Drainage
(1) The building shall be located and the building site graded so that water will not accumulate at or near the building and will not adversely affect any adjacent properties.
3.1.19. Above Ground Electrical Conductors
3.1.19.1. Clearance to Buildings
(1) A building shall not be located beneath existing above ground electrical conductors.
(2) The horizontal clearance measured from the maximum conductor swing to the building, including balconies, fire escapes, flat roofs or other accessible projections beyond the face of the building, shall,
(a) be not less than 1 m, for electrical conductors carrying voltages 750 V or less, except where necessary to connect to the electrical wiring of the building,
(b) be not less than 3 m, for electrical conductors carrying voltages greater than 750 V but not exceeding 46 kV,
(c) be not less than 3.7 m, for electrical conductors carrying voltages greater than 46 kV but not exceeding 69 kV, or
(d) conform to the requirements of CAN/CSA-C22.3 No.1, “Overhead Systems”, for electrical conductors carrying voltages greater than 69 kV.
(3) Where the swing of an above ground electrical conductor not owned or operated by an electrical supply authority is not known, a swing of not less than 1.8 m shall be used.
(4) Sentences (1) to (3) do not apply to a building containing electrical equipment and electrical installations used exclusively in the generation, transformation or transmission of electrical power or energy intended for sale or distribution to the public.
3.1.20. Glass in Guards
3.1.20.1. Glass
(1) Except as provided in Sentence 3.3.4.7.(1), glass in guards shall conform to MMAH Supplementary Standard SB-13, “Glass in Guards”.
3.1.21. Revoked: O. Reg. 88/19, s. 27.
Section 3.2. Building Fire Safety
3.2.1. General
3.2.1.1. Exceptions in Determining Building Height
(1) A rooftop enclosure provided for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, shall not be considered as a storey in calculating the building height.
(2) Space under tiers of seats in a building of the arena type shall not be considered as adding to the building height provided the space is used only for dressing rooms, concession stands and similar purposes incidental to the major occupancy of the building.
(3) Except as required by Sentence (5), the space above a mezzanine need not be considered as a storey in calculating building height provided,
(a) the aggregate area of mezzanines that are not superimposed does not exceed 40% of the open area of the room in which they are located, and
(b) except as permitted in Sentence (8) and Sentence 3.3.2.11.(3) the space above the mezzanine is used as an open area without partitions or subdividing walls higher than 1 070 mm above the mezzanine floor.
(4) Except as required by Sentence (5), the space above a mezzanine need not be considered as a storey in calculating the building height provided,
(a) the aggregate area of mezzanines that are not superimposed and do not meet the conditions of Sentence (3) does not exceed 10% of the floor area in which they are located, and
(b) the area of mezzanine in a suite does not exceed 10% of the area of that suite.
(5) Except as permitted by Sentences (6) and (7), each level of mezzanine that is partly or wholly superimposed above the first level of mezzanine shall be considered as a storey in calculating the building height.
(6) Platforms intended solely for periodic inspection and elevated catwalks need not be considered as floor assemblies or mezzanines for the purpose of determining building height provided,
(a) they are not used for storage,
(b) they are constructed with noncombustible materials unless the building is permitted to be of combustible construction, and
(c) where they are intended to be occupied, they have an occupant load of not more than four persons.
(7) Mezzanines, elevated walkways and platforms that are intended to be occupied in Group F, Division 2 or 3 major occupancies need not be considered as storeys in calculating building height provided,
(a) the building is of noncombustible construction, and
(b) the occupant load is not more than four persons.
(8) The space above a mezzanine conforming to Sentence (3) is permitted to include an enclosed space whose area does not exceed 10% of the open area of the room in which the mezzanine is located, provided the enclosed space does not obstruct visual communication between the open space above the mezzanine and the room in which it is located.
(9) A service space in which facilities are included to permit a person to enter and to undertake maintenance and other operations pertaining to building services from within the service space need not be considered a storey if it conforms to Articles 3.2.5.15. and 3.3.1.23. and Sentences 3.2.4.20.(12), 3.2.7.3.(2), 3.3.1.3.(7), 3.4.2.4.(3) and 3.4.4.4.(9).
3.2.1.2. Storage Garage Considered as a Separate Building
(1) A basement used primarily as a storage garage is permitted to be considered as a separate building for the purposes of Subsection 3.2.2. and Sentences 3.2.5.13.(2) and (3), provided the floor and roof assemblies above the basement and, except as permitted by Sentence (2), the exterior walls of the basement above the adjoining ground level are constructed as fire separations of,
(a) masonry or concrete having a fire-resistance rating not less than 2 h, or
(b) noncombustible construction having a fire-resistance rating of not less than 2 h, where the building conforms to Clauses 3.1.10.2.(4)(a) and (c) to (e).
(2) The exterior wall of a basement that is required to be a fire separation with a fire-resistance rating in accordance with Sentence (1) is permitted to be penetrated by openings that are not protected by closures provided,
(a) the storage garage is sprinklered,
(b) every opening in the exterior wall is separated from storeys above the opening by a projection of the floor or roof assembly above the basement, extending not less than,
(i) 1 m beyond the exterior face of the storage garage if the upper storeys are required to be of noncombustible construction, or
(ii) 2 m beyond the exterior face of the storage garage if the upper storeys are permitted to be of combustible construction or encapsulated mass timber construction, or
(c) the exterior walls of any storeys located above the floor or roof assembly referred to in Sentence (1) are recessed behind the outer edge of the assembly by not less than,
(i) 1 m if the upper storeys are required to be of noncombustible construction, or
(ii) 2 m if the upper storeys are permitted to be of combustible construction or encapsulated mass timber construction.
(3) The floor or roof assembly projection referred to in Clause (2)(b) shall have a fire-resistance rating not less than 2 h and shall have no openings within the projection.
3.2.1.3. Roof Considered as a Wall
(1) For the purposes of this Section any part of a roof that is pitched at an angle of 60° or more to the horizontal and is adjacent to a space intended for occupancy within a building shall be considered as part of an exterior wall of the building.
3.2.1.4. Floor Assembly over Basement
(1) Except as permitted by Sentence 3.2.2.42.(3), 3.2.2.43.(3), 3.2.2.44.(3), 3.2.2.45.(3), 3.2.2.46.(3), 3.2.2.47.(3) or 3.2.2.48.(3), a floor assembly immediately above a basement shall be constructed as a fire separation having a fire-resistance rating conforming to the requirements of Articles 3.2.2.20. to 3.2.2.83. for a floor assembly, but not less than 45 min.
(2) All loadbearing walls, columns and arches supporting a floor assembly immediately above a basement shall have a fire-resistance rating not less than that required by Sentence (1) for the floor assembly.
3.2.1.5. Fire Containment in Basements
(1) Except as permitted by Sentences (2) and 3.2.2.15.(3), in a building in which an automatic sprinkler system is not required to be installed by Articles 3.2.2.20. to 3.2.2.83., every basement shall,
(a) be sprinklered, or
(b) be subdivided into fire compartments not more than 600 m2 in area by a fire separation having a fire-resistance rating not less than that required for the floor assembly immediately above the basement.
(2) An open-air storey need not conform to Sentence (1).
3.2.1.6. Mezzanines
(1) The floor assembly of a mezzanine that is required to be considered as a storey in calculating building height shall be constructed in conformance with the fire separation requirements for floor assemblies in Articles 3.2.2.20. to 3.2.2.83.
3.2.2. Building Size and Construction Relative to Occupancy
3.2.2.1. Application
(1) Except as permitted by Article 3.2.2.3., a building shall be constructed in conformance with this Subsection to prevent fire spread and collapse caused by the effects of fire.
3.2.2.2. Special and Unusual Structures
(1) A structure that cannot be identified with the characteristics of a building in Articles 3.2.2.20. to 3.2.2.83. shall be protected against fire spread and collapse in conformance with good fire protection engineering practice.
3.2.2.3. Exceptions to Structural Fire Protection
(1) Fire protection is not required for,
(a) steel lintels above openings not more than 2 m wide in loadbearing walls and not more than 3 m wide in non-loadbearing walls,
(b) steel lintels above openings more than 2 m wide in loadbearing walls and more than 3 m wide in non-loadbearing walls, provided the lintels are supported at intervals of not more than 2 m by structural members with the required fire-resistance rating,
(c) the bottom flanges of shelf angles and plates that are not a part of the structural frame,
(d) steel members for framework around elevator hoistway doorways, steel for the support of elevator and dumbwaiter guides, counterweights and other similar equipment, that are entirely enclosed in a hoistway and are not a part of the structural frame of the building,
(e) steel members of stairways and escalators that are not a part of the structural frame of a building,
(f) steel members of porches, exterior balconies, exterior stairways, fire escapes, cornices, marquees and other similar appurtenances, provided they are outside an exterior wall of a building, and
(g) loadbearing steel or concrete members wholly or partly outside a building face in a building not more than 4 storeys in building height and classified as Group A, B, C, D or F, Division 3 major occupancy provided the members are,
(i) not less than 1 m away from any unprotected opening in an exterior wall, or
(ii) shielded from heat radiation in the event of a fire within the building by construction that will provide the same degree of protection that would be necessary if the member was located inside the building, with the protection extending on either side of the member a distance equal to the projection of the member from the face of the wall.
3.2.2.4. Buildings with Multiple Major Occupancies
(1) The requirements restricting fire spread and collapse for a building of a single major occupancy classification are provided in this Subsection according to its building height and building area.
(2) If a building contains more than one major occupancy, classified in more than one Group or Division, the requirements of this Subsection concerning building size and construction relative to major occupancy shall apply according to Articles 3.2.2.5. to 3.2.2.8.
(3) For the purposes of Sentences (1) and (2), a retirement home is deemed to be a separate major occupancy.
3.2.2.5. Applicable Building Height and Area
(1) In determining the fire safety requirements of a building in relation to each of the major occupancies contained in it, the building height and building area of the entire building shall be used.
(2) For the purposes of Sentence (1), a retirement home is deemed to be a separate major occupancy.
3.2.2.6. Multiple Major Occupancies
(1) Except as permitted by Articles 3.2.2.7. and 3.2.2.8. and Sentences 3.2.2.42A.(4), 3.2.2.43A.(5), 3.2.2.49A.(3) and 3.2.2.50A.(4), in a building containing more than one major occupancy, the requirements of this Subsection for the most restricted major occupancy contained shall apply to the whole building.
(2) For the purposes of Sentence (1), a retirement home is deemed to be a separate major occupancy.
3.2.2.7. Superimposed Major Occupancies
(1) Except as permitted by Article 3.2.2.8. and Sentences 3.2.2.42A.(4), 3.2.2.43A.(5), 3.2.2.49A.(3) and 3.2.2.50A.(4), in a building in which one major occupancy is located entirely above another major occupancy, the requirements in this Subsection for each portion of the building containing a major occupancy shall apply to that portion as if the entire building was of that major occupancy.
(2) If one major occupancy is located above another major occupancy, the fire-resistance rating of the floor assembly between the major occupancies shall be determined on the basis of the requirements of this Subsection for the lower major occupancy.
(3) For the purposes of Sentences (1) and (2), a retirement home is deemed to be a separate major occupancy.
3.2.2.8. Exceptions for Major Occupancies
(1) In a building in which the aggregate area of all major occupancies in a particular Group or Division is not more than 10% of the floor area of the storey in which they are located, these major occupancies need not be considered as major occupancies for the purposes of this Subsection, provided they are not classified as Group F, Division 1 or 2 occupancies.
(1.1) For the purposes of Sentence (1), a retirement home is deemed to be a separate major occupancy.
(2) A helicopter landing area on the roof of a building need not be considered a major occupancy for purposes of Subsection 3.2.2. where such landing area is not more than 10% of the area of the roof.
3.2.2.9. Crawl Spaces
(1) For the purposes of Articles 3.2.1.4. and 3.2.1.5., a crawl space shall be considered as a basement if it is,
(a) more than 1 800 mm high between the lowest part of the floor assembly and the ground or other surface below,
(b) used for any occupancy,
(c) used for the passage of flue pipes, or
(d) used as a plenum in combustible construction.
(2) A floor assembly immediately above a crawl space is not required to be constructed as a fire separation and is not required to have a fire-resistance rating provided the crawl space is not required to be considered as a basement by Sentence (1).
3.2.2.10. Streets
(1) Every building shall face a street located in conformance with the requirements of Articles 3.2.5.4 and 3.2.5.5 for access routes.
(2) For the purposes of Subsections 3.2.2. and 3.2.5. an access route conforming to Subsection 3.2.5. is permitted to be considered as a street.
(3) A building within the scope of Article 3.2.2.43A. or 3.2.2.50A. is considered to face one street, where,
(a) not less than 25% of the building perimeter is located within 15 m of a street or streets, or
(b) not less than 10% of the building perimeter is located within 15 m of a street or streets, provided the exterior cladding conforms to Sentence 3.1.4.8.(2).
(4) A building is considered to face two streets provided not less than 50% of the building perimeter is located within 15 m of a street or streets.
(5) A building is considered to face three streets provided not less than 75% of the building perimeter is located within 15 m of a street or streets.
(6) Enclosed spaces, tunnels, bridges and similar structures, even though used for vehicular or pedestrian traffic, are not considered as streets for the purpose of this Part.
3.2.2.11. Exterior Balconies
(1) Except as provided in Sentence (2), an exterior balcony shall be constructed in accordance with the type of construction required by Articles 3.2.2.20. to 3.2.2.83., as applicable to the occupancy classification of the building.
(2) The floor assembly of an exterior balcony in a building or part of a building conforming to Article 3.2.2.42A. or 3.2.2.49A. shall,
(a) be of noncombustible construction, or
(b) be constructed in accordance with Article 3.1.6.3., but need not comply with Sentence 3.1.6.4.(1).
3.2.2.12. Exterior Passageways
(1) An elevated exterior passageway used as part of a means of egress shall conform to the requirements of Articles 3.2.2.20. to 3.2.2.83. for mezzanines.
3.2.2.13. Occupancy on Roof
(1) A portion of a roof that supports an occupancy shall be constructed in conformance with the fire separation requirements of Articles 3.2.2.20. to 3.2.2.83. for floor assemblies.
3.2.2.14. Rooftop Enclosures
(1) A rooftop enclosure for elevator machinery or for a service room shall be constructed in accordance with the type of construction required by Articles 3.2.2.20. to 3.2.2.83.
(2) A rooftop enclosure for elevator machinery or for a service room, not more than 1 storey high, is not required to have a fire-resistance rating.
(3) A rooftop enclosure for a stairway shall be constructed in accordance with the type of construction required by Articles 3.2.2.20. to 3.2.2.83.
(4) A rooftop enclosure for a stairway need not have a fire-resistance rating nor be constructed as a fire separation.
3.2.2.15. Storeys below Ground
(1) If a building is erected entirely below the adjoining finished ground level and does not extend more than 1 storey below that ground level, the minimum precautions against fire spread and collapse shall be the same as are required for basements under a building of 1 storey in building height having the same occupancy and building area.
(2) If any portion of a building is erected entirely below the adjoining finished ground level and extends more than 1 storey below that ground level, the following minimum precautions against fire spread and collapse shall be taken:
(a) except as permitted by Sentence (3), the basements shall be sprinklered,
(b) a floor assembly below the ground level shall be constructed as a fire separation with a fire-resistance rating not less than,
(i) 3 h if the basements are intended for use as Group E or Group F, Division 1 or 2 occupancies, or
(ii) 2 h if the basements are not intended for use as Group E or Group F, Division 1 or 2 occupancies, and
(c) all loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the construction that they support.
(3) If the first storey of a building is not required to be sprinklered, sprinklers are not required in the storey immediately below the first storey, provided the storey below,
(a) contains only residential occupancies, and
(b) has at least one unobstructed access opening conforming to Sentence 3.2.5.1.(2) installed on that storey for each 15 m of wall length in at least one wall required by this Subsection to face a street.
3.2.2.16. Heavy Timber Roof Permitted
(1) Unless otherwise permitted by Articles 3.2.2.20. to 3.2.2.83., a roof assembly in a building up to 2 storeys in building height is permitted to be of heavy timber construction regardless of building area or type of construction required, provided the building is sprinklered.
(2) If Sentence (1) permits a roof assembly to be of heavy timber construction, structural members in the storey immediately below the roof assembly are permitted to be of heavy timber construction.
3.2.2.17. Sprinklers in Lieu of Roof Rating
(1) The requirements in Articles 3.2.2.20. to 3.2.2.83. for roof assemblies to have a fire-resistance rating are permitted to be waived provided,
(a) except as provided by Sentence (2), the building is sprinklered,
(b) the sprinkler system in Clause (a) is electrically supervised in conformance with Sentence 3.2.4.10.(3), and
(c) the operation of the sprinkler system in Clause (a) will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.8.(4).
(2) The fire-resistance rating of roof assemblies required by Clause 3.2.2.43A.(2)(b) or 3.2.2.50A.(2)(b) is not permitted to be waived.
3.2.2.18. Automatic Sprinkler System Required
(1) If an automatic sprinkler system is required by Articles 3.2.2.20. to 3.2.2.83., the system shall conform to the requirements of Articles 3.2.4.8. to 3.2.4.10. and 3.2.5.13.
3.2.2.19. Buildings Containing Impeded Egress Zones
(1) A building containing an impeded egress zone and conforming to the appropriate requirements of Articles 3.2.2.20. to 3.2.2.83. is not required to conform to the requirements of Articles 3.2.2.36. and 3.2.2.37. for a Group B, Division 1 major occupancy provided,
(a) the building is sprinklered,
(b) it is not more than 1 storey in building height,
(c) it does not include,
(i) a contained use area,
(ii) sleeping accommodation,
(iii) a high hazard industrial occupancy, or
(iv) a mercantile occupancy,
(d) the building area is not more than 6 400 m2 if the building includes a medium hazard industrial occupancy,
(e) the impeded egress zone does not extend beyond the boundaries of the fire compartment in which it is located, and
(f) the occupant load of the impeded egress zone is not more than 100.
3.2.2.20. Group A, Division 1, Any Height, Any Area, Sprinklered
(1) Except as permitted by Articles 3.2.2.21. and 3.2.2.22., a building classified as Group A, Division 1 shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.21. Group A, Division 1, 1 Storey, Limited Area
(1) A building classified as Group A, Division 1 is permitted to conform to Sentence (2) provided,
(a) it is not more than 1 storey in building height,
(b) it has less than 40% of the area of the building as 2 storeys for the purpose of,
(i) development of productions including preparation of scenery and costumes and rehearsal of performers,
(ii) organization of performers, scenery and sound equipment,
(iii) preparation by performers for a performance,
(iv) managerial functions, or
(v) toilets, rest rooms and similar public facilities,
(c) it has no occupancy above or below the auditorium other than one that serves it or is dependent on it,
(d) it is not more than 600 m2 in building area, and
(e) the occupant load is not more than 600.
(2) The building referred to in Sentence (1) is permitted to be of heavy timber construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations,
(i) with a fire-resistance rating not less than 45 min, or
(ii) of heavy timber construction, and
(b) loadbearing walls, columns and arches shall,
(i) have a fire-resistance rating not less than that required for the supported assembly, or
(ii) be of heavy timber construction.
3.2.2.22. Group A, Division 1, 1 Storey
(1) A building classified as Group A, Division 1 is permitted to conform to Sentence (2) provided,
(a) it is not more than 1 storey in building height,
(b) no part of an auditorium floor is more than 5 m above or below grade,
(c) no occupancy is above or below the auditorium other than one that serves it or is dependent on it, and
(d) the occupant load of the auditorium floor is not more than 300.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min,
(c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min, and
(d) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction, and
(e) loadbearing walls, columns and arches supporting a fire separation shall have a fire-resistance rating not less than that required for the fire separation.
3.2.2.23. Group A, Division 2, Any Height, Any Area, Sprinklered
(1) Except as permitted by Articles 3.2.2.24. to 3.2.2.28., a building classified as Group A, Division 2 shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.24. Group A, Division 2, up to 6 Storeys, Any Area, Sprinklered
(1) A building classified as Group A, Division 2, that is not limited by building area, is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered, and
(b) it is not more than 6 storeys in building height.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) all loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.25. Group A, Division 2, up to 2 Storeys
(1) A building classified as Group A, Division 2 is permitted to conform to Sentence (2) provided,
(a) it is not more than 2 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.25.
Table 3.2.2.25.
Maximum Building Area, Group A, Division 2, up to 2 Storeys
Forming Part of Sentence 3.2.2.25.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
1 600 |
2 000 |
2 400 |
2. |
2 |
800 |
1 000 |
1 200 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less 45 min,
(c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min, except that in a building not more than 1 storey in building height, the fire-resistance rating is permitted to be waived provided the roof assembly is constructed as a fire-retardant treated wood roof system conforming to Article 3.1.14.1., and the building area is not more than,
(i) 800 m2 if facing one street,
(ii) 1 000 m2 if facing two streets, or
(iii) 1 200 m2 if facing three streets, and
(d) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.26. Group A, Division 2, up to 2 Storeys, Increased Area, Sprinklered
(1) A building classified as Group A, Division 2 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 4 800 m2 if 1 storey in building height, or
(ii) 2 400 m2 if 2 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less 45 min, and
(c) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.27. Group A, Division 2, up to 2 Storeys, Sprinklered
(1) A building classified as Group A, Division 2 is permitted to be of combustible construction or noncombustible construction used singly or in combination, provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 2 400 m2 if 1 storey in building height with no basement,
(ii) 1 200 m2 if 1 storey in building height, or
(iii) 600 m2 if 2 storeys in building height.
3.2.2.28. Group A, Division 2, 1 Storey
(1) A building classified as Group A, Division 2 is permitted to be of combustible construction or noncombustible construction used singly or in combination, provided,
(a) it is not more than 1 storey in building height, and
(b) except as permitted by Sentence (2), it has a building area not more than,
(i) 400 m2 if facing one street,
(ii) 500 m2 if facing two streets, or
(iii) 600 m2 if facing three streets.
(2) In a building referred to in Sentence (1) without a basement, the building area limits of Sentence (1) are permitted to be doubled provided a fire separation with a fire-resistance rating not less than 1 h is used to separate the building into fire compartments, each one of which does not exceed the area limits of Clause (1)(b).
3.2.2.29. Group A, Division 3, Any Height, Any Area
(1) Except as permitted by Articles 3.2.2.30. to 3.2.2.34., a building classified as Group A, Division 3 shall conform to Sentences (2) and (3).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered if it is regulated by Subsection 3.2.6.,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less than 1 h,
(d) if the building is not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, and
(e) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) If intended for occasional use for trade shows and similar exhibition purposes, the building referred to in Sentence (1) that is more than 1 500 m2 in building area shall be sprinklered.
3.2.2.30. Group A, Division 3, up to 2 Storeys
(1) A building classified as Group A, Division 3 is permitted to conform to Sentence (2) provided,
(a) it is not more than 2 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.30.
Table 3.2.2.30.
Maximum Building Area, Group A, Division 3, up to 2 Storeys
Forming Part of Sentence 3.2.2.30.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
4 000 |
5 000 |
6 000 |
2. |
2 |
2 000 |
2 500 |
3 000 |
(2) Except as permitted by Clauses (c) and (d), the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h,
(c) roof assemblies shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of heavy timber construction, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly, except that arches and structural members within the storey immediately below a roof assembly are permitted to be of heavy timber construction.
(3) If intended for occasional use for trade shows and similar exhibition purposes, the building referred to in Sentence (1) that is more than 1 500 m2 in building area shall be sprinklered.
3.2.2.31. Group A, Division 3, up to 2 Storeys, Sprinklered
(1) A building classified as Group A, Division 3 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 12 000 m2 if 1 storey in building height, or
(ii) 6 000 m2 if 2 storeys in building height.
(2) Except as permitted by Clause (c) and Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly, except that arches are permitted to be of heavy timber construction.
3.2.2.32. Group A, Division 3, 1 Storey, Increased Area
(1) A building classified as Group A, Division 3 is permitted to conform to Sentences (2)
and (3) provided,
(a) it is not more than 1 storey in building height, and
(b) it has a building area not more than,
(i) 2 400 m2 if facing one street,
(ii) 3 000 m2 if facing two streets, or
(iii) 3 600 m2 if facing three streets.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min,
(b) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min, except that the fire-resistance rating is permitted to be waived provided the roof assembly is constructed as a fire-retardant treated wood roof system conforming to Article 3.1.14.1., and the building area is not more than,
(i) 1 200 m2 if facing one street,
(ii) 1 500 m2 if facing two streets, or
(iii) 1 800 m2 if facing three streets, and
(c) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
(3) If intended for occasional use for trade shows and similar exhibition purposes, the building referred to in Sentence (1) that is more than 1 500 m2 in building area shall be sprinklered.
3.2.2.33. Group A, Division 3, 1 Storey, Sprinklered
(1) A building classified as Group A, Division 3 is permitted to be of combustible construction or noncombustible construction used singly or in combination, provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 1 storey in building height, and
(c) it has a building area not more than 7 200 m2.
3.2.2.34. Group A, Division 3, 1 Storey
(1) A building classified as Group A, Division 3 is permitted to be of combustible construction or noncombustible construction used singly or in combination, provided,
(a) it is not more than 1 storey in building height, and
(b) it has a building area not more than,
(i) 1 000 m2 if facing one street,
(ii) 1 250 m2 if facing two streets, or
(iii) 1 500 m2 if facing three streets.
3.2.2.35. Group A, Division 4
(1) Except as permitted by Sentences (2) and (3), a building classified as Group A, Division 4 shall be of noncombustible construction.
(2) Roof assemblies and supporting arches and columns are permitted to be of heavy timber construction.
(3) A building classified as Group A, Division 4 is permitted to be of combustible construction provided,
(a) the occupant load is less than 1 500, and
(b) the building has a limiting distance not less than 6 m.
(4) Sprinklers shall be installed in all spaces below tiers of seats in a building classified as Group A, Division 4 if those spaces are used for occupancy.
3.2.2.36. Group B, Division 1, Any Height, Any Area, Sprinklered
(1) Except as permitted by Article 3.2.2.37., a building classified as Group B, Division 1 shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.37. Group B, Division 1, up to 3 Storeys, Sprinklered
(1) A building classified as Group B, Division 1 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1) the building is sprinklered,
(b) it is not more than 3 storeys in building height, and
(c) it has a building area,
(i) that is not limited if the building is not more than 1 storey in building height,
(ii) not more than 12 000 m2 if 2 storeys in building height, or
(iii) not more than 8 000 m2 if 3 storeys in building height.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.38. Group B, Division 2 or Division 3, Any Height, Any Area, Sprinklered
(1) Except as permitted by Articles 3.2.2.39. to 3.2.2.41., a building classified as Group B, Division 2 or Division 3 shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.39. Group B, Division 2 or Division 3, up to 3 Storeys, Sprinklered
(1) A building classified as Group B, Division 2 or Division 3 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 3 storeys in building height, and
(c) it has a building area,
(i) that is not limited if the building is not more than 1 storey in building height,
(ii) not more than 12 000 m2 if 2 storeys in building height, or
(iii) not more than 8 000 m2 if 3 storeys in building height.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.40. Group B, Division 2 or Division 3, up to 2 Storeys, Sprinklered
(1) A building classified as Group B, Division 2 or Division 3 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 2 400 m2 if 1 storey in building height, or
(ii) 1 600 m2 if 2 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.41. Group B, Division 2 or Division 3, 1 Storey, Sprinklered
(1) A building classified as Group B, Division 2 or Division 3 is permitted to be of combustible construction or noncombustible construction used singly or in combination, provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 1 storey in building height, and
(c) it has a building area not more than 500 m2.
3.2.2.42. Group C, Any Height, Any Area, Sprinklered
(1) Except as permitted by Articles 3.2.2.43. to 3.2.2.48., a building classified as Group C, other than a retirement home, shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) except as permitted by Sentence (3), floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
3.2.2.42A. Group C, up to 12 Storeys, Sprinklered, Encapsulated Mass Timber Construction
(1) A building classified as Group C is permitted to conform to Sentence (2), provided,
(a) it is sprinklered,
(b) it is not more than 12 storeys in building height,
(c) it has a height of not more than 42 m measured between the floor of the first storey and the uppermost floor level that does not serve as a rooftop enclosure for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, and
(d) it has a building area not more than 6 000 m2.
(2) Except as provided in Article 3.2.2.16., the building referred to in Sentence (1) is permitted to be of encapsulated mass timber construction or noncombustible construction, used singly or in combination, and,
(a) except as provided in Sentence (3), floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, that are entirely contained within these dwelling units shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
(4) Group A, Division 2 major occupancies, Group E major occupancies and storage garages located in a building or part of a building within the scope of this Article are permitted to be constructed in accordance with this Article, provided,
(a) the Group A, Division 2 major occupancy is located below the fourth storey,
(b) the Group E major occupancy is located below the third storey, and
(c) the storage garage is located below the fifth storey.
3.2.2.43. Group C, up to 6 Storeys, Sprinklered, Noncombustible Construction
(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 6 storeys in building height, and
(c) it has a building area,
(i) that is not limited if the building is not more than 2 storeys in building height,
(ii) not more than 12 000 m2 if 3 storeys in building height,
(iii) not more than 9 000 m2 if 4 storeys in building height,
(iv) not more than 7 200 m2 if 5 storeys in building height, or
(v) not more than 6 000 m2 if 6 storeys in building height.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence (3), floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
3.2.2.43A. Group C, up to 6 Storeys, Sprinklered, Combustible Construction
(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided,
(a) it is sprinklered,
(b) it is not more than 6 storeys in building height,
(c) it has a height of not more than 18 m, measured between the floor level of the first storey and the floor level of the uppermost storey or mezzanine that is not a rooftop enclosure provided for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, and
(d) it has a building area of not more than,
(i) 9 000 m2 if 1 storey in building height,
(ii) 4 500 m2 if 2 storeys in building height,
(iii) 3 000 m2 if 3 storeys in building height,
(iv) 2 250 m2 if 4 storeys in building height,
(v) 1 800 m2 if 5 storeys in building height, or
(vi) 1 500 m2 if 6 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction, used singly or in combination, and,
(a) except as permitted by Sentence (3), floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) roof assemblies shall have a fire-resistance rating not less than 1 h,
(c) except as provided by Sentence (4), where the roof assembly has a height greater than 25 m measured from the floor level of the first storey to the highest point of the roof assembly, the roof assembly shall,
(i) be of noncombustible construction, or
(ii) be constructed of fire-retardant treated wood conforming to Article 3.1.4.5.,
(d) mezzanines shall have a fire-resistance rating not less than 1 h,
(e) Revoked: O. Reg. 89/23, s. 7 (1).
(f) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
(4) The construction of non-contiguous roof assemblies at different elevations is permitted to be evaluated separately to determine which roof assemblies are required to be constructed in accordance with Clause (2)(c).
(5) Group A, Division 2 major occupancies, Group E major occupancies and storage garages located in a building or part of a building within the scope of this Article are permitted to be constructed in accordance with this Article, provided,
(a) Group A, Division 2 major occupancies and Group E major occupancies are located below the third storey, and
(b) storage garages are located below the fourth storey.
3.2.2.44. Group C, up to 4 Storeys, Noncombustible Construction
(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided,
(a) it is not more than,
(i) 3 storeys in building height, or
(ii) 4 storeys in building height provided there is not more than one dwelling unit above another dwelling unit, and vertical fire separations of adjacent dwelling units conform to Sentence (4), and
(b) it has a building area not more than the value in Table 3.2.2.44.
Table 3.2.2.44.
Maximum Building Area, Group C, up to 4 Storeys
Forming Part of Sentence 3.2.2.44.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
not limited |
not limited |
not limited |
2. |
2 |
6 000 |
not limited |
not limited |
3. |
3 |
4 000 |
5 000 |
6 000 |
4. |
4 |
3 000 |
3 750 |
4 500 |
(2) The building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence (3), floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h,
(c) roof assemblies shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
(4) The dwelling units described in Subclause (1)(a)(ii) shall be separated by continuous vertical fire separations that extend through all storeys and service spaces of the separated portions.
(5) Revoked: O. Reg. 139/17, s. 19.
3.2.2.45. Group C, up to 4 Storeys, Sprinklered
(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 4 storeys in building height, and
(c) it has a building area not more than,
(i) 7 200 m2 if 1 storey in building height,
(ii) 3 600 m2 if 2 storeys in building height,
(iii) 2 400 m2 if 3 storeys in building height, or
(iv) 1 800 m2 if 4 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) except as permitted by Sentences (3) and (4), floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, that are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
(4) In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived.
3.2.2.46. Group C, up to 3 Storeys, Increased Area
(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided,
(a) it is not more than 3 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.46.
Table 3.2.2.46.
Maximum Building Area, Group C up to 3 Storeys, Increased Area
Forming Part of Sentence 3.2.2.46.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
2 400 |
3 000 |
3 600 |
2. |
2 |
1 200 |
1 500 |
1 800 |
3. |
3 |
800 |
1 000 |
1 200 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) except as permitted by Sentences (3) and (4), floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h,
(c) roof assemblies shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, that are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
(4) In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived.
(5) Revoked: O. Reg. 139/17, s. 21.
3.2.2.47. Group C, up to 3 Storeys
(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided,
(a) it is not more than 3 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.47.
Table 3.2.2.47.
Maximum Building Area, Group C, up to 3 Storeys
Forming Part of Sentence 3.2.2.47.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
1 800 |
2 250 |
2 700 |
2. |
2 |
900 |
1 125 |
1 350 |
3. |
3 |
600 |
750 |
900 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) except as permitted by Sentences (3) and (4), floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, that are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 45 min but need not be constructed as fire separations.
(4) In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived.
(5) Revoked: O. Reg. 139/17, s. 22 (2).
3.2.2.48. Group C, up to 3 Storeys, Sprinklered
(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 3 storeys in building height, and
(c) it has a building area not more than,
(i) 5 400 m2 if 1 storey in building height,
(ii) 2 700 m2 if 2 storeys in building height, or
(iii) 1 800 m2 if 3 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) except as permitted by Sentences (3) and (4), floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction a fire-resistance rating not less than 45 min, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, that are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 45 min but need not be constructed as fire separations.
(4) In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived.
3.2.2.48A. Group C, Retirement Home, Any Height, Any Area, Sprinklered
(1) Except as permitted by Articles 3.2.2.48B. to 3.2.2.48E., a retirement home shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.48B. Group C, Retirement Home, up to 4 Storeys, Sprinklered, Increased Area
(1) A retirement home is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 4 storeys in building height, and
(c) it has a building area not more than,
(i) 12 000 m2 if 1 storey in building height,
(ii) 6 000 m2 if 2 storeys in building height,
(iii) 4 000 m2 if 3 storeys in building height, or
(iv) 3 000 m2 if 4 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.48C. Group C, Retirement Home, up to 4 Storeys, Sprinklered
(1) A retirement home is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 4 storeys in building height, and
(c) it has a building area not more than,
(i) 6 600 m2 if 1 storey in building height,
(ii) 3 300 m2 if 2 storeys in building height,
(iii) 2 200 m2 if 3 storeys in building height, or
(iv) 1 650 m2 if 4 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.48D. Group C, Retirement Home, up to 3 Storeys, Sprinklered, Noncombustible Construction
(1) A retirement home is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 3 storeys in building height, and
(c) it has a building area that is,
(i) not limited if the building is not more than 1 storey in building height,
(ii) not more than 12 000 m2 if 2 storeys in building height, or
(iii) not more than 8 000 m2 if 3 storeys in building height.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) is permitted to be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.48E. Group C, Retirement Home, up to 3 Storeys, Sprinklered, Combustible Construction
(1) A retirement home is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 3 storeys in building height, and
(c) it has a building area not more than,
(i) 4 800 m2 if 1 storey in building height,
(ii) 2 400 m2 if 2 storeys in building height, or
(iii) 1 600 m2 if 3 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.49. Group D, Any Height, Any Area
(1) Except as permitted by Articles 3.2.2.50. to 3.2.2.56., a building classified as Group D shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered if it is regulated by Subsection 3.2.6.,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less 1 h,
(d) if the building is not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, except that in a building not more than 1 storey in building height this requirement is waived, and
(e) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.49A. Group D, up to 12 Storeys, Sprinklered, Encapsulated Mass Timber Construction
(1) A building classified as Group D is permitted to conform to Sentence (2), provided,
(a) it is sprinklered,
(b) it is not more than 12 storeys in building height,
(c) it has a height of not more than 42 m measured between the floor of the first storey and the uppermost floor level that does not serve as a rooftop enclosure for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, and
(d) it has a building area not more than 7 200 m2.
(2) Except as provided in Article 3.2.2.16., the building referred to in Sentence (1) is permitted to be of encapsulated mass timber construction or nonconbustible construction, used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) Group A, Division 2 major occupancies, Group E major occupancies, Group F, Division 2 and 3 major occupancies and storage garages located in a building or part of a building within the scope of this Article are permitted to be constructed in accordance with this Article, provided,
(a) the Group A, Division 2 major occupancy is located below the fourth storey,
(b) the Group E major occupancy and Group F, Division 2 or 3 major occupancy are located below the third storey, and
(c) the storage garage is located below the fifth storey.
3.2.2.50. Group D, up to 6 Storeys
(1) A building classified as Group D is permitted to conform to Sentence (2) provided,
(a) it is not more than 6 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.50.
Table 3.2.2.50.
Maximum Building Area, Group D, up to 6 Storeys
Forming Part of Sentence 3.2.2.50.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
not limited |
not limited |
not limited |
2. |
2 |
7 200 |
not limited |
not limited |
3. |
3 |
4 800 |
6 000 |
7 200 |
4. |
4 |
3 600 |
4 500 |
5 400 |
5. |
5 |
2 800 |
3 600 |
4 320 |
6. |
6 |
2 400 |
3 000 |
3 600 |
(2) The building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h,
(c) roof assemblies shall have a fire-resistance rating not less than 1 h, except that in a building not more than 1 storey in building height this requirement is waived, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.50A. Group D, up to 6 Storeys, Sprinklered, Combustible Construction
(1) A building classified as Group D is permitted to conform to Sentence (2) provided,
(a) it is sprinklered,
(b) it is not more than 6 storeys in building height,
(c) it has a height of not more than 18 m, measured between the floor level of the first storey and the floor level of the uppermost storey or mezzanine that is not a rooftop enclosure provided for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, and
(d) it has a building area of not more than,
(i) 18 000 m2 if 1 storey in building height,
(ii) 9 000 m2 if 2 storeys in building height,
(iii) 6 000 m2 if 3 storeys in building height,
(iv) 4 500 m2 if 4 storeys in building height,
(v) 3 600 m2 if 5 storeys in building height, or
(vi) 3 000 m2 if 6 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) roof assemblies shall have a fire-resistance rating not less than 1 h,
(c) except as provided by Sentence (3), where the roof assembly has a height greater than 25 m measured from the floor level of the first storey to the highest point of the roof assembly, the roof assembly shall,
(i) be of noncombustible construction, or
(ii) be constructed of fire-retardant treated wood conforming to Article 3.1.4.5.,
(d) mezzanines shall have a fire-resistance rating not less than 1 h,
(e) Revoked: O. Reg. 89/23, s. 8 (1).
(f) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) The construction of non-contiguous roof assemblies at different elevations is permitted to be evaluated separately to determine which roof assemblies are required to be constructed in accordance with Clause (2)(c).
(4) Group A, Division 2 major occupancies, Group E major occupancies, Group F, Division 2 and 3 major occupancies and storage garages located in a building or part of a building within the scope of this Article are permitted to be constructed in accordance with this Article, provided,
(a) Group A, Division 2 major occupancies, Group E major occupancies and Group F, Division 2 or 3 major occupancies are located below the third storey, and
(b) storage garages are located below the fourth storey.
3.2.2.51. Group D, up to 6 Storeys, Sprinklered, Noncombustible Construction
(1) A building classified as Group D is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 6 storeys in building height, and
(c) it has a building area,
(i) that is not limited if the building is not more than 2 storeys in building height,
(ii) not more than 14 400 m2 if 3 storeys in building height,
(iii) not more than 10 800 m2 if 4 storeys in building height,
(iv) not more than 8 640 m2 if 5 storeys in building height, or
(v) not more than 7 200 m2 if 6 storeys in building height.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.52. Group D, up to 4 Storeys, Sprinklered
(1) A building classified as Group D is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 4 storeys in building height, and
(c) it has a building area not more than 3 600 m2.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.53. Group D, up to 3 Storeys
(1) A building classified as Group D is permitted to conform to Sentence (2) provided,
(a) it is not more than 3 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.53.
Table 3.2.2.53.
Maximum Building Area, Group D, up to 3 Storeys
Forming Part of Sentence 3.2.2.53.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
4 800 |
6 000 |
7 200 |
2. |
2 |
2 400 |
3 000 |
3 600 |
3. |
3 |
1 600 |
2 000 |
2 400 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min,
(c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min, except that in a building not more than 1 storey in building height, the fire-resistance rating is permitted to be waived provided the roof assembly is constructed as a fire-retardant treated wood roof system conforming to Article 3.1.14.1., and the building area is not more than,
(i) 2 400 m2 if facing one street,
(ii) 3 000 m2 if facing two streets, or
(iii) 3 600 m2 if facing three streets, and
(d) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.54. Group D, up to 3 Storeys, Sprinklered
(1) A building classified as Group D is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 3 storeys in building height, and
(c) it has a building area not more than,
(i) 14 400 m2 if 1 storey in building height,
(ii) 7 200 m2 if 2 storeys in building height, or
(iii) 4 800 m2 if 3 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min, and
(c) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.55. Group D, up to 2 Storeys
(1) A building classified as Group D is permitted to conform to Sentence (2) provided,
(a) it is not more than 2 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.55.
Table 3.2.2.55.
Maximum Building Area, Group D, up to 2 Storeys
Forming Part of Sentence 3.2.2.55.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
1 000 |
1 250 |
1 500 |
2. |
2 |
800 |
1 000 |
1 200 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min, and
(b) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.56. Group D, up to 2 Storeys, Sprinklered
(1) A building classified as Group D is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 3 000 m2 if 1 storey in building height, or
(ii) 2 400 m2 if 2 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min, and
(b) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.57. Group E, Any Height, Any Area, Sprinklered
(1) Except as permitted by Articles 3.2.2.58. to 3.2.2.62., a building classified as Group E
shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.58. Group E, up to 4 Storeys, Sprinklered
(1) A building classified as Group E is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 4 storeys in building height, and
(c) it has a building area not more than 1 800 m2.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.59. Group E, up to 3 Storeys
(1) A building classified as Group E is permitted to conform to Sentence (2) provided,
(a) it is not more than 3 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.59.
Table 3.2.2.59.
Maximum Building Area, Group E, up to 3 Storeys
Forming Part of Sentence 3.2.2.59.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
1 500 |
1 500 |
1 500 |
2. |
2 |
1 200 |
1 500 |
1 500 |
3. |
3 |
800 |
1 000 |
1 500 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min,
(c) roof assemblies shall have a fire-resistance rating not less than 45 min, except that in a building not more than 1 storey in building height, the fire-resistance rating is permitted to be waived provided the roof assembly is of noncombustible construction or is constructed as a fire-retardant treated wood roof system conforming to Article 3.1.14.1.,
(d) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction, and
(e) loadbearing walls, columns and arches supporting a fire separation shall have a fire-resistance rating not less than that required for the fire separation.
3.2.2.60. Group E, up to 3 Storeys, Sprinklered
(1) A building classified as Group E is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 3 storeys in building height, and
(c) it has a building area not more than,
(i) 7 200 m2 if 1 storey in building height,
(ii) 3 600 m2 if 2 storeys in building height, or
(iii) 2 400 m2 if 3 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min,
(c) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction, and
(d) loadbearing walls, columns and arches supporting a fire separation shall have a fire-resistance rating not less than that required for the fire separation.
3.2.2.61. Group E, up to 2 Storeys
(1) A building classified as Group E is permitted to conform to Sentence (2) provided,
(a) it is not more than 2 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.61.
Table 3.2.2.61.
Maximum Building Area, Group E, up to 2 Storeys
Forming Part of Sentence 3.2.2.61.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
1 000 |
1 250 |
1 500 |
2. |
2 |
600 |
750 |
900 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min, and
(b) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.62. Group E, up to 2 Storeys, Sprinklered
(1) A building classified as Group E is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 3 000 m2 if 1 storey in building height, or
(ii) 1 800 m2 if 2 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min, and
(b) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.63. Group F, Division 1, up to 4 Storeys, Sprinklered
(1) Except as permitted by Articles 3.2.2.64. to 3.2.2.66., a building classified as Group F, Division 1 shall conform to Sentence (2) provided,
(a) it is not more than 4 storeys in building height, and
(b) it has a building area not more than,
(i) 9 000 m2 if 1 storey in building height,
(ii) 4 500 m2 if 2 storeys in building height,
(iii) 3 000 m2 if 3 storeys in building height, or
(iv) 2 250 m2 if 4 storeys in building height.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.64. Group F, Division 1, up to 3 Storeys, Sprinklered
(1) A building classified as Group F, Division 1 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 3 storeys in building height, and
(c) it has a building area not more than,
(i) 3 600 m2 if 1 storey in building height,
(ii) 1 800 m2 if 2 storeys in building height, or
(iii) 1 200 m2 if 3 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of heavy timber construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.65. Group F, Division 1, up to 2 Storeys, Sprinklered
(1) A building classified as Group F, Division 1 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 2 400 m2 if 1 storey in building height, or
(ii) 1 200 m2 if 2 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,
(b) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.66. Group F, Division 1, 1 Storey
(1) A building classified as Group F, Division 1 is permitted to be of combustible construction or noncombustible construction used singly or in combination provided,
(a) it is not more than 1 storey in building height, and
(b) it has a building area not more than 800 m2.
3.2.2.67. Group F, Division 2, Any Height, Any Area, Sprinklered
(1) Except as permitted by Articles 3.2.2.68. to 3.2.2.72., a building classified as Group F, Division 2 shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.68. Group F, Division 2, up to 6 Storeys
(1) A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided,
(a) it is not more than 6 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.68.A. or Table 3.2.2.68.B.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h,
(c) if the building is not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
Table 3.2.2.68.A.
Maximum Building Area, Group F, Division 2, up to 6 Storeys
Forming Part of Sentence 3.2.2.68.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
9 000 |
11 250 |
13 500 |
2. |
2 |
4 500 |
5 625 |
6 750 |
3. |
3 |
3 000 |
3 750 |
4 500 |
4. |
4 |
2 250 |
2 810 |
3 375 |
5. |
5 |
1 800 |
2 250 |
2 700 |
6. |
6 |
1 500 |
1 875 |
2 250 |
Table 3.2.2.68.B.
Maximum Building Area, Group F, Division 2, up to 6 Storeys, Sprinklered
Forming Part of Sentence 3.2.2.68.(1)
Item |
Column 1 |
Column 2 |
|
No. of Storeys |
Maximum Area, m2 |
1. |
1 |
27 000 |
2. |
2 |
13 500 |
3. |
3 |
9 000 |
4. |
4 |
6 750 |
5. |
5 |
5 400 |
6. |
6 |
4 500 |
3.2.2.69. Group F, Division 2, up to 4 Storeys, Increased Area
(1) A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided,
(a) it is not more than 4 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.69.A. or Table 3.2.2.69.B.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h,
(c) if the building is not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
Table 3.2.2.69.A.
Maximum Building Area, Group F, Division 2, up to 4 Storeys, Increased Area
Forming Part of Sentence 3.2.2.69.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
6 000 |
7 500 |
9 000 |
2. |
2 |
3 000 |
3 750 |
4 500 |
3. |
3 |
2 000 |
2 500 |
3 000 |
4. |
4 |
1 500 |
1 875 |
2 250 |
Table 3.2.2.69.B.
Maximum Building Area, Group F, Division 2, up to 4 Storeys, Increased Area, Sprinklered
Forming Part of Sentence 3.2.2.69.(1)
Item |
Column 1 No. of Storeys |
Column 2 Maximum Area, m2 |
1. |
1 |
18 000 |
2. |
2 |
9 000 |
3. |
3 |
6 000 |
4. |
4 |
4 500 |
3.2.2.70. Group F, Division 2, up to 4 Storeys
(1) A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided,
(a) it is not more than 4 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.70.A. or Table 3.2.2.70.B.
(2) The building referred to in Sentence (1) shall be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min,
(c) if the building is not sprinklered, roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min, except that in buildings not more than 1 storey in building height, the fire-resistance rating is permitted to be waived provided the roof assembly is constructed as a fire-retardant treated wood roof system conforming to Article 3.1.14.1., and the building area is not more than,
(i) 1 600 m2 if facing one street,
(ii) 2 000 m2 if facing two streets, or
(iii) 2 400 m2 if facing three streets,
(d) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction, and
(e) loadbearing walls, columns and arches supporting a fire separation shall have a fire-resistance rating not less than that required for the supported assembly.
Table 3.2.2.70.A.
Maximum Building Area, Group F, Division 2, up to 4 Storeys
Forming Part of Sentence 3.2.2.70.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
3 200 |
4 000 |
4 800 |
2. |
2 |
1 600 |
2 000 |
2 400 |
3. |
3 |
1 070 |
1 340 |
1 600 |
4. |
4 |
800 |
1 000 |
1 200 |
Table 3.2.2.70.B.
Maximum Building Area, Group F, Division 2, up to 4 Storeys, Increased Area, Sprinklered
Forming Part of Sentence 3.2.2.70.(1)
Item |
Column 1 No. of Storeys |
Column 2 Maximum Area, m2 |
1. |
1 |
9 600 |
2. |
2 |
4 800 |
3. |
3 |
3 200 |
4. |
4 |
2 400 |
3.2.2.71. Group F, Division 2, up to 2 Storeys
(1) A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided,
(a) it is not more than 2 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.71.
Table 3.2.2.71.
Maximum Building Area, Group F, Division 2, up to 2 Storeys
Forming Part of Sentence 3.2.2.71.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
1 000 |
1 250 |
1 500 |
2. |
2 |
600 |
750 |
900 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min, and
(b) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.72. Group F, Division 2, up to 2 Storeys, Sprinklered
(1) A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 4 500 m2 if 1 storey in building height, or
(ii) 1 800 m2 if 2 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min, and
(b) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.73. Group F, Division 3, Any Height, Any Area
(1) Except as permitted by Articles 3.2.2.74. to 3.2.2.83., a building classified as Group F, Division 3 shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered if it is regulated by Subsection 3.2.6.,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h, except that floor assemblies are permitted to be fire separations with a fire-resistance rating not less than 1 h in a storage garage with all storeys constructed as open-air storeys,
(c) mezzanines shall have a fire-resistance rating not less 1 h,
(d) if the building is not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, and
(e) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.74. Group F, Division 3, up to 6 Storeys
(1) A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided,
(a) it is not more than 6 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.74.
Table 3.2.2.74.
Maximum Building Area, Group F, Division 3, up to 6 Storeys
Forming Part of Sentence 3.2.2.74.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
not limited |
not limited |
not limited |
2. |
2 |
7 200 |
9 000 |
10 800 |
3. |
3 |
4 800 |
6 000 |
7 200 |
4. |
4 |
3 600 |
4 500 |
5 400 |
5. |
5 |
2 880 |
3 600 |
4 320 |
6. |
6 |
2 400 |
3 000 |
3 600 |
(2) The building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h,
(c) roof assemblies shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.75. Group F, Division 3, up to 6 Storeys, Sprinklered
(1) A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 6 storeys in building height, and
(c) it has a building area,
(i) that is not limited if the building is not more than 1 storey in building height,
(ii) not more than 21 600 m2 if 2 storeys in building height,
(iii) not more than 14 400 m2 if 3 storeys in building height,
(iv) not more than 10 800 m2 if 4 storeys in building height,
(v) not more than 8 640 m2 if 5 storeys in building height, or
(vi) not more than 7 200 m2 if 6 storeys in building height.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
3.2.2.76. Group F, Division 3, up to 4 Storeys
(1) A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided,
(a) it is not more than 4 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.76.
Table 3.2.2.76.
Maximum Building Area, Group F, Division 3, up to 4 Storeys
Forming Part of Sentence 3.2.2.76.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
4 800 |
6 000 |
7 200 |
2. |
2 |
2 400 |
3 000 |
3 600 |
3. |
3 |
1 600 |
2 000 |
2 400 |
4. |
4 |
1 200 |
1 500 |
1 800 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min,
(c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min, except that in a building not more than 1 storey in building height, the fire-resistance rating is permitted to be waived provided the roof assembly is constructed as a fire-retardant treated wood roof system conforming to Article 3.1.14.1., and the building area is not more than,
(i) 2 400 m2 if facing one street,
(ii) 3 000 m2 if facing two streets, or
(iii) 3 600 m2 if facing three streets, and
(d) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.77. Group F, Division 3, up to 4 Storeys, Sprinklered
(1) A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 4 storeys in building height, and
(c) it has a building area not more than,
(i) 14 400 m2 if 1 storey in building height,
(ii) 7 200 m2 if 2 storeys in building height,
(iii) 4 800 m2 if 3 storeys in building height, or
(iv) 3 600 m2 if 4 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min, and
(c) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.78. Group F, Division 3, up to 2 Storeys
(1) A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided,
(a) it is not more than 2 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.78.
Table 3.2.2.78.
Maximum Building Area, Group F, Division 3, up to 2 Storeys
Forming Part of Sentence 3.2.2.78.(1)
Item |
Column 1 |
Column 2 |
Column 3 |
Column 4 |
|
No. of Storeys |
Maximum Area, m2 |
|
|
|
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets |
1. |
1 |
1 600 |
2 000 |
2 400 |
2. |
2 |
800 |
1 000 |
1 200 |
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,
(b) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.79. Group F, Division 3, up to 2 Storeys, Sprinklered
(1) A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than,
(i) 7 200 m2 if 1 storey in building height, or
(ii) 2 400 m2 if 2 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and,
(a) floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,
(b) loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall,
(i) have a fire-resistance rating not less than 45 min, or
(ii) be of noncombustible construction.
3.2.2.80. Group F, Division 3, 1 Storey
(1) A building classified as Group F, Division 3 is permitted to be of heavy timber construction or noncombustible construction used singly or in combination provided,
(a) it is not more than 1 storey in building height, and
(b) it has a building area not more than,
(i) 5 600 m2 if facing one street,
(ii) 7 000 m2 if facing two streets, or
(iii) 8 400 m2 if facing three streets.
3.2.2.81. Group F, Division 3, 1 Storey, Sprinklered
(1) A building classified as Group F, Division 3 is permitted to be of heavy timber construction or noncombustible construction used singly or in combination provided,
(a) except as permitted by Sentence 3.2.2.7.(1), the building is sprinklered,
(b) it is not more than 1 storey in building height, and
(c) it has a building area not more than 16 800 m2.
3.2.2.82. Group F, Division 3, 1 Storey, Any Area, Low Fire Load Occupancy
(1) A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided it is,
(a) not more than 1 storey in building height,
(b) used solely for low fire load occupancies such as,
(i) power generating plants, or
(ii) plants for the manufacture or storage of noncombustible materials, and
(c) not limited in building area.
(2) The building referred to in Sentence (1) shall be of noncombustible construction.
3.2.2.83. Group F, Division 3, Storage Garages up to 22 m High
(1) A building used as a storage garage with all storeys constructed as open-air storeys and having no other occupancy above it is permitted to have its floor, wall, ceiling and roof assemblies constructed without a fire-resistance rating provided it is,
(a) of noncombustible construction,
(b) not more than 22 m high, measured between grade and the ceiling level of the top storey,
(c) not more than 10 000 m2 in building area, and
(d) designed so that every portion of each floor area is within 60 m of an exterior wall opening.
3.2.3. Spatial Separation and Exposure Protection
3.2.3.1. Limiting Distance and Area of Unprotected Openings
(1) Except as permitted by Articles 3.2.3.10. to 3.2.3.12., the area of unprotected openings in an exposing building face for the applicable limiting distance shall be not more than the value determined in accordance with,
(a) Table 3.2.3.1.B. or Table 3.2.3.1.C. for an exposing building face conforming to Article 3.2.3.2. of a building or fire compartment that is not sprinklered, or
(b) Table 3.2.3.1.D. or Table 3.2.3.1.E. for an exposing building face conforming to Article 3.2.3.2. of a sprinklered fire compartment that is part of a building that is sprinklered in conformance with Section 3.2.
(2) The area of the unprotected openings in an exposing building face shall be the aggregate area of unprotected openings expressed as a percentage of the area of the exposing building face in Table 3.2.3.1.B., Table 3.2.3.1.C., Table 3.2.3.1.D. or Table 3.2.3.1.E.
(3) For the purpose of determining the type of construction and cladding and the fire-resistance rating of an exterior wall,
(a) the exposing building face shall be taken as the projection of the exterior wall onto a vertical plane located so that no portion of the exterior wall of the building or of a fire compartment, if the fire compartment complies with the requirements of Article 3.2.3.2., is between the vertical plane and the line to which the limiting distance is measured, and
(b) the area of unprotected openings shall be determined from Table 3.2.3.1.B., Table 3.2.3.1.C., Table 3.2.3.1.D. or Table 3.2.3.1.E.
(4) For the purpose of determining the actual percentage of unprotected openings permitted in an exterior wall, the location of the exposing building face is permitted to be taken at a vertical plane located so that there are no unprotected openings between the vertical plane and the line to which the limiting distance is measured.
(5) Except for buildings that are sprinklered, where the limiting distance is 2 m or less, the area of each individual unprotected opening in an exposing building face shall not be greater than,
(a) the area in Table 3.2.3.1.A., or
(b) for a limiting distance equal to or greater than 1.2 m, the area calculated as follows:
Area = 0.24 [(2 × LD) – 1.2]2
where,
Area = area of the unprotected opening in m2, and
LD = limiting distance in m.
Table 3.2.3.1.A
Maximum Concentrated Area of Unprotected Openings
Forming Part of Sentence 3.2.3.1.(5)
Item |
Column 1 Limiting Distance, m |
Column 2 Maximum Area of Individual Unprotected Openings, m2 |
1. |
1.2 |
0.35 |
2. |
1.5 |
0.78 |
3. |
2.0 |
1.88 |
(6) The distance between individual unprotected openings described in Sentence (5) that serve a single room or space described in Sentence (7) shall not be less than,
(a) 2 m measured horizontally where the unprotected openings are on the same exposing building face, or
(b) 2 m measured vertically where the unprotected openings both serve,
(i) the single room or space, or
(ii) another room or space on the same storey.
(7) For the purpose of Sentence (6), “single room or space” means a room or space that,
(a) is not divided by a wall,
(b) is divided by,
(i) a wall that extends less than 1.5 m from the interior face of the exterior wall, or
(ii) a partial height wall, or
(c) consists of two or more stacked spaces that are on the same storey.
(8) If a building has any storey that is not sprinklered and firefighting facilities cannot reach it within 10 min of the alarm being received, the required limiting distance shall be doubled.
(9) If the surface temperature on the unexposed surface of a wall assembly exceeds the temperature limit of a standard fire test as permitted by Article 3.1.7.2., an allowance shall be made for the radiation from the hot unexposed wall surface by adding an equivalent area of unprotected opening to the area of actual openings as follows:
AC = A + (AF × FEO)
where,
AC = corrected area of unprotected openings including actual and equivalent openings,
A = actual area of unprotected openings,
AF = area of exterior surface of the exposing building face, exclusive of openings, on which the temperature limit of the standard test is exceeded, and
FEO = an equivalent opening factor derived from the following expression:
FEO =
where,
Tu = average temperature in degrees Celsius of the unexposed wall surface at the time the required fire-resistance rating is reached under test conditions,
Te = 892°C for a fire-resistance rating not less than 45 min, 927°C for a fire-resistance rating not less than 1 h, and 1 010°C for a fire-resistance rating not less than 2 h.
(10) Unless a closure used to protect an opening in an exposing building face has a protective performance equivalent to that required for the wall assembly in which it is located, an equivalent area of unprotected opening, determined in accordance with the procedures of Sentence (9) shall be added to the greater of,
(a) the actual area of unprotected openings, or
(b) the corrected area of unprotected openings.
(11) The required limiting distance for an exposing building face is permitted to be measured to a point beyond the property line that is not the centre line of a street, lane or public thoroughfare if,
(a) the owners of the properties on which the limiting distance is measured and the municipality enter into an agreement in which such owners agree that,
(i) each owner covenants that, for the benefit of land owned by the other covenantors, the owner will not construct a building on his or her property unless the limiting distance for exposing building faces in respect of the proposed construction is measured in accordance with the agreement,
(ii) the covenants contained in the agreement are intended to run with the lands, and the agreement shall be binding on the parties and their respective heirs, executors, administrators, successors and assigns,
(iii) the agreement shall not be amended or deleted from title without the consent of the municipality, and
(iv) they will comply with such other conditions as the municipality considers necessary, including indemnification of the municipality by the other parties, and
(b) the agreement referred to in Clause (a) is registered against the title of the properties to which it applies.
(12) Where an agreement referred to in Sentence (11) is registered against the title of a property, the limiting distance for exposing building faces shall be measured to the point referred to in the agreement.
Table 3.2.3.1.B.
Unprotected Opening Limits for a Building or Fire Compartment that is not Sprinklered
Forming Part of Article 3.2.3.1.
Item |
Exposing Building Face |
Area of Unprotected Openings for Groups A, C, D, and F, Division 3 Occupancies, % |
|
|
|
|
|
|||||||||||||||||||||
|
Maximum Area, m2 |
Ratio (L/H or H/L)(1) |
Limiting Distance, m |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
0 |
1.2 |
1.5 |
2 |
2.5 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
14 |
16 |
18 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
1. |
10 |
Less than 3:1 |
0 |
8 |
10 |
18 |
29 |
46 |
91 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
8 |
12 |
21 |
33 |
50 |
96 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
11 |
18 |
32 |
48 |
68 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2. |
15 |
Less than 3:1 |
0 |
7 |
9 |
14 |
22 |
33 |
63 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
8 |
10 |
17 |
25 |
37 |
67 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
10 |
15 |
26 |
39 |
53 |
87 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3. |
20 |
Less than 3:1 |
0 |
7 |
9 |
12 |
18 |
26 |
49 |
81 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
8 |
10 |
15 |
21 |
30 |
53 |
85 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
9 |
14 |
23 |
33 |
45 |
72 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4. |
25 |
Less than 3:1 |
0 |
7 |
8 |
11 |
16 |
23 |
41 |
66 |
98 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
8 |
9 |
13 |
19 |
26 |
45 |
70 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
9 |
13 |
21 |
30 |
39 |
62 |
90 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5. |
30 |
Less than 3:1 |
0 |
7 |
8 |
11 |
15 |
20 |
35 |
56 |
83 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
7 |
9 |
12 |
17 |
23 |
39 |
61 |
88 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
8 |
12 |
19 |
27 |
36 |
56 |
79 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6. |
40 |
Less than 3:1 |
0 |
7 |
8 |
10 |
13 |
17 |
28 |
44 |
64 |
89 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
7 |
8 |
11 |
15 |
20 |
32 |
48 |
69 |
93 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
8 |
11 |
17 |
24 |
31 |
47 |
66 |
88 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7. |
50 |
Less than 3:1 |
0 |
7 |
8 |
9 |
12 |
15 |
24 |
37 |
53 |
72 |
96 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
7 |
8 |
10 |
14 |
18 |
28 |
41 |
57 |
77 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
8 |
10 |
15 |
21 |
28 |
41 |
57 |
76 |
97 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8. |
60 |
Less than 3:1 |
0 |
7 |
8 |
9 |
11 |
14 |
21 |
32 |
45 |
62 |
81 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
7 |
8 |
10 |
13 |
16 |
25 |
36 |
49 |
66 |
85 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
8 |
10 |
14 |
20 |
25 |
38 |
51 |
67 |
85 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
9. |
80 |
Less than 3:1 |
0 |
7 |
7 |
8 |
10 |
12 |
18 |
26 |
36 |
48 |
62 |
79 |
98 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
7 |
8 |
9 |
11 |
14 |
21 |
29 |
40 |
52 |
67 |
84 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
8 |
9 |
13 |
17 |
22 |
32 |
44 |
56 |
70 |
86 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10. |
100 |
Less than 3:1 |
0 |
7 |
7 |
8 |
9 |
11 |
16 |
22 |
30 |
40 |
51 |
65 |
80 |
97 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
7 |
8 |
9 |
11 |
13 |
18 |
25 |
34 |
44 |
56 |
69 |
84 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
7 |
9 |
12 |
16 |
20 |
29 |
39 |
49 |
61 |
74 |
89 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
11. |
150 |
Less than 3:1 |
0 |
7 |
7 |
8 |
9 |
10 |
13 |
17 |
22 |
29 |
37 |
46 |
56 |
67 |
79 |
93 |
100 |
|
|
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
7 |
7 |
8 |
10 |
11 |
15 |
20 |
26 |
33 |
41 |
50 |
60 |
71 |
84 |
97 |
100 |
|
|
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
7 |
8 |
11 |
13 |
17 |
24 |
31 |
39 |
48 |
57 |
68 |
79 |
91 |
100 |
|
|
|
|
|
|
|
|
|
|
|
12. |
250 |
Less than 3:1 |
0 |
7 |
7 |
7 |
8 |
9 |
10 |
13 |
16 |
20 |
25 |
30 |
36 |
43 |
51 |
59 |
68 |
87 |
100 |
|
|
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
7 |
7 |
8 |
9 |
10 |
12 |
15 |
19 |
24 |
28 |
34 |
40 |
47 |
55 |
63 |
72 |
92 |
100 |
|
|
|
|
|
|
|
|
|
over 10:1 |
0 |
7 |
8 |
9 |
11 |
14 |
19 |
24 |
30 |
36 |
43 |
50 |
57 |
65 |
73 |
82 |
92 |
100 |
|
|
|
|
|
|
|
|
13. |
350 |
Less than 3:1 |
0 |
7 |
7 |
7 |
8 |
8 |
9 |
11 |
14 |
16 |
20 |
24 |
28 |
33 |
38 |
44 |
50 |
64 |
81 |
99 |
100 |
|
|
|
|
|
|
|
3:1 to 10:1 |
0 |
7 |
7 |
8 |
9 |
9 |
11 |
13 |
16 |
19 |
23 |
27 |
32 |
37 |
42 |
48 |
55 |
69 |
85 |
100 |
|
|
|
|
|
|
|
|
over 10:1 |
0 |
7 |
8 |
9 |
10 |
12 |
16 |
21 |
25 |
30 |
36 |
41 |
47 |
53 |
59 |
66 |
73 |
88 |
100 |
|
|
|