1. Scope

This standard specifies, for the purposes of Article 1.2.1.1. of Division A of the Building Code, the objectives and functional statements that have been attributed to acceptable solutions provided in Division B of the Building Code.

2. Objectives and Functional Statements

The objectives listed in this standard are those set out in Part 2 of Division A of the Building Code.

The functional statements listed in this standard are set out in Part 3 of Division A of the Building Code.

3. Attribution to Acceptable Solutions

For the purposes of compliance with the Building Code, as required in Sentence 1.2.1.1.(2) of Division A of the Building Code, the objectives and functional statements attributed to the acceptable solutions in Division B shall be the objectives and functional statements listed in Table 2, Table 3, Table 4, Table 5, Table 6, Table 7, Table 8, Table 9, Table 10, Table 11 and Table 12.

Table 2 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 2 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 2 of Division B
Acceptable SolutionsObjectives and Functional Statements
2.2.1.2. Prohibition of Occupancy CombinationsN/A
(1)[F02-OS1.2]
(2)[F02-OS1.2]
2.2.1.4. Separation of OccupanciesN/A
(1)[F03-OS1.2]
(3)[F03-OS1.2]
2.2.1.5. Fire Separations and ClosuresN/A
(1)[F03-OS1.2]
2.2.1.7. FirewallsN/A
(1)[F03-OS1.2] [F12-OS1.5]
(2)[F03-OS1.2] [F12-OS1.5]
2.1.1.8. Fire BlocksN/A
(1)[F03-OS1.2]
(2)[F03-OS1.2]
(3)[F03-OS1.2]
(4)[F03-OS1.2]
2.1.1.9. Additional Fire SeparationsN/A
(1)[F03-OS1.2]
(3)(a) [F02-OS1.2] (b) [F02, F03-OS1.2]
(4)[F02, F03-OS1.2]
(5)[F02, F03-OS1.2]
2.2.1.10. Determination of Fire-Resistance RatingsN/A
(1)[F03-OS1.2] [F04-OS1.3]
(2)[F03-OS1.2] [F04-OS1.3]
2.2.1.12. Flame-Spread RatingN/A
(1)[F02, F03-OS1.2]
(3)[F02, F03-OS1.2]
2.2.1.13. Foamed PlasticsN/A
(1)[F01-OS1.1] [F02-OS1.2]
2.2.1.14. Fabrics and FilmsN/A
(1)[F02-OS1.2]
2.2.1.15. Electrical Wiring and EquipmentN/A
(2)[F01-OS1.1] [F81-OS1.4]
2.2.1.17. Occupant LoadN/A
(1)[F10-OS1.5]
2.2.3.1. Determination of Requirement for a Fire Alarm SystemN/A
(1)[F11-OS1.5] [F13-OS1.2, OS1.5]
2.2.3.2. Types of Fire Alarm SystemsN/A
(1)[F11-OS1.5]
2.2.3.3. Design of Fire Alarm SystemsN/A
(1)(a) [F03-OS1.2] (b) [F11-OS1.2]
2.2.3.4. Fire Alarm SignalsN/A
(1)(b), (c) [F11-OS1.5]
(2)[F11-OS1.5]
(3)[F11-OS1.5]
2.2.3.5. Silencing of Alarm SignalsN/A
(1)[F11-OS1.5] [F34, F81-OS1.5]
2.2.3.6. Electrical SupervisionN/A
(1)[F82-OS1.2, OS1.5]
2.2.3.7. Fire DetectorsN/A
(1)(a) [F11-OS1.5] (b) [F11-OS1.5]
(2)[F02-OS1.2] [F11-OS1.5]
2.2.4.1. Fire Department Access to BuildingsN/A
(1)[F12-OS1.2, OS1.5]
(2)[F12-OS1.2, OS1.5]
2.2.4.2. Automatic Sprinkler SystemsN/A
(3)[F11-OS1.5] [F12-OS1.2, OS1.5]
2.2.4.3. Portable Fire ExtinguishersN/A
(1)[F02, F12, F81-OS1.2]
2.2.5.1. Minimum Lighting RequirementsN/A
(1)[F30-OS3.1] [F10-OS3.7] [F10-OS1.5]
(2)[F30-OS3.1] [F10-OS3.7] [F10-OS1.5]
(3)[F30-OS3.1] [F10-OS3.7] [F10-OS1.5]
2.2.6.2. Egress DoorwaysN/A
(1)[F10-OS1.5]
(2)[F10-OS1.5]
(3)[F10-OS1.5]
2.2.6.3. Travel DistanceN/A
(1)[F10-OS1.5]
2.2.6.5. Access to ExitsN/A
(1)[F30-OS3.1] [F10-OS3.7] [F10-OS1.5]
(2)[F43-OS3.7]
2.2.6.6. Door SwingN/A
(1)[F10-OS3.7] [F10-OS1.5]
(2)[F10-OS3.7]
2.2.6.7. Doors and Door HardwareN/A
(1)(a), (b), (c) [F10, F12-OS3.7] (d) [F30-OS3.1]
(2)(a) [F03-OS1.2] (b) [F44-OS3.4]
2.2.6.8. Ramps and StairwaysN/A
(1)(a) [F30-OS3.1]
(2)[F30-OS3.1]
2.2.6.9. Floor OpeningsN/A
(1)[F20-OS3.1]
(2)[F30-OS3.1]
2.2.6.10. GuardsN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
2.2.6.12. Transparent Doors and PanelsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
2.2.7.3. Minimum Number of ExitsN/A
(1)[F10, F12-OS3.7] [F10, F12-OS1.5]
2.2.7.4. Distance Between ExitsN/A
(1)[F10-OS1.5]
2.2.7.5. Location of ExitsN/A
(1)[F10-OS3.7] [F10-OS1.5]
2.2.7.6. Width and Height of ExitsN/A
(1)[F10-OS3.7]
(3)[F10-OS1.5] [F10, F30-OS3.7]
2.2.7.7. Direction of Exit Door SwingN/A
(1)[F10-OS1.5] [F10-OS3.7]
2.2.7.8. Exit Door HardwareN/A
(1)[F10-OS1.5] [F10-OS3.7]
2.2.7.9. Exit Stairs and Fire EscapesN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F10-OS1.5] [F10-OS3.7]
(5)[F10, F12-OS1.5] [F30-OS3.1] [F10, F12-OS3.7]
2.2.8.1. GeneralN/A
(1)[F01, F02, F03-OS1.1, OS1.2] [F43-OS3.4]
(2)[F43-OS1.1] [F43-OS3.4]
2.2.8.2. Exhaust Ventilation and Explosion VentingN/A
(1)[F01-OS1.1]
2.2.8.3. Below-Floor Storage Areas for Liquid ManureN/A
(2)[F01-OS1.1]
(3)(a) [F11-OS1.1, OS1.4] (b), (c) [F11-OS1.1, OS1.4] (d) [F01, F02-OS1.1] (e) [F01, F02-OS1.4]
(4)[F12-OS1.1] [F01, F02-OS1.2]
(5)[F03-OS1.2]
2.2.8.5. Liquid Manure Storage Tanks and Piping SystemsN/A
(3)[F30, F34-OS3.1]
(4)[F34-OS3.4]
(5)[F34, F43-OS3.4]
(6)[F34, F43-OS3.4]
2.2.8.6. Gas Traps or ValvesN/A
(1)[F01-OS1.1] [F43-OS3.4]
(2)[F01-OS1.1] [F43-OS3.4]
2.2.8.8. Pesticide Storage AreasN/A
(2)(a) [F01-OS1.1] (a) [F43-OS3.4] (b),(c) [F34-OS3.4]
(3)[F43, F44-OS3.4]
(4)[F01, F02, F03-OS1.2] [F43, F44, F46-OS3.4]
2.3.2.2. Poultry ManureN/A
(1)[F20-OS2.1]
(2)[F20-OS2.1]
2.3.2.3. Stored ProductsN/A
(1)[F20-OS2.1]
2.3.2.4. Farm Machinery and VehiclesN/A
(1)[F20-OS2.1]
(3)[F20-OS2.1] [F20-OS2.4]
2.3.2.5. Liquid Manure Storage TanksN/A
(0.1)[F43-OS3.4]
(1)[F20-OS2.1] [F20-OS2.4]
(2)[F20-OS2.1]
(3)[F20-OS2.1]
(4)[F20-OS2.1]
(5)[F43-OS3.4] [F80-OS2.3]
(6)[F43-OS3.4]
(7)[F20-OS2.2, OS2.3] [F20-OP2.2, OP2.3, OP2.4]
(8)[F20-OS2.2, OS2.3] [F20-OP2.2, OP2.3, OP2.4]
2.3.3.1. Unobstructed Slippery RoofsN/A
(1)[F20-OS2.1]
2.3.3.2. Roof Areas of GreenhousesN/A
(1)[F20-OS2.1]
2.4.2.2. GreenhousesN/A
(1)[F44, F50-OS3.4]
2.4.2.3. Controlled-Atmosphere Storage AreasN/A
(3)[F50-OS3.4]
(4)[F50-OS3.4]
2.4.2.4. Silos and Grain Storage BinsN/A
(1)[F01-OS1.1] [F50-OS3.4]
(2)[F02, F44-OS1.2]
(3)[F01-OS1.1] [F50-OS3.4]
2.4.2.5. Below-Floor Storage of Liquid ManureN/A
(1)(a) [F01-OS1.1] (b) [F40-OS3.4] (c) [F01-OS1.1] (c) [F40-OS3.4]

Table 3 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 3 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 3 of Division B
Acceptable SolutionsObjectives and Functional Statements
3.1.1.5. RadonN/A
(1)[F40, F50-OH1.1]
3.1.1.6. Building in Flood PlainsN/A
(1)(a) [F20-OP2.1] (a) [F20-OS2.1, OS2.3] (a) [F61-OH1.3] (b) [F10, F12-OS3.1] [F10, F30-OS3.7]
3.1.3.1. Separation of Major OccupanciesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OS1.2]
(3)[F02, F03, F06-OS1.2] [F10, F05-OS1.5] [F02, F03, F06-OP1.2]
3.1.3.2. Prohibition of Occupancy CombinationsN/A
(1)[F02, F03-OS1.2] [F10-OS1.5]
(2)[F02, F03-OS1.2] [F10-OS1.5]
(3)[F41-OH2.1]
(5)[F02, F03-OS1.2] [F10-OS1.5]
3.1.4.2. Protection of Foamed PlasticsN/A
(1)[F01-OP1.1] [F02-OP1.2] [F01-OS1.1] [F02-OS1.2]
(1.1)[F01-OP1.1] [F02-OP1.2] [F01-OS1.1] [F02-OS1.2]
(2)[F01-OP1.1] [F02-OP1.2] [F01-OS1.1] [F02-OS1.2]
3.1.4.3. Wires and CablesN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F02-OP1.2] [F02-OS1.2]
(3)[F02-OP1.2] [F02-OS1.2]
3.1.4.5. Fire-Retardant Treated WoodN/A
(1)[F02-OP1.2] [F02-OS1.2]
3.1.4.8. Exterior CladdingN/A
(1)[F02, F03-OP3.1]
(2)[F02, F03-OP3.1]
3.1.5.1. Noncombustible MaterialsN/A
(1)[F02-OP1.2] [F02-OS1.2]
3.1.5.5. Combustible Cladding for Exterior WallsN/A
(2)[F02, F03-OP3.1]
3.1.5.21. Wires and CablesN/A
(2)[F02-OP1.2] [F02-OS1.2]
(3)[F02-OP1.2] [F02-OS1.2]
3.1.5.23. Wires in Computer Room FloorsN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F02-OP1.2] [F02-OS1.2]
3.1.6.2. Materials PermittedN/A
(1)[F02-OS1.2] [F02-OP1.2]
3.1.6.3. Structural Mass Timber ElementsN/A
(2)[F04-OS1.3] [F04-OP1.3]
(3)[F02-OS1.2] [F02-OP1.2]
3.1.6.4. Encapsulation of Mass Timber ElementsN/A
(1)[F02-OS1.2] [F02-OP1.2]
(2)[F02-OS1.2] [F02-OP1.2]
3.1.6.5. Determination of Encapsulation RatingsN/A
(1)[F02-OS1.2] [F04-OS1.3] [F02-OP1.2] [F02-OP1.3]
3.1.6.9. Exterior CladdingN/A
(1)[F02-OS1.2] [F02-OP1.2]
(7)[F03-OS1.2] [F03-OP1.2]
(9)[F02, F03-OP3.1] r 1
3.1.6.17. Penetration by Outlet BoxesN/A
(3)[F03-OS1.2] [F03-OP1.2]
3.1.7.1. Determination of RatingsN/A
(1)[F03-OP1.2] [F04-OP1.3] [F03-OS1.2] [F04-OS1.3]
3.1.7.5. Rating of Supporting ConstructionN/A
(1)[F04-OP1.3] [F04-OS1.3]
(3)[F04-OP1.3] [F04-OS1.3]
3.1.8.1. General RequirementsN/A
(1)(a) [F03-OP1.2] (a) [F03-OS1.2]
(2)[F03-OP1.2] Applies to the requirement that openings in fire separations be protected with closures, shafts or other means. [F03-OS1.2] Applies to the requirement that openings in fire separations be protected with closures, shafts or other means.
3.1.8.2. Combustible Construction SupportN/A
(1)[F04-OP1.2] [F04-OS1.2]
3.1.8.3. Continuity of Fire SeparationsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
3.1.8.4. Determination of RatingsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
3.1.8.5. Installation of ClosuresN/A
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F81-OP1.2] [F81-OS1.2]
(6)[F03-OP1.2] [F03-OS1.2]
(7)[F03-OP1.2] [F03-OS1.2]
3.1.8.6. Maximum OpeningsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
3.1.8.7. Location of Fire Dampers and Smoke DampersN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
3.1.8.10. Installation of Fire DampersN/A
(1)[F04-OP1.2] [F04-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F04-OP1.2] [F04-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
(5)[F82-OH1.2] Applies to portion of code text “A tightly fitted access door shall be installed for each fire damper to provide access for ... the resetting of the release device.” [F82-OP1.2] Applies to portion of code text “A tightly fitted access door shall be installed for each fire damper to provide access for the inspection of the damper...” [F82-OS1.2] Applies to portion of code text “A tightly fitted access door shall be installed for each fire damper to provide access for the inspection of the damper...”
3.1.8.11. Installation of Smoke DampersN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
(5)[F82-OH1.2] Applies to portion of code text “A tightly fitted access door shall be installed for each fire damper to provide access for ... the resetting of the release device.” [F82-OP1.2] Applies to portion of code text “A tightly fitted access door shall be installed for each fire damper to provide access for the inspection of the damper...” [F82-OS1.2] Applies to portion of code text “A tightly fitted access door shall be installed for each fire damper to provide access for the inspection of the damper...”
3.1.8.12. Twenty-Minute ClosuresN/A
(3)[F03-OP1.2] [F03-OS1.2]
3.1.8.13. Self-Closing DevicesN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.1.8.14. Hold-Open DevicesN/A
(1)[F03-OS1.2] [F03-OP1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
(5)[F03-OP1.2] [F03-OS1.2]
3.1.8.15. Door LatchesN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.1.8.16. Wired Glass and Glass BlockN/A
(3)[F04-OP1.2] Applies to portion of Code text: “Glass blocks permitted by Sentence (1) shall be ... reinforced with steel reinforcement in each horizontal joint.” [F04-OS1.2] Applies to portion of Code text: “Glass blocks permitted by Sentence (1) shall be ... reinforced with steel reinforcement in each horizontal joint.”
3.1.8.17. Temperature Rise Limit for DoorsN/A
(1)[F03-OP1.2] [F03, F31-OS1.2] [F05-OS1.5]
3.1.8.18. Area Limits for Wired Glass and Glass BlockN/A
(1)[F31-OS1.2] [F05-OS1.5] [F30-OS3.1]
(2)[F31-OS1.2] [F05-OS1.5]
3.1.8.20. Sprinkler Protected Glazed Wall AssemblyN/A
(1)[F03-OP1.2] [F04-OP1.3] [F03-OS1.2] [F04-OS1.3]
(2)[F03-OP1.2] [F04-OP1.3] [F03-OS1.2] [F04-OS1.3]
(3)[F03, F06-OS1.2] [F05, F06-OS1.5] [F03, F06-OP1.2]
3.1.9.1. Fire StopN/A
(1)[F03-OP1.2] [F04-OP1.3] [F03-OS1.2] [F04-OS1.3]
(2)[F03-OP1.2] [F03-OP3.1] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(6)[F03-OP1.2] [F03-OS1.2]
(7)[F03-OP1.2] [F03-OS1.2]
3.1.9.3. Penetration by Outlet BoxesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
3.1.9.4. Combustible Piping PenetrationsN/A
(3)[F03-OS1.2] [F02, F04-OS1.3] [F03-OP1.2] [F02, F04-OP1.3]
(7)[F03-OS1.2] [F02-OS1.3] [F04-OS1.3] [F03-OP1.2] [F02-OP1.3] [F04-OP1.3]
3.1.9.5. Openings Through a Membrane CeilingN/A
(1)[F04-OP1.3] [F04-OS1.3]
(2)[F04-OP1.3] [F04-OS1.3]
3.1.10.1. Prevention of Firewall CollapseN/A
(1)[F04-OP1.2] [F04-OP3.1] [F04-OS1.2]
(2)[F03, F04-OP1.2] [F03, F04-OP3.1] [F03, F04-OS1.2]
(4)[F04-OP1.2] [F04-OP3.1] [F04-OS1.2]
3.1.10.2. Rating of FirewallsN/A
(1)[F03-OP1.2] Applies to portion of Code text: “A firewall which separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2 major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h ...” [F03-OP3.1] Applies to portion of Code text: “A firewall which separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2 major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h …” [F03-OS1.2] Applies to portion of Code text: “A firewall which separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2 major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h ...”
(2)[F03-OP1.2] [F03-OP3.1] [F03-OS1.2]
(3)[F80, F04-OP1.2] [F80, F04-OP1.3] [F80, F04-OS1.2]
(4)[F80, F04-OP1.2] [F80, F04-OP3.1] [F80, F04-OS1.2]
3.1.10.3. Continuity of FirewallsN/A
(1)[F03-OP1.2] Applies to portion of Code text: “A firewall shall extend from the ground continuously through, or adjacent to, all storeys of a building or buildings so separated ...” [F03-OP3.1] Applies to portion of Code text: “A firewall shall extend from the ground continuously through, or adjacent to, all storeys of a building or buildings so separated …” [F03-OS1.2] Applies to portion of Code text: “A firewall shall extend from the ground continuously through, or adjacent to, all storeys of a building or buildings so separated ...”
3.1.10.4. ParapetsN/A
(1)[F03-OP1.2] [F03-OP3.1] [F03-OS1.2]
3.1.10.5. Maximum OpeningsN/A
N/A[F03-OP1.2]
(2)[F03-OP3.1] [F03-OS1.2]
3.1.10.7. Combustible ProjectionsN/A
(1)[F03-OP1.2] Applies to portion of Code text: “Combustible material shall not extend across the end of a firewall...” [F03-OP3.1] Applies to portion of Code text: “Combustible material shall not extend across the end of a firewall...” [F03-OS1.2] Applies to portion of Code text: “Combustible material shall not extend across the end of a firewall...”
(2)[F03-OP1.2] [F03-OP3.1] [F03-OS1.2]
3.1.11.1. Separation of Concealed SpacesN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.1.11.2. Fire Blocks in Wall AssembliesN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.1.11.3. Fire Blocks between Nailing and Supporting ElementsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
3.1.11.4. Fire Blocks Between Vertical and Horizontal SpacesN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.1.11.5. Fire Blocks of Horizontal Concealed SpacesN/A
(1)[F03, F04-OP1.2] [F03, F04-OS1.2]
(2)[F03, F04-OP1.2] [F03, F04-OS1.2]
(3)[F03, F04-OP1.2] [F03, F04-OS1.2]
(4)[F02, F03-OS1.2] [F04-OS1.3] [F02, F03-OP1.2] [F04-OP1.3]
3.1.11.6. Fire Blocks of Crawl SpacesN/A
(1)[F03, F04-OP1.2] [F03, F04–OS1.2]
3.1.11.7. Fire Block MaterialsN/A
(1)[F04-OP1.2] [F04-OS1.2]
(6)[F04-OP1.2] [F04-OS1.2]
(7)[F03-OP1.2] [F03-OS1.2]
3.1.12.1. Determination of RatingsN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F02-OP1.2] [F02-OS1.2]
3.1.13.2. Flame-Spread RatingN/A
(1)[F02-OP1.2] [F02-OS1.2]
3.1.13.5. SkylightsN/A
(1)[F02-OS1.5]
3.1.13.6. CorridorsN/A
(1)[F02-OS1.2, OS1.5] [F02-OP1.2]
(5)[F02-OS1.2, OS1.5] [F02-OP1.2]
(6)[F02-OS1.2] [F02-OP1.2]
3.1.13.7. High BuildingsN/A
(1)[F02-OP1.2] [F02-OS1.2]
(5)[F02-OP1.2] [F02-OS1.2]
3.1.13.9. Underground WalkwaysN/A
(1)[F02-OP3.1] [F02-OS1.2]
3.1.13.10. Exterior Exit PassagewayN/A
(1)[F02-OS1.5]
3.1.13.11. Elevator CarsN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F02-OP1.2] [F02-OS1.2]
3.1.14.1. Fire-Retardant Treated Wood Roof SystemsN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F02-OP1.3] [F02-OS1.2, OS1.3]
3.1.14.2. Metal Roof Deck AssembliesN/A
(1)[F02-OP1.2] [F02-OS1.2]
3.1.15.1. Roof Covering ClassificationN/A
(1)[F02-OP1.2] [F02-OP3.1] [F02-OS1.2]
3.1.15.2. Roof CoveringsN/A
(1)[F02-OP1.2] [F02-OP3.1] [F02-OS1.2]
(3)[F02-OP1.2] [F02-OP3.1] [F02-OS1.2]
(4)[F02-OP1.2] [F02-OP3.1] [F02-OS1.2]
3.1.16.1. Fabric Awnings, Canopies and MarqueesN/A
(1)[F02-OP1.2] [F02-OS1.2, OS1.5]
3.1.17.1. Occupant Load DeterminationN/A
(1)[F10-OS3.7] [F72-OH2.1] [F71-OH2.3]
(2)[F10-OS3.7] [F72-OH2.1] [F71-OH2.3]
(4)[F10-OS3.7] [F72-OH2.1] [F71-OH2.3]
3.1.17.2. Public PoolsN/A
(1)[F10-OS3.7] [F72-OH2.1] [F71-OH2.3]
(2)[F10-OS3.7] [F72-OH2.1] [F71-OH2.3]
3.1.18.1. DrainageN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OS2.3]
3.1.19.1. Clearance to BuildingsN/A
(1)[F01-OP1.1] [F01-OS1.1] [F32-OS3.3]
(2)[F01-OP1.1] [F01-OS1.1] [F32-OS3.3]
(3)[F01-OP1.1] [F01-OS1.1] [F32-OS3.3]
3.1.20.1. GlassN/A
(1)[F30-OS2.3, OS3.1]
3.2.1.2. Storage Garage Considered as a Separate BuildingN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
3.2.1.4. Floor Assembly over BasementN/A
(1)[F04-OP1.3] [F03-OS1.2] [F04-OS1.3]
(2)[F04-OP1.2, OP1.3] [F04-OS1.2, OS1.3]
3.2.1.5. Fire Containment in BasementsN/A
(1)[F02-OP1.2, OP1.3] [F02-OS1.2, OS1.3]
3.2.2.2. Special and Unusual StructuresN/A
(1)[F02, F03, F04-OP1.2, OP1.3] [F02, F03, F04-OS1.2, OS1.3]
3.2.2.6. Multiple Major OccupanciesN/A
(1)[F02, F03, F04-OP1.2, OP1.3] [F02, F03, F04-OS1.2, OS1.3]
3.2.2.10. StreetsN/A
(1)[F12-OP1.2] [F12-OS1.2, OS1.5]
3.2.2.15. Storeys Below GroundN/A
(2)(a) [F02, F04-OP1.2, OP1.3] (a) [F02, F04-OS1.2, OS1.3] (b), (c) [F03, F04-OP1.2] [F04-OP1.3] (b), (c) [F03, F04-OS1.2] [F04-OS1.3]
3.2.2.18. Automatic Sprinkler System Required r 1N/A
(2)[F02, F04-OS1.2, OS1.3] [F02, F04-OP1.2, OP1.3]
3.2.2.20. Group A, Division 1, Any Height, Any Area, SprinkleredN/A
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of non- combustible construction,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of non- combustible construction,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” (b), (d) [F03, F04-OP1.2] [F04-OP1.3] (b), (d) [F03, F04-OS1.2] [F04-OS1.3] (c) [F04-OP1.3] (c) [F04-OS1.3]
3.2.2.21. Group A, Division 1, One Storey, Limited Area, SprinkleredN/A
(1)(a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building is sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building is sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “The building referred to in Sentence (1) is permitted to be of heavy timber construction or noncombustible construction used singly or in combination,” [F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a) floor assemblies shall be fire separations, (i) with a fire-resistance rating not less than 45 min,” and to Clause (b). [F02-OS1.2] Applies to portion of Code text: “The building referred to in Sentence (1) is permitted to be of heavy timber construction or noncombustible construction used singly or in combination,” [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) floor assemblies shall be fire separations, (i) with a fire-resistance rating not less than 45 min,” and to Clause (b).
3.2.2.22. Group A, Division 1, One Storey, SprinkleredN/A
(1)(a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building is sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building is sprinklered throughout,”
(2)(a) (d) [F03, F04-OP1.2] [F04-OP1.3] (a) (d) [F03, F04-OS1.2] [F04-OS1.3] (b), (c) [F04-OP1.3] (b), (c) [F04-OS1.3]
3.2.2.23. Group A, Division 2, Any Height, Any Area, SprinkleredN/A
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” (b), (d) [F03, F04-OP1.2] [F04-OP1.3] (b), (d) [F03, F04-OS1.2] [F04-OS1.3] (c) [F04-OP1.3] (c) [F04-OS1.3]
3.2.2.24. Group A, Division 2, up to 6 Storeys, Any Area, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered, throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” (a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.25. Group A, Division 2, up to 2 StoreysN/A
(2)[F04-OP1.3] Applies to portion of Code text: “(c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min,” and to Clause (d). [F04-OS1.3] Applies to portion of Code text: “(c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min,” and to Clause (d). (a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a), (d) [F03, F04-OP1.2] [F04-OP1.3] (a), (d) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.26. Group A, Division 2, up to 2 Storeys, Increased Area, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)(a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.27. Group A, Division 2, up to 2 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) the building is sprinklered throughout,”
3.2.2.28. Group A, Division 2, One StoreyN/A
(2)[F03-OP1.2] [F03-OS1.2]
3.2.2.29. Group A, Division 3, Any Height, Any AreaN/A
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” (b), (e) [F03, F04-OP1.2] [F04-OP1.3] (b), (e) [F03, F04-OS1.2] [F04-OS1.3] (c) [F04-OP1.3] (c) [F04-OS1.3]
(3)[F02-OP1.2] [F04-OP1.3] [F02-OS1.2] [F04-OS1.3]
3.2.2.30. Group A, Division 3, up to 2 StoreysN/A
(2)[F02-OP1.2] Applies to portion of Code text: “Except as permitted by Clauses (c) and (d), the building referred to in Sentence (1) shall be of noncombustible construction,” [F04-OP1.3] Applies to portion of Code text: “(c) roof assemblies shall (i) have a fire-resistance rating not less than 45 min,” and to Clause (d). [F02-OS1.2] Applies to portion of Code text: “Except as permitted by Clauses (c) and (d), the building referred to in Sentence (1) shall be of noncombustible construction,” [F04-OS1.3] Applies to portion of Code text: “(c) roof assemblies shall (i) have a fire-resistance rating not less than 45 min,” and to Clause (d). (a), (d) [F03, F04-OP1.2] [F04-OP1.3] (a), (d) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04–OP1.3] (b) [F04-OS1.3]
(3)[F02-OP1.2] [F04-OP1.3] [F02-OS1.2] [F04–OS1.3]
3.2.2.31. Group A, Division 3, up to 2 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)...the building shall be sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ...the building shall be sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “Except as permitted by Clause (c) ... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “Except as permitted by Clause (c) ... the building referred to in Sentence (1) shall be of noncombustible construction,” (a), (c) [F03-OP1.2] [F04-OP1.2, OP1.3] (a), (c) [F03-OS1.2] [F04-OS1.2, OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.32. Group A, Division 3, One Storey, Increased AreaN/A
(2)[F04-OP1.3] Applies to portion of Code text: “(b) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min,” and to Clause (c). [F04-OS1.3] Applies to portion of Code text: “(b) roof assemblies shall have, if of combustible construction, a fire- resistance rating not less than 45 min,” and to Clause (c). (a), (c) [F04-OP1.3] (a), (c) [F04-OS1.3]
(3)[F02-OP1.2] [F04-OP1.3] [F02-OS1.2] [F04-OS1.3]
3.2.2.33. Group A, Division 3, One Storey, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ...the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ...the building is sprinklered throughout,”
3.2.2.35. Group A, Division 4N/A
(1)[F02-OP1.2] Applies to portion of Code text: “a building classified as Group A, Division 4 shall be of noncombustible construction.” [F02-OS1.2] Applies to portion of Code text: “a building classified as Group A, Division 4 shall be of noncombustible construction.”
(4)[F02, F04-OP1.2, OP1.3] [F02, F04-OS1.2, OS1.3]
3.2.2.36. Group B, Division 1, Any Height, Any Area, SprinkleredN/A
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” (b), (d) [F03, F04-OP1.2] [F04-OP1.3] (b), (d) [F03, F04-OS1.2] [F04-OS1.3] (c) [F04-OP1.3] (c) [F04-OS1.3]
3.2.2.37. Group B, Division 1, up to 3 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” (a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.38. Group B, Division 2, Any Height, Any Area, SprinkleredN/A
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” (b), (d) [F03, F04-OP1.2] [F04-OP1.3] (b), (d) [F03, F04-OS1.2] [F04-OS1.3] (c) [F04-OP1.3] (c) [F04-OS1.3]
3.2.2.39. Group B, Division 2, up to 3 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” (a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.40. Group B, Division 2, up to 2 Storeys, SprinkleredN/A
(1)[F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)(a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.41. Group B, Division 2, One Storey, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,”
3.2.2.42. Group B, Division 3, Any Height, Any Area, SprinkleredN/A
(2)[F02-OS1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OP1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” (a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building shall be sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building shall be sprinklered throughout,” (b), (d) [F03, F04-OP1.2] [F04-OP1.3] (b), (d) [F03, F04-OS1.2] [F04-OS1.3] (c) [F04-OP1.3] (c) [F04-OS1.3]
3.2.2.43. Group B, Division 3, up to 3 Storeys (noncombustible), SprinkleredN/A
(1)(a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building is sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building is sprinklered throughout,”
(2)[F02-OS1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OP1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” (a), (c) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (c) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (c) [F04-OS1.3] (b), (c) [F04-OP1.3]
3.2.2.44. Group B, Division 3, up to 3 Storeys, SprinkleredN/A
(1)(a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building is sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building is sprinklered throughout,”
(2)(a), (c) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (c) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (c) [F04-OS1.3] (b), (c) [F04-OP1.3]
3.2.2.45. Group B, Division 3, up to 2 Storeys, SprinkleredN/A
(1)(a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building is sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building is sprinklered throughout,”
(2)(a), (c) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (c) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (c) [F04-OS1.3] (b), (c) [F04-OP1.3]
3.2.2.46. Group B, Division 3, up to One Storey, SprinkleredN/A
(1)(a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building is sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building is sprinklered throughout,”
3.2.2.47. Group C, Any Height, Any Area, SprinkleredN/A
(2)[F02-OP1.2] Applies to portion of Code text: “...the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “...the building referred to in Sentence (1) shall be of noncombustible construction,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “...the building shall be sprinklered throughout,” (a) [F02, F04-OS1.2, OP1.3] Applies to portion of Code text: “...the building shall be sprinklered throughout,” (b), (d) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (d) [F03-OS1.2] [F04-OS1.2, OS1.3] (c), (d) [F04-OP1.3] (c), (d) [F04-OS1.3]
3.2.2.48. Group C, up to 12 Storeys, Sprinklered, Encapsulated Mass Timber ConstructionN/A
(2)(b), (c) [F04-OS1.3] (b), (c) [F04-OP1.3] (a), (c) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (c) [F03-OP1.2] [F04-OP1.2, OP1.3]
3.2.2.49. Group C, up to 6 Storeys, Sprinklered, Noncombustible constructionN/A
(1)(a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “...the building shall be sprinklered throughout,” (a) [F02, F04-OS1.2, OP1.3] Applies to portion of Code text: “...the building shall be sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “...the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “...the building referred to in Sentence (1) shall be of noncombustible construction,” (a), (c) [F03-OP1.2] [F04-OP1.2, OP1.3] (a), (c) [F03-OS1.2] [F04-OS1.2, OS1.3] (b), (c) [F04-OP1.3] (b,) (c) [F04-OS1.3]
3.2.2.50. Group C, up to 4 Storeys, Noncombustible constructionN/A
(2)[F02-OP1.2] Applies to portion of Code text: “...the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “...the building referred to in Sentence (1) shall be of noncombustible construction,” [F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (d). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (d). (b), (d) [F04-OP1.3] (b), (d) [F04-OS1.3] (c), (d) [F04-OP1.3] (c), (d) [F04-OS1.3]
3.2.2.51. Group C, up to 6 Storeys, Sprinklered, Combustible constructionN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ...the building shall be sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ...the building shall be sprinklered throughout,”
(2)[F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (e). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (e). (b), (d), (e) [F04-OS1.3] (b), (d), (e) [F04-OP1.3] (c) [F04-OS1.3] Applies to portion of Code text: “... the roof assembly shall be constructed of noncombustible construction or fire-retardant-treated wood conforming Article 3.1.4.5.,” (c) [F04-OP1.3] Applies to portion of Code text: “... the roof assembly shall be constructed of noncombustible construction or fire-retardant-treated wood conforming Article 3.1.4.5.,”
3.2.2.52. Group C, up to 4 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (c). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (c). (b), (c) [F04-OP1.3] (b), (c) [F04-OS1.3]
3.2.2.53. Group C, up to 3 Storeys, Increased AreaN/A
(2)[F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (d). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (d). (b), (d) [F04-OP1.3] (b), (d) [F04-OS1.3] (c), (d) [F04-OP1.3] (c), (d) [F04-OS1.3]
3.2.2.54. Group C, up to 3 StoreysN/A
(2)[F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a)... floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,” and to Clause (c). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,” and to Clause (c). (b), (c) [F04-OP1.3] (b), (c) [F04-OS1.3]
3.2.2.55. Group C, up to 3 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F03-OS1.2] [F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,” and to Clause (c). to [F03-OP1.2] [F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) … floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,” and to Clause (c). to (b), (c) [F04-OP1.3] (b), (c) [F04–OS1.3]
3.2.2.55A. Group C, Retirement Home, Any Height, Any Area, SprinkleredN/A
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building shall be sprinklered,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building shall be sprinklered throughout,” [F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(b)... floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,” and to Clause (d). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(b) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,” and to Clause (d). (c), (d) [F04-OP1.3] (c), (d) [F04-OS1.3]
3.2.2.55B. Group C, Retirement Home, up to 4 Storeys, Sprinklered, Increased AreaN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a)... floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,” and to Clause (c). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,” and to Clause (c). (b), (c) [F04-OP1.3] (b), (c) [F04-OS1.3]
3.2.2.55C. Group C, Retirement Home, up to 4 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a)... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (c). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (c). (b), (c) [F04-OP1.3] (b), (c) [F04-OS1.3]
3.2.2.55D. Group C, Retirement Home, up to 3 Storeys, Sprinklered, Noncombustible constructionN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a)... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (c). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (c). (b), (c) [F04-OP1.3] (b), (c) [F04-OS1.3]
3.2.2.55E. Group C, Retirement Home, up to 3 Storeys, Sprinklered, Combustible constructionN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) is permitted... or noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) is permitted… or noncombustible construction,” [F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a)... floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,” and to Clause (c). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,” and to Clause (c). (b), (c) [F04-OP1.3] (b), (c) [F04-OS1.3]
3.2.2.56. Group D, Any Height, Any Area, SprinkleredN/A
(2)[F02-OS1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OP1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” (a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building shall be sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building shall be sprinklered throughout,” (b), (d) [F03-OS1.2] [F04-OS1.2, OS1.3] (b), (d) [F03-OP1.2] [F04-OP1.2, OP1.3] (c), (d) [F04-OS1.3] (c), (d) [F04-OP1.3]
3.2.2.57. Group D, up to 12 Storeys, Sprinklered, Encapsulated Mass Timber ConstructionN/A
(2)(b), (c) [F04-OS1.3] (b), (c) [F04-OP1.3] (a), (c) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (c) [F03-OP1.2] [F04-OP1.2, OP1.3]
3.2.2.58. Group D, up to 6 StoreysN/A
(2)[F02-OP1.2] Applies to portion of Code text: “The building referred to in Sentence (1) shall be of noncombustible construction,” [F04-OP1.3] Applies to portion of Code text: “(c) roof assemblies shall have a fire-resistance rating not less than 1 h,” and to Clause (d). [F02-OS1.2] Applies to portion of Code text: “The building referred to in Sentence (1) shall be of noncombustible construction,” [F04-OS1.3] Applies to portion of Code text: “(c) roof assemblies shall have a fire-resistance rating not less than 1 h,” and to Clause (d). (a), (d) [F03, F04-OP1.2] [F04-OP1.3] (a), (d) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.59. Group D, up to 6 Storeys, Sprinklered, Noncombustible constructionN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ...the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” (a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.60. Group D, up to 6 Storeys, Sprinklered,N/A
(1)(a) [F02, F04-OS1.2, OS1.3] (a) [F02, F04-OP1.2, OP1.3]
(2)(a), (e) [F03-OS1.2] [F04-OS1.3, OS1.2] (a), (e) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (d), (e) [F04-OS1.3] (b), (d), (e) [F04-OP1.3] (c) [F04-OS1.3] Applies to portion of Code text: “... the roof assembly shall be constructed of noncombustible construction or fire-retardant-treated wood conforming Article 3.1.4.5.,” (c) [F04-OP1.3] Applies to portion of Code text: “.... the roof assembly shall be constructed of noncombustible construction or fire-retardant-treated wood conforming Article 3.1.4.5.,”
3.2.2.61. Group D, up to 4 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)...the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)...the building is sprinklered throughout,”
(2)(a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.62. Group D, up to 3 StoreysN/A
(2)[F04-OP1.3] Applies to portion of Code text: “(c) roof assemblies shall have, if of combustible construction, a fire- resistance rating not less than 45 min,” and to Clause (d). [F04-OS1.3] Applies to portion of Code text: “(c) roof assemblies shall have, if of combustible construction, a fire- resistance rating not less than 45 min,” and to Clause (d). (a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a), (d) [F03, F04-OP1.2] [F04-OP1.3] (a), (d) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.63. Group D, up to 3 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)...the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)...the building is sprinklered throughout,”
(2)(a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.64. Group D, up to 2 StoreysN/A
(2)[F03, F04-OP1.2] [F04-OP1.3] [F03, F04-OS1.2] [F04-OS1.3] (a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that to noncombustible floor assemblies be fire separations.
3.2.2.65. Group D, up to 2 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ...the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ...the building is sprinklered throughout,”
(2)[F03, F04-OP1.2] [F04-OP1.3] [F03, F04-OS1.2] [F04-OS1.3] (a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations.
3.2.2.66. Group E, Any Height, Any Area, SprinkleredN/A
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “... the building shall be sprinklered throughout,” (a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “... the building shall be sprinklered throughout,” (b), (d) [F03, F04-OP1.2] [F04-OP1.3] (b), (d) [F03, F04-OS1.2] [F04-OS1.3] (c) [F04-OP1.3] (c) [F04-OS1.3]
3.2.2.67. Group E, up to 4 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,”
(2)(a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.68. Group E, up to 3 StoreysN/A
(2)(a), (e) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (e) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (d) [F04-OS1.3] (b), (d) [F04-OP1.3] (c), (d) [F04-OS1.3] (c), (d) [F04-OP1.3]
3.2.2.69. Group E, up to 3 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,”
(2)(a), (d) [F03, F04-OP1.2] [F04-OP1.3] (a), (d) [F03, F04-OS1.2] [F04-OS1.3] (b), (c) [F04-OP1.3] (b), (c) [F04-OS1.3]
3.2.2.70. Group E, up to 2 StoreysN/A
(2)[F03, F04-OS1.2] [F04-OS1.3] (a), (b) [F03, F04-OP1.2] [F04-OP1.3]
3.2.2.71. Group E, up to 2 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,”
(2)[F03, F04-OS1.2] [F04-OS1.3] (a), (b) [F03, F04-OP1.2] [F04-OP1.3]
3.2.2.72. Group F, Division 1, up to 4 Storeys, SprinkleredN/A
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building shall be sprinklered throughout,” (b), (d) [F03-OS1.2] [F04-OS1.2, OS1.3] (b), (d) [F03-OP1.2] [F04-OP1.2, OP1.3] (c), (d) [F04-OS1.3]
3.2.2.73. Group F, Division 1, up to 3 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “The building referred to in Sentence (1) is permitted to be of heavy timber construction or noncombustible construction used singly or in combination,” [F03, F04-OP1.2] [F04-OP1.3] [F02-OS1.2] Applies to portion of Code text: “The building referred to in Sentence (1) is permitted to be of heavy timber construction or noncombustible construction used singly or in combination,” [F03, F04-OS1.2] [F04-OS1.3]
3.2.2.74. Group F, Division 1, up to 2 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,”
(2)[F03-OP1.2] Applies to portion of Code text: “(a) [noncombustible] floor assemblies shall be fire separations,” [F04-OP1.2, OP1.3] [F03-OS1.2] Applies to portion of Code text: “(a) [noncombustible] floor assemblies shall be fire separations,” [F04-OS1.2, OS1.3]
3.2.2.76. Group F, Division 2, Any Height, Any Area, SprinkleredN/A
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building shall be sprinklered throughout,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building shall be sprinklered throughout,” (b), (d) [F03, F04-OP1.2] [F04-OP1.3] (b), (d) [F03, F04-OS1.2] [F04-OS1.3] (c) [F04-OP1.3] (c) [F04-OS1.3]
3.2.2.77. Group F, Division 2, up to 4 Storeys, Increased Area, SprinkleredN/A
(1)(a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building is sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building is sprinklered throughout,”
(2)[F02-OS1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OP1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” (a), (c) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (c) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (c) [F04-OS1.3] (b), (c) [F04-OP1.3]
3.2.2.78. Group F, Division 2, up to 3 StoreysN/A
(2)(a), (e) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (e) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (d) [F04-OS1.3] (b), (d) [F04-OP1.3] [F04-OS1.3] Applies to portion of Code text: “… (c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min,” and to Clause (d). [F04-OP1.3] Applies to portion of Code text: “… (c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min,” and to Clause (d).
3.2.2.79. Group F, Division 2, up to 4 Storeys, SprinkleredN/A
(1)(a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building is sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building is sprinklered throughout,”
(2)(a), (d) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (d) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (c) [F04-OS1.3] (b), (c) [F04-OP1.3]
3.2.2.80. Group F, Division 2, up to 2 StoreysN/A
(2)[F03, F04-OP1.2] [F04-OP1.3] [F03, F04-OS1.2] [F04-OS1.3] (a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations.
3.2.2.81. Group F, Division 2, up to 2 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F03, F04-OP1.2] [F04-OP1.3] [F03, F04-OS1.2] [F04-OS1.3] (a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations.
3.2.2.82. Group F, Division 3, Any Height, Any Area, SprinkleredN/A
(2)[F02-OS1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OP1.2] Applies to portion of Code text: “… the building referred to in Sentence (1) shall be of noncombustible construction,” (a) [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “… the building shall be sprinklered throughout,” (a) [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “… the building shall be sprinklered throughout,” (b), (d) [F03-OS1.2] [F04-OS1.2, OS1.3] (b), (d) [F03-OP1.2] [F04-OP1.2, OP1.3] (c), (d) [F04-OS1.3] (c), (d) [F04-OP1.3]
3.2.2.83. Group F, Division 3, up to 6 StoreysN/A
(2)[F02-OP1.2] Applies to portion of Code text: “The building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “The building referred to in Sentence (1) shall be of noncombustible construction,” (a), (d) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (d) [F03-OP1.2] [F04-OP1.2, OP1.3] (b), (d) [F04-OS1.3] (b), (d) [F04-OP1.3] (c), (d) [F04-OS1.3] (c), (d) [F04-OP1.3]
3.2.2.84. Group F, Division 3, up to 6 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F02-OP1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... the building referred to in Sentence (1) shall be of noncombustible construction,” (a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04–OP1.3] (b) [F04-OS1.3]
3.2.2.85. Group F, Division 3, up to 4 StoreysN/A
(2)[F04-OP1.3] Applies to portion of Code text: “(c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min,” and to Clause (d). [F04-OS1.3] Applies to portion of Code text: “(c) roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min,” and to Clause (d). (a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a), (d) [F03, F04-OP1.2] [F04-OP1.3] (a), (d) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.86. Group F, Division 3, up to 4 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a) the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) the building is sprinklered throughout,”
(2)(a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b) [F04-OP1.3] (b) [F04-OS1.3]
3.2.2.87. Group F, Division 3, up to 2 StoreysN/A
(2)[F03, F04-OP1.2] [F04-OP1.3] [F03, F04-OS1.2] [F04-OS1.3] (a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations.
3.2.2.88. Group F, Division 3, up to 2 Storeys, SprinkleredN/A
(1)[F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a)... the building is sprinklered throughout,”
(2)[F03, F04-OP1.2] [F04-OP1.3] [F03, F04-OS1.2] [F04-OS1.3] (a) [F03-OP1.2] Applies to the requirement that noncombustible floor assemblies be fire separations. (a) [F03-OS1.2] Applies to the requirement that noncombustible floor assemblies be fire separations.
3.2.2.89. Group F, Division 3, One StoreyN/A
(1)[F02-OP1.2] Applies to portion of Code text: “A building classified as Group F, Division 3 is permitted to be of heavy timber construction or noncombustible construction used singly or in combination,” [F02-OS1.2] Applies to portion of Code text: “A building classified as Group F, Division 3 is permitted to be of heavy timber construction or noncombustible construction used singly or in combination,”
3.2.2.90. Group F, Division 3, One Storey, SprinkleredN/A
(1)[F02-OP1.2] Applies to portion of Code text: “A building classified as Group F, Division 3 is permitted to be of heavy timber construction or noncombustible construction used singly or in combination,” [F02, F04-OP1.2, OP1.3] Applies to portion of Code text: “a) ... the building is sprinklered throughout,” [F02-OS1.2] Applies to portion of Code text: “A building classified as Group F, Division 3 is permitted to be of heavy timber construction or noncombustible construction used singly or in combination,” [F02, F04-OS1.2, OS1.3] Applies to portion of Code text: “(a) ... the building is sprinklered throughout,”
3.2.2.91. Group F, Division 3, One Storey, Any Area, Low Fire Load OccupancyN/A
(2)[F02-OP1.2] [F02-OS1.2]
3.2.2.92. Group F, Division 3, Storage Garages up to 22 m HighN/A
(1)[F02-OP1.2] Applies to portion of Code text: “A building used as a storage garage with all storeys constructed as open-air storeys and having on other occupancy above it is permitted to have its floor, wall, ceiling and roof assemblies constructed without a fire-resistance rating provided it is a) of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “A building used as a storage garage with all storeys constructed as open-air storeys and having on other occupancy above it is permitted to have its floor, wall, ceiling and roof assemblies constructed without a fire-resistance rating provided it is a) of noncombustible construction,”
3.2.2.93. Encapsulated Mass Timber Construction, Various Occupancies, Heights and Areas, SprinkleredN/A
(2)(b), (c) [F04-OS1.3] (b), (c) [F04-OP1.3] (a), (c) [F03-OS1.2] [F04-OS1.2, OS1.3] (a), (c) [F03-OP1.2] [F04-OP1.2, OP1.3]
3.2.3.1. Limiting Distance and Area of Unprotected OpeningsN/A
N/AOpenings
(1), (5), (6), (8) to (10)[F03-OP3.1]
3.2.3.5. Wall with Limiting Distance Less Than 1.2 mN/A
(1)[F03-OP3.1]
(2)[F03-OP3.1]
3.2.3.6. Combustible ProjectionsN/A
(1) to (3)[F03-OP3.1]
(5)[F03-OP3.1]
3.2.3.7. Construction of Exposing Building FaceN/A
(1)[F02, F03-OP3.1]
(2)[F02, F03-OP3.1]
(3)[F02, F03-OP3.1]
(4)[F02, F03-OP3.1]
3.2.3.8. Protection of Exterior Building FaceN/A
(1)[F02, F03-OP3.1]
3.2.3.9. Protection of Structural MembersN/A
(1)[F04-OP1.3] [F04-OS1.3]
3.2.3.10. Unlimited Unprotected OpeningsN/A
(1)[F03-OP3.1]
(2)[F03-OP3.1]
3.2.3.11. Low Fire Load, One Storey BuildingN/A
(1)(a) [F04-OP3.1] (b) [F03-OP3.1]
3.2.3.12. Area Increase for Unprotected OpeningsN/A
(1)[F03-OP3.1]
3.2.3.13. Protection of Exit FacilitiesN/A
(4)[F06-OP1.2] [F05, F06-OS1.2]
3.2.3.14. Wall Exposed to Another WallN/A
(1)[F03-OP1.2] [F03-OP3.1] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OP3.1] [F03-OS1.2]
3.2.3.15. Wall Exposed to Adjoining RoofN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.2.3.16. Protection of SoffitsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F02-OP1.2] [F02-OS1.2]
3.2.3.17. Canopy Protection for Vertically Separated OpeningsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F02-OP1.2] [F02-OS1.2]
3.2.3.18. Covered Vehicular PassagewayN/A
(1)[F03-OP3.1]
(2)[F03-OP3.1]
3.2.3.19. Walkway between BuildingsN/A
(1)[F03-OP3.1]
(2)[F02-OP3.1]
(3)[F02-OP3.1]
(4)[F02, F12-OP3.1]
3.2.3.20. Underground WalkwayN/A
(1)[F01, F02-OP3.1]
(2)[F03-OP3.1]
(3)[F02-OP3.1] Applies to portion of Code text: “An underground walkway shall be of noncombustible construction...” [F80-OP2.3] Applies to portion of Code text: “An underground walkway shall be ... suitable for an underground location.”
(4)(a) [F06-OS1.2] [F05-OS1.5] (b) [F12-OS1.2] [F10-OS1.5]
3.2.4.1. Determination of Requirement for a Fire Alarm SystemN/A
(1)[F11-OS1.5] [F13-OS1.5, OS1.2] [F13-OP1.2]
(4)[F11-OS1.5]
3.2.4.2. Continuity of Fire Alarm SystemN/A
(1)[F11-OS1.5]
(2)[F11-OS1.5]
(3)[F11-OS1.5]
(4)[F03-OS1.2] [F10-OS1.5]
(5)[F11, F13-OS1.2]
(6)[F11-OS1.5]
3.2.4.3. Types of Fire Alarm SystemsN/A
(1)(a) [F11-OS1.5] (b) [F11-OS1.4] [F13-OS1.5] (c), (d), (e) [F11-OS1.5]
3.2.4.4. Description of Fire Alarm SystemsN/A
(1)[F11-OS1.5]
(2)(a), (d) [F11-OS1.4] [F13-OS1.5] (b), (c) [F11-OS1.5]
(3)[F13-OS1.5]
(4)[F13-OS1.5]
3.2.4.5. Installation and Verification of Fire Alarm SystemsN/A
(1)[F12, F13, F81-OS1.2] [F11, F12, F13, F81-OS1.5] [F11, F12-OS3.7] Applies to voice communication systems.
(2)[F82-OS1.5]
3.2.4.6. Silencing of Alarm SignalsN/A
(1)[F11-OS1.5]
(2)[F34, F81-OS1.5]
3.2.4.7. Signals to Fire DepartmentN/A
(1)[F13-OP1.2] [F13-OS1.2, OS1.5]
(2)[F13-OP1.2] [F13-OS1.2, OS1.5]
(3)[F13-OP1.2] [F13-OS1.2, OS1.5]
(4)[F13, F81-OP1.2] [F13, F81-OS1.2, OS1.5]
(5)[F13-OP1.2] [F13-OS1.2, OS1.5]
(6)[F13-OP1.2] [F13-OS1.2]
3.2.4.8. Annunciator and Zone IndicationN/A
(1)[F12-OS1.2, OS1.5]
(2)[F12-OS1.2, OS1.5]
(4)[F12-OS1.2, OS1.5]
(7)[F12-OS1.2, OS1.5]
(8)[F12-OS1.2, OS1.5]
(9)[F12-OS1.2, OS1.5]
3.2.4.9. Electrical SupervisionN/A
(1)[F82-OS1.2, OS1.5]
(2)F82-OS1.2] F82-OP1.2]
(3)(a), (d), (e), (f), (g) [F82-OP1.2] (a), (d), (e), (f), (g) [F82-OS1.2] (b), (c) [F82-OS1.5]
(4)[F81, F82-OP1.2] [F81, F82-OS1.2]
(5)(a), (b) [F81, F82-OP1.2] (a), (b) [F81, F82-OS1.2] (c) [F81, F82 - OS1.5]
(6)[F82-OP1.2] [F82-OS1.2]
3.2.4.10. Fire DetectorsN/A
(1)[F11-OS1.5]
(2)[F11-OS1.5]
(3)[F02-OS1.2] [F11-OS1.5]
(4)[F11-OS1.5]
3.2.4.11. Smoke and Heat DetectorsN/A
(1)[F11-OS1.5]
(2)[F11-OS1.5]
(3)[F12-OS1.5]
(4)[F10-OS1.5]
(5)[F11-OS1.5]
(7)[F11-OS1.4, OS1.5]
3.2.4.12. Prevention of Smoke CirculationN/A
(1)[F03-OS1.2]
3.2.4.13. Vacuum Cleaning System ShutdownN/A
(1)[F03-OS1.2]
3.2.4.14. Elevator Emergency ReturnN/A
(1)[F10-OS1.5]
(2)[F11-OS1.5]
(3)[F02-OS1.2]
3.2.4.15. System MonitoringN/A
(1)[F12-OS1.2] [F11, F12-OS1.5] [F12-OP1.2]
(2)[F13-OS1.2] [F11, F13-OS1.5] [F13-OP1.2]
3.2.4.16. Manual StationsN/A
(1)[F11-OS1.5]
(2)[F02, F12-OS1.2] [F10, F12-OS1.5]
(3)[F02, F12-OS1.2] [F10, F12-OS1.5]
(4)[F11-OS1.5]
(5)[F11-OS1.5]
(6)[F11-OS1.5]
(7)[F81-OS1.2] [F11, F81-OS1.5]
(8)[F11-OS1.5]
3.2.4.17. Alert and Alarm SignalsN/A
(2)[F11-OS1.5]
(3)[F11-OS1.5]
3.2.4.18. Audibility of Alarm SystemsN/A
(1)[F11-OS1.5]
(2)[F11-OS1.5]
(3)[F11-OS1.5]
(4)[F33-OS3.5]
(5)[F11-OS1.5]
(6)[F11-OS1.5]
(7)[F11-OS1.5]
(8)[F11, F81-OS1.5]
(9)[F11, F81-OS1.5]
(10)[F11, F81-OS1.5]
(11)[F11-OS1.5]
(13)[F11-OS1.5]
3.2.4.19. Visible SignalsN/A
(1)[F11-OS1.5]
(3)[F11-OS1.5]
3.2.4.20. Smoke AlarmsN/A
(2)[F81, F11-OS1.5]
(3)[F11-OS1.5]
(4)[F11-OS1.5]
(6)[F11-OS1.5]
(9)[F11, F81-OS1.5]
(10)[F11, F81-OS1.5]
(12)[F11-OS1.5]
(13)[F81, F11-OS1.5]
(14)[F11, F81-OS1.5]
(16)[F11-OS1.5]
(17)[F74-OA2], [F11-OS1.5]
(19)[F74-OA2], [F11-OS1.5]
(20)[F11, F81-OS1.5]
3.2.4.21. Residential Fire Warning SystemsN/A
(1)[F81, F11-OS1.5]
3.2.4.22. Two-Way Voice Communication SystemsN/A
(1)[F11, F12-OS3.7]
(2)[F11-OS1.5]
(3)[F11-OS1.5]
(4)F11-OS1.5] [F13-OS1.4, OS1.5]
(5)[F11-OS1.5]
(6)[F12-OS3.7]
(7)[F11-OS1.5]
3.2.4.23. One-Way Voice Communication SystemsN/A
(1)[F11-OS1.5]
(2)[F11-OS1.5]
(3)[F11-OS1.5]
3.2.5.1. Access to Above Grade StoreysN/A
(1)[F12-OP1.2] [F12-OS1.2, OS1.5]
(2)[F12-OP1.2] [F12-OS1.2, OS1.5]
(3)[F12-OP1.2] [F12-OS1.2, OS1.5]
3.2.5.2. Access to BasementsN/A
(1)[F12-OP1.2] [F12-OS1.2, OS1.5]
(2)[F12-OP1.2] [F12-OS1.2, OS1.5]
3.2.5.3. Roof AccessN/A
(1)[F12-OP1.2] [F12-OS1.2]
(2)[F12-OP1.2] [F12-OS1.2] [F05, F06, F10, F12-OS3.7]
3.2.5.4. Access RoutesN/A
(1)[F12-OP1.2] [F12-OS1.2, OS1.5]
3.2.5.5. Location of Access RoutesN/A
(1)[F12-OP1.2] [F06-OS1.1] [F12-OS1.2, OS1.5]
(2)[F12-OP1.2] [F12-OS1.2]
(4)[F12-OP1.2] [F12-OS1.2]
3.2.5.6. Access Route DesignN/A
(1)[F12-OP1.2] [F12-OS1.2]
(2)[F12-OP1.2] [F12-OS1.2]
3.2.5.7. Water SupplyN/A
(1)[F02-OP1.2] [F02-OP3.1] [F02-OS1.2]
(2)[F02, F12-OP1.2] [F02-OP3.1] [F02, F12-OS1.2]
3.2.5.8. Standpipe SystemN/A
(1)[F02-OS1.2] [F02-OP1.2]
3.2.5.9. Standpipe System DesignN/A
(1)[F02-OS1.2] [F02-OP1.2]
(2)[F02-OS1.2] [F02-OP1.2]
(4)[F02-OS1.2] [F02-OP1.2]
(5)[F02-OS1.2] [F02-OP1.2]
3.2.5.10. Hose ConnectionN/A
(1)[F03-OS1.2] [F05, F06-OS1.5,OS1.2] [F03, F06-OP1.2]
(2)[F12-OS1.2] [F12-OP1.2]
(3)[F02-OS1.2] [F02-OP1.2]
3.2.5.11. Hose StationN/A
(1)[F02-OS1.2] [F02-OP1.2]
(2)[F02-OS1.2] [F02-OP1.2]
(3)[F02, F12-OS1.2] [F02, F12-OP1.2]
(4)[F03-OS1.2] [F03-OP1.2]
(5)[F10-OS1.5]
(6)[F02-OS1.2] [F02-OP1.2]
(7)[F01-OS1.1]
3.2.5.12. Automatic Sprinkler SystemsN/A
(1)[F02, F81, F82-OP1.2] [F02, F81, F82-OS1.2]
(2)[F02, F81, F82-OP1.2] [F02, F81, F82-OS1.2]
(3)[F02, F81, F82-OP1.2] [F02, F81, F82-OS1.2]
(4)[F02-OP1.2] [F02-OS1.2]
(5)[F81-OP1.2] [F81-OS1.2]
(6)[F02-OP1.2] [F02-OS1.2]
(7)[F02, F81, F82-OP1.2] [F02, F81, F82-OS1.2]
(8)[F81-OS3.3, OS3.6]
(10)[F02, F04 – OP1.2, OP1.3] [F02, F04 – OS1.2, OS1.3]
3.2.5.13. Combustible Sprinkler PipingN/A
(2)[F02, F81-OP1.2] [F02, F81-OS1.2]
(3)[F06-OP1.2] [F06-OS1.2]
(4)[F06-OP1.2] [F06-OS1.2]
3.2.5.14. Sprinklered Service SpaceN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F12-OP1.2] [F12-OS1.2]
(3)[F12-OS1.2] [F11, F12-OS1.5] [F12-OP1.2]
3.2.5.15. Fire Department ConnectionsN/A
(1)[F12-OP1.2] [F12-OS1.2]
(2)[F12-OP1.2] [F12-OS1.2]
3.2.5.16. Portable Fire ExtinguishersN/A
(1)[F02, F12, F81-OP1.2] [F02, F12, F81-OS1.2]
(2)[F12- OP1.2] [F12-OS1.2]
3.2.5.17. Protection from FreezingN/A
(1)[F81-OP1.2] [F81-OS1.2]
3.2.5.18. Fire PumpsN/A
(1)[F02, F81-OP1.2] [F02, F81-OS1.2]
3.2.6.2. Limits to Smoke MovementN/A
(1)[F02-OP1.2] [F02-OS1.2, OS1.5]
(2)[F06-OP1.2] [F06-OS1.2] [F05, F06-OS1.5]
(3)[F06-OP1.2] [F06-OS1.2] [F05, F06-OS1.5]
(4)[F03, F12-OP1.2] [F03 F12-OS1.2, OS1.5]
(5)[F03-OP1.2] [F03-OS1.2, OS1.5]
(6)[F03, F12-OP1.2] [F03, F12-OS1.2, OS1.5]
(7)[F02-OP1.2] [F02-OS1.2, OS1.5]
3.2.6.3. Connected BuildingsN/A
(1)[F03-OP1.2] [F03-OP3.1] [F03-OS1.2, OS1.5]
3.2.6.4. Emergency Operation of ElevatorsN/A
(1)[F12-OP1.2] [F12-OS1.2, OS1.5]
(2)[F12-OP1.2] [F12-OS1.2, OS1.5]
(3)[F12-OP1.2] [F12-OS1.2, OS1.5]
(4)[F12-OP1.2] [F12-OS1.2, OS1.5]
(5)[F12-OP1.2] [F12-OS1.2, OS1.5]
(6)[F12-OP1.2] [F12-OS1.2, OS1.5]
(7)[F11-OS1.5]
3.2.6.5. Elevator for Use by FirefightersN/A
(1)[F12, F06-OP1.2] [F12, F06-OS1.2, OS1.5]
(2)[F12-OP1.2] [F12-OS1.2, OS1.5]
(3)[F06-OP1.2] [F06-OS1.2, OS1.5]
(4)[F12-OP1.2] [F12-OS1.2, OS1.5]
(5)[F12-OP1.2] [F12-OS1.2, OS1.5]
(6)[F06-OP1.2] [F06-OS1.2, OS1.5]
3.2.6.6. Venting to Aid FirefightingN/A
(1)[F06-OP1.2] [F06-OS1.2, OS1.5]
(2)[F30-OS3.1]
(3)[F12-OP1.2] [F12-OS1.2, OS1.5]
(4)[F03-OS1.2] [F12-OS1.2, OS1.5]
3.2.6.7. Central Alarm and Control FacilityN/A
(1)[F12-OP1.2] [F12-OS1.2, OS1.5]
(2)[F12-OP1.2] [F12-OS1.2, OS1.5] [F11-OS1.5]
3.2.6.8. Voice Communication SystemN/A
(1)[F12, F11-OS3.7]
3.2.6.9. TestingN/A
(1)[F82-OP1.2] [F82-OS1.2, OS1.5]
3.2.7.1. Minimum Lighting RequirementsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1]
(5)[F74-OA2]
(6)[F74-OA2]
(7)[F10-OS3.7] [F74-OA2] [F30-OS3.1]
(9)[F30-OS3.1] [F10-OS3.7]
(10)[F30-OS3.1] [F10-OS3.7]
(11)[F30-OS3.1] [F10-OS3.7] [F40-OH2.4]
(12)[F30-OS3.1] [F10-OS3.7] [F40-OH2.4]
3.2.7.2. Recessed Lighting FixturesN/A
(1)[F01-OP1.1, OP1.2] [F01-OS1.1, OS1.2]
3.2.7.3. Emergency LightingN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
3.2.7.4. Emergency Power for LightingN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30, F81-OS3.1] [F10, F81-OS3.7]
3.2.7.5. Emergency Power Supply InstallationN/A
(1)[F02, F03, F06, F10, F11, F12, F81-OS1.2, OS1.5] [F02, F06, F30, F81-OS3.1] [F10, F11, F12, F81-OS3.7] [F02, F03, F06, F81-OP1.2]
(2)[F12-OS1.5]
3.2.7.6. Emergency Power for HospitalsN/A
(1)[F02, F03, F06, F10, F11, F12, F81-OS1.2, OS1.5] [F02, F06, F30, F81-OS3.1] [F10, F11, F12, F81-OS3.7] [F02, F03, F06, F81-OP1.2]
3.2.7.7. Fuel Supply Shut-off Valves and Exhaust PipesN/A
(1)[F12-OH5] Applies to the requirement for a suitably identified shut-off valve outside the building [F12-OP1.2] Applies to the requirement for a suitably identified shut-off valve outside the building [F12-OS1.1, OS1.2] Applies to the requirement for a suitably identified shut-off valve outside the building [F12-OS1.2, OS1.5] Applies to the requirement for a suitably identified separate shut-off valve. [F81-OS3.1, OS3.7] Applies to the requirement for a suitably identified separate shut-off valve.
(2)[F03-OP1.2] [F03-OS1.2]
3.2.7.8. Emergency Power for Fire Alarm SystemsN/A
(1)[F13-OS1.2] [F11, F13-OS1.5] [F13-OP1.2] Applies to the requirement for fire alarm systems, including those with a voice communication system, to be provided with an emergency power supply.
(2)[F13-OS1.2] [F11, F13-OS1.5] [F13-OP1.2]
(3)[F13-OS1.2] [F11, F13-OS1.5] [F13-OP1.2]
(4)[F13-OS1.2] [F11, F13-OS1.5] [F13-OP1.2]
3.2.7.9. Emergency Power for Building ServicesN/A
(1)[F02, F03, F12-OP1.2] [F02, F03, F12-OS1.2, OS1.5] (a) [F36-OS3.6] [F10, F12-OS3.7] (b) [F02-OP3.1]
(2)[F12-OP1.2] [F12-OS1.2, OS1.5] [F36-OS3.6] [F12-OS3.7]
3.2.7.10. Protection of Electrical ConductorsN/A
(2)[F06-OP1.2] [F06-OS1.2, OS1.5]
(3)[F06-OP1.2] [F06-OS1.2, OS1.5]
(4)[F06-OP1.2] [F06-OS1.2, OS1.5]
(6)[F06-OP1.2] [F06-OS1.2, OS1.5]
(8)[F06-OP1.2] [F06-OS1.2, OS1.5]
(10)[F06-OS1.4] [F06-OP1.2] [F10-OS3.7]
3.2.8.1. ApplicationN/A
(1)[F03, F06-OP1.2] [F03, F06-OS1.2] [F05-OS1.5]
3.2.8.2. Exceptions to Special ProtectionN/A
(3)[F03-OP1.2] [F03-OS1.2]
(5)[F02, F03-OP1.2] [F02, F03-OS1.2]
3.2.8.3. SprinklersN/A
(1)[F02-OS1.2] [F02-OP1.2]
(2)[F02-OS1.2] [F11-OS1.5] [F13-OS1.5, OS1.2] [F02, F13-OP1.2]
3.2.8.4. VestibulesN/A
(1)[F02-OS1.2] [F11-OS1.5] [F13-OS1.5, OS1.2] [F02, F13-OP1.2]
3.2.8.5. Protected Floor SpaceN/A
(1)[F05-OS1.2] [F06-OS1.5]
3.2.8.6. Draft StopsN/A
(1)[F02-OS1.2] [F11-OS1.5] [F13-OS1.5, OS1.2] [F02, F13-OP1.2]
3.2.8.7. Mechanical Exhaust SystemN/A
(1)[F03-OS1.5, OS1.2] [F03-OP1.2]
(2)[F03-OS1.5, OS1.2] [F03-OP1.2]
3.2.8.8. Combustible Content LimitsN/A
(1)[F02-OS1.2] [F02-OP1.2]
3.2.9.1. TestingN/A
(1)[F02, F81, F82-OS1.2, OS1.5] [F02, F81, F82-OP1.2]
3.3.1.1. Separation of SuitesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(3)[F02-OP1.2] [F02-OS1.2]
3.3.1.2. Hazardous Substances, Equipment and ProcessesN/A
(1)[F01, F02, F03-OP1.1, OP1.2] [F01, F02, F03-OS1.1, OS1.2] [F43-OS3.4]
(3)[F05-OS1.5] [F43-OS3.7]
3.3.1.3. Means of EgressN/A
(3)[F10-OS3.7]
(4)[F05, F06, F10, F12-OS3.7]
(5)[F10, F12-OS3.7]
(6)[F05, F06, F10, F12-OS3.7]
(7)[F05, F06, F10, F12-OS3.7]
(8)[F05-OS1.5]
(9)[F05, F06, F10, F12-OS3.7]
3.3.1.4. Public Corridor SeparationsN/A
(1)[F06-OS1.2] [F03, F05, F06-OS1.5] [F03, F06-OP1.2]
(2)[F06-OS1.2] [F03, F05, F06-OS1.5] [F03, F06-OP1.2]
(3)[F06-OS1.2] [F03, F05, F06-OS1.5] [F03, F06-OP1.2]
(4)(a), (b) [F06, F12-OS1.2] [F03, F05, F06, F10, F12- OS1.5] (a), (b) [F03, F06, F12-OP1.2] (c) [F03, F06-OS1.2] [F03, F05, F06-OS1.5] (c) [F03, F06-OP1.2]
3.3.1.5. Egress DoorwaysN/A
(1)[F10, F05-OS1.5]
(2)[F10, F05-OS1.5]
(3)[F10-OS3.7]
3.3.1.6. Travel DistanceN/A
(1)[F10, F05-OS1.5]
3.3.1.7. Protection on Floor Areas with a Barrier-Free Path of TravelN/A
(1)[F10-OS3.7] (a) [F06-OS1.5]
(1.1)[F05, F10-OS1.5]
(1.2)[F02-OP1.2] [F02-OS1.2]
(2)[F03-OS1.2] [F06-OS1.5]
(4)(a), (b) [F10, F73-OS1.5] (c), (d) [F10-OS1.5]
3.3.1.8. Headroom and Protruding ObjectsN/A
(2)[F30, F73-OS3.1]
3.3.1.9. CorridorsN/A
(1)[F10, F12-OS3.7]
(2)[F10, F12-OS3.7]
(3)[F10, F12-OS3.7]
(4)(a) [F10, F12-OS3.7] (b) [F06-OS1.2] [F05, F06-OS1.5]
(6)[F10-OS3.7]
(7)[F10-OS3.7]
(8)[F10-OS1.5]
(9)[F10-OS1.5] [F10-OS3.7]
(10)[F10-OS1.5] [F10-OS3.7]
(11)[F10-OS1.5] [F10-OS3.7]
(12)[F10-OS3.7]
3.3.1.11. Door SwingN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7]
(4)[F10-OS3.7]
3.3.1.12. Sliding DoorsN/A
(1)(b) [F10-OS3.7]
3.3.1.13. Doors and Door HardwareN/A
(1)(a), (b) [F10, F12-OS3.7] (c) [F30-OS3.1] [F10-OS3.7] (d) [F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7]
(4)[F10-OS3.7]
(5)[F10-OS3.7] [F73-OA1]
(8)[F12-OS3.7]
(9)[F12-OS3.7]
(10)[F12-OS3.7]
3.3.1.16. Tapered Treads in a Curved FlightN/A
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
3.3.1.17. Capacity of Access to ExitsN/A
(2)[F10-OS3.7]
(3)[F10-OS3.7]
(4)[F10-OS3.7]
(6)[F10-OS3.7]
3.3.1.18. GuardsN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
(2.1)[F30-OS3.1]
(3)[F30-OS3.1]
(4)[F30-OS3.1]
3.3.1.19. Tactile Walking Surface IndicatorsN/A
(1)[F30-OS3.1]
3.3.1.20. Transparent Doors and PanelsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F20-OS3.1]
(4)[F30-OS3.1] [F10-OS3.7]
(6)[F30-OS3.1] [F10-OS3.7]
(8)[F30-OS3.1]
3.3.1.21. Exhaust Ventilation and Explosion VentingN/A
(1)[F01-OS1.1]
(2)[F02-OP1.2] [F02-OS1.2]
(3)[F02-OP1.3] Applies to the requirement for explosion- relief devices and vents. [F02-OS1.3] Applies to the requirement for explosion- relief devices and vents.
3.3.1.22. Janitors’ RoomsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(3)[F02-OP1.2] [F02-OS1.2]
3.3.1.23. Common Laundry RoomsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(3)[F02-OP1.2] [F02-OS1.2]
3.3.1.24. ObstructionsN/A
(1)[F10-OS3.7]
3.3.1.25. Signs in Service SpacesN/A
(1)[F10-OS3.7]
3.3.1.26. Welding and CuttingN/A
(1)[F02, F03-OP1.2] [F02, F03-OS1.2]
3.3.2.2. Fire SeparationsN/A
(1)[F03-OS1.2]
(3)[F03-OS1.2] Applies where space under tiers of seats is sprinklered. [F03-OS1.2] Applies where space under tiers of seats is not sprinklered.
(4)[F03-OS1.2] [F03-OP1.2]
(5)[F03-OS1.2] [F03-OP1.2]
(7)[F03-OS1.2] [F03-OP1.2]
(8)[F03-OS1.2]
(9)[F03-OS1.2] [F03-OP1.2]
3.3.2.4. Fixed SeatsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(3)[F10-OS3.7]
3.3.2.4. AislesN/A
(3)[F10-OS3.7]
(4)[F10-OS3.7]
(5)[F10-OS3.7]
(7)[F10-OS3.7]
(8)[F10-OS3.7]
(9)[F10-OS3.7]
(10)[F10-OS3.7]
(11)[F10-OS3.7]
(12)[F10-OS3.7]
(13)[F03-OS1.2] [F10-OS3.7]
(14)[F03-OS1.2] [F10-OS3.7]
(15)[F10-OS3.7]
(16)[F10-OS3.7]
(17)[F10-OS3.7]
(18)[F30-OS3.1] [F10-OS3.7]
(19)[F30-OS3.1] [F10-OS3.7]
(20)[F30-OS3.1] [F10-OS3.7]
(21)[F30-OS3.1] [F10-OS3.7]
(22)[F30-OS3.1] [F10-OS3.7]
(23)[F30-OS3.1] [F10-OS3.7]
(24)[F30-OS3.1] [F10-OS3.7]
(25)[F30-OS3.1] [F10-OS3.7]
(26)[F30-OS3.1] [F10-OS3.7]
3.3.2.6. CorridorsN/A
(1)[F06-OS1.2] [F03, F05, F06-OS1.5] [F03, F06-OP1.2]
(3)[F06-OS1.2] [F03, F05, F06-OS1.5] [F03, F06-OP1.2]
(4)[F10-OS3.7]
3.3.2.7. DoorsN/A
(1)[F10-OS3.7]
3.3.2.8. Fixed Bench-Type Seats without ArmsN/A
(1)[F10-OS3.7] [F10-OS3.7]
3.3.2.10. Handrails in Aisles with StepsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
3.3.2.11. Outdoor Places of AssemblyN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7]
(5)[F10-OS3.7]
3.3.2.12. BleachersN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1]
3.3.2.13. LibrariesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F02-OP1.2] [F02-OS1.2]
3.3.2.14. Stages for Theatrical PerformancesN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
(5)[F02, F06-OS1.2] [F06-OS1.5] [F02, F06-OP1.2]
(6)[F03-OP1.2] [F03-OS1.2, OS1.5]
3.3.2.15. Risers for StairsN/A
(1)[F30-OS3.1]
3.3.2.16. Storage RoomsN/A
(1)[F12-OP1.2] [F12-OS1.2]
3.3.2.17. Safety GlazingN/A
(1)[F20, F30-OS3.1]
(2)[F20, F30-OS3.1]
3.3.3.2. Fire SeparationsN/A
(1)[F03-OS1.2] [F44-OS3.4]
(2)[F03-OS1.2] [F03-OP1.2]
(3)[F03-OS1.5] [F03-OP1.2]
3.3.3.3. CorridorsN/A
(1)[F10-OS3.7]
(2)[F10, F12-OS3.7]
(3)[F10-OS1.5] [F10, F12-OS3.7]
(4)(a) [F10-OS3.7] (b) [F10, F12-OS3.7]
3.3.3.4. Doorway WidthN/A
(1)[F10, F12-OS3.7]
3.3.3.5. Hospitals and Long-Term Care HomesN/A
(2)[F06-OS1.2] [F05, F06-OS1.5] [F06-OP1.2]
(4)[F03, F06-OP1.2] [F05, F06-OS1.2] [F06-OS1.5]
(7)[F10-OS1.5]
(8)[F10-OS1.5]
(9)[F03, F05-OS1.2] [F06-OS1.5]
(12)[F03, F05-OS1.2] [F06-OS1.5]
3.3.3.6. Protection for Special Care and Treatment FacilitiesN/A
(1)[F03-OS1.2]
3.3.3.7. Contained Use AreasN/A
(2)[F03, F06-OS1.2] [F06-OS1.5] [F03, F06-OP1.2]
(3)[F02, F06-OS1.2] [F06-OS1.5] [F02, F06-OP1.2]
(4)[F02, F06-OS1.2] [F06-OS1.5] [F02, F06-OP1.2]
(5)[F10-OS3.7]
3.3.3.8. HandrailsN/A
(1)[F30-OS3.1] [F73-OA1]
3.3.4.2. Fire SeparationsN/A
(1)[F03, F06-OS1.2] [F05, F06-OS1.5] [F03, F06-OP1.2]
(4)[F44-OS1.1] [F02, F03-OS1.2] (a), (b) [F02, F03-OP1.2]
(5)[F01-OS1.1] [F03-OS1.2] [F44-OS3.4] (a) [F03-OP1.2]
3.3.4.3. Storage RoomsN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(4)[F12-OP1.2] [F12-OS1.2]
3.3.4.4. Egress from Dwelling UnitsN/A
(2)[F05, F10-OS3.7]
(3)[F10-OS3.7]
(4)[F05-OS1.2, OS1.5]
(5)[F05, F10-OS3.7]
(6)[F05, F10-OS3.7]
(7)[F05-OS1.2] [F10-OS3.7]
(8)[F05, F10-OS3.7]
3.3.4.5. Automatic Locking ProhibitionN/A
(1)[F10-OS3.7]
3.3.4.8. Window ProtectionN/A
(1)[F30-OS3.1]
3.3.4.9. Stud Wall ReinforcementN/A
(1)[F74-OA2]
3.3.4.10. Resistance to Forced EntryN/A
(1)[F4.1-OS3.1]
3.3.4.11. Retirement HomesN/A
(2)[F06-OS1.2] [F05, F06-OS1.5] [F06-OP1.2]
(4)[F03, F06-OP1.2] [F05, F06-OS1.2] [F06-OS1.5]
(6)[F05-OS1.2] [F06-OS1.5]
(7)[F10-OS1.5]
(8)[F10-OS1.5]
(9)[F03-OS1.2] [F03-OP1.2]
(10)[F10-OS3.7]
(11)[F10, F12-OS3.7]
(12)[F11, F12-OS3.7]
3.3.5.2. Fire Extinguishing SystemsN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.3.5.3. BasementsN/A
(1)[F12-OP1.2] [F01-OS1.1] [F12-OS1.2, OS1.5]
(2)[F06-OS1.2] [F05, F06-OS1.5,] Applies to the separation of exits from the remainder of the building. [F06-OS1.2, OS1.5] Applies to the separation of entrances to basements and to rooms containing building services from the remainder of the building. [F06-OP1.2] Applies to the separation of exits from the remainder of the building. [F06-OP1.2] Applies to the separation of entrances from the remainder of the building.
(3)[F44-OS1.1]
3.3.5.4. Repair and Storage GaragesN/A
(2)[F30-OS3.1] [F10, F12-OS3.7]
(5)[F30-OS3.1]
(6)[F30-OS3.1]
(8)[F02-OP1.2] [F02-OS1.2]
3.3.5.5. Repair Garage SeparationN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.3.5.6. Storage Garage SeparationN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.3.5.7. VestibulesN/A
(4)[F44-OS1.1] [F44-OS3.4]
3.3.5.11. Toe-Boards RequiredN/A
(1)[F30-OS3.1]
3.3.6.2. Storage of Dangerous GoodsN/A
(1)[F03-OS1.2] [F03-OP1.2]
(2)[F03-OS1.2] [F03-OP1.2]
(3)[F01, F02, F03, F81-OS1.1, OS1.2] [F01, F02, F03, F81-OP1.1, OP1.2]
3.3.6.3. Indoor Storage of Compressed GasesN/A
(1)(a) [F03-OS1.2] [F44-OS1.1] (a) [F03-OP1.2] (a) [F44-OS1.2, OS1.5, OS1.1] Applies to gas-tight fire separations. (b) [F12-OS1.2] [F01-OS1.1] [F02-OS1.3] (b) [F02-OP1.3] (c) [F12-OS1.1] (e) [F02-OS1.1] (e) [F02-OP1.1] (f) (g) [F01-OS1.1] (f) (g) [F01-OP1.1]
(2)[F44-OS1.1]
(3)(a) [F03-OS1.2] [F44-OS1.1] (a) [F03-OP1.2] (a) [F44- OS1.2, OS1.5, OS1.1] Applies to gas-tight fire separations. (b) [F12-OS1.2] [F02-OS1.3] (b) [F02-OP1.3]
(4)[F44-OS1.1] [F44-OP1.1] [F50-OH1.1]
(5)[F44, F01-OS1.1] [F44, F01-OP1.1]
3.3.6.4. Storage and Dispensing Rooms for Flammable Liquids and Combustible LiquidsN/A
(1)[F03-OS1.2] [F03-OP1.2]
(2)[F02-OS1.3] [F02-OP1.3]
(4)[F02-OS1.3] [F02-OP1.3]
(6)[F10-OS1.5]
(7)[F05, F10-OS1.5]
(8)[F10-OS1.5]
3.3.6.5. Tire StorageN/A
(1)[F03-OS1.2] [F03-OP1.2]
3.3.6.6. Ammonium Nitrate StorageN/A
(1)(a) [F01-OS1.1] [F02, F12-OS1.2] (a) [F01-OP1.1] [F02, F12-OP1.2] (b) (c) [F03-OS1.2] [F01-OS1.1] (b) (c) [F03-OP1.2] [F01-OP1.1] (c) [F44-OH5] (d) [F01-OS1.1] [F02-OS1.2] (d) [F43-OS3.4] (e) [F01, F81-OS1.1] (f) [F12, F02-OS1.1] (f) [F12, F02-OP1.2]
3.3.6.7. Flooring MaterialN/A
(1)[F43-OS3.4] [F44-OH5] [F01-OS1.1]
3.3.6.8. Fire Separations in Process PlantsN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.3.6.9. Basements and PitsN/A
(1)[F01-OS1.1] [F01-OP1.1]
3.4.1.2. Separation of ExitsN/A
(1)[F05, F06, F10, F12-OS3.7] [F06, F12-OP1.2] [F06, F12-OS1.2, OS1.5]
(2)[F10-OS3.7]
3.4.1.5. Exterior Exit PassagewaysN/A
(1)[F10-OS3.7]
3.4.1.6. Restricted Use of Horizontal ExitsN/A
(1)[F10-OS3.7]
(2)[F05, F10-OS3.7]
3.4.1.7. Slide EscapesN/A
(1)[F10-OS3.7]
3.4.1.9. Mirrors near ExitsN/A
(1)[F30-OS3.1] [F10-OS3.7]
3.4.1.10. Combustible Glazing in ExitsN/A
(1)[F03, F06-OP1.2] [F05, F06-OS1.2] [F06-OS1.5]
3.4.1.11. Exterior Stairway for Nursing HomeN/A
(1)[F10-OS3.1, OS3.7]
3.4.2.1. Minimum Number of ExitsN/A
(1)[F05, F06, F10, F12-OS3.7] [F06, F12-OP1.2] [F06, F12-OS1.2]
(3)[F10-OS3.7]
3.4.2.2. Means of Egress from ExitingN/A
(1)[F05-OS1.5]
3.4.2.3. Distance Between ExitsN/A
(1)[F05, F10-OS1.5]
(4)[F10-OS3.7]
3.4.2.4. Travel DistanceN/A
(3)[F10-OS3.7]
3.4.2.5. Location of ExitsN/A
(1)[F10-OS3.7]
(3)[F10-OS3.7]
3.4.2.6. Principal EntranceN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
3.4.3.1. Exit Width Based on Occupant LoadN/A
(2)[F10-OS3.7]
3.4.3.2. Exit WidthN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7]
(6)[F10-OS3.7]
(7)[F10-OS3.7]
(8)[F12-OP1.2] [F12-OS1.2] [F30-OS3.1] [F10, F12-OS3.7]
3.4.3.3. Exit Width ReductionN/A
(1)[F12-OS1.2] [F30-OS3.1] [F10, F12-OS3.7] [F12-OP1.2]
(2)[F12-OS1.2] [F10, F12-OS3.7] [F12-OP1.2]
(3)[F12-OS1.2] [F10, F12-OS3.7] [F12-OP1.2]
(4)[F12-OS1.2] [F10, F12-OS3.7] [F12-OP1.2]
(5)[F12-OS1.2] [F10, F12-OS3.7] [F12-OP1.2]
3.4.3.4. Headroom ClearanceN/A
(1)[F12-OP1.2] [F12-OS1.2] [F30-OS3.1] [F10, F12-OS3.7]
(4)[F12-OP1.2] [F12-OS1.2] [F30-OS3.1] [F10, F12-OS3.7]
(5)[F12-OP1.2] [F12-OS1.2] [F30-OS3.1] [F10, F12-OS3.7]
3.4.4.1. Fire-resistance rating of Exit SeparationsN/A
(1)[F03, F06-OS1.2] [F05, F06-OS1.5] [F03, F06-OP1.2]
3.4.4.2. Exits Through LobbiesN/A
(1)[F05, F06-OS1.5]
(2)[F05, F06, F10, F12-OS1.5]
3.4.4.3. Exterior Passageway ExceptionsN/A
(1)[F05, F06, F10-OS1.5]
3.4.4.4. Integrity of ExitsN/A
(1)[F03, F06-OS1.2] [F05, F06-OS1.5] [F03, F06-OP1.2]
(2)[F06-OS1.2] [F05, F06-OS1.5] [F06-OP1.2]
(3)[F06-OS1.2] [F05, F06-OS1.5] [F06-OP1.2]
(4)[F06-OS1.2] [F05, F06-OS1.5] [F43-OS3.7] [F06-OP1.2]
(5)[F03, F06-OP1.2] [F03, F06-OS1.2] [F05, F06-OS1.5]
(6)[F12-OS1.2] [F05, F10, F12-OS1.5] [F30-OS3.1] [F31-OS3.2] [F32-OS3.3] [F43-OS3.4] [F10, F12-OS3.7] [F12-OP1.2]
(7)[F06-OS1.2] [F05, F06-OS1.5] [F06-OP1.2] [F43-OS3.7]
(8)[F06-OS1.2] [F05, F06-OS1.5] [F06-OP1.2]
(9)[F06-OS1.2] [F05, F06-OS1.5] [F06-OP1.2]
(10)[F81-OS1.5] [F81-OS3.7] [F81-OP1.2]
3.4.5.1. Exit SignageN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10, F81-OS3.7]
(4)[F10, F81-OS3.7]
(4.1)[F10-OS3.7]
(5)[F10-OS3.7]
(6)[F10-OS3.7]
(7)[F10-OS3.7]
(8)[F10-OS3.7]
3.4.5.2. Exit Signs with Tactile InformationN/A
(1)[F10-OS3.7]
3.4.5.3. Signs for Stairs and Ramps at Exit LevelN/A
(1)[F10-OS3.7]
3.4.6.1. Surface Finish of Ramps and StairsN/A
(1)(a), (b) [F30-OS3.1] [F10-OS3.7]
(1.1)[F73-OA1]
(2)[F12-OS1.2, OS1.5] [F30-OS3.1] [F10, F12-OS3.7] [F12-OP1.2]
3.4.6.2. Minimum Number of RisersN/A
(1)[F30-OS3.1]
3.4.6.3. Maximum Vertical Rise of Stair Flights and Required LandingsN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7] [F30-OS3.1]
(3)[F10, F12-OS3.7] [F30-OS3.1]
3.4.6.4. Dimensions of LandingsN/A
(1)[F30-OS3.1] [F10, F12-OS3.7] [F12-OP1.2] [F12-OS1.2, OS1.5]
(2)[F30-OS3.1] [F10, F12-OS3.7] [F12-OP1.2] [F12-OS1.2, OS1.5]
(4)[F30-OS3.1] [F10, F12-OS3.7]
(5)[F30-OS3.1] [F10, F12-OS3.7]
3.4.6.5. HandrailsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1] [F10-OS3.7]
(7)[F30-OS3.1] [F10-OS3.7]
(9)[F30-OS3.1] [F10-OS3.7]
(10)[F30-OS3.1] [F10-OS3.7] [F73-OA1]
(11)[F30-OS3.1] [F10-OS3.7]
(12)[F30-OS3.1] [F10-OS3.7] [F73-OA1]
(13)[F30-OS3.1] [F10-OS3.7]
(15)[F30-OS3.1] [F10-OS3.7]
(16)[F30-OS3.1] [F10-OS3.7] [F73-OA1]
3.4.6.6. GuardsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1]
(5.1)[F30-OS3.1]
(6)[F30-OS3.1]
(7)[F30-OS3.1]
3.4.6.7. Ramp SlopeN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F10-OS3.7] [F30-OS3.1]
3.4.6.8. Treads and RisersN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7] [F73-OA1]
(4)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1] [F10-OS3.7]
(6)[F30-OS3.1] [F10-OS3.7]
(7)[F30-OS3.1] [F10-OS3.7]
(8)[F30-OS3.1]
(9)[F10-OS3.7] [F30-OS3.1]
(10)[F30-OS3.1]
3.4.6.9. Curved Flights in ExitsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
3.4.6.10. Horizontal ExitsN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(4)[F10, F73-OS3.7]
(5)[F10-OS3.7]
(7)[F10-OS1.5]
3.4.6.11. DoorsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7] Applies to portion of Code text: “No exit door shall open directly onto a step...” [F10, F81-OS3.7] Applies where there is a danger of blockage from ice or snow.
(4)[F10-OS3.7]
(5)[F10, F12-OS3.7]
(6)[F10-OS3.7]
3.4.6.12. Direction of Door SwingN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
3.4.6.13. Self-Closing DevicesN/A
(1)[F06-OS1.2] [F05, F06-OS1.5] [F03, F06-OP1.2]
3.4.6.14. Sliding DoorsN/A
(2)[F12-OS3.7]
3.4.6.15. Revolving DoorsN/A
(1)(a) [F30-OS3.1] [F10-OS3.7] (b) [F10, F12-OS3.7] (c) [F10-OS3.7] (d) [F30-OS3.1] [F10-OS3.7] (e) [F20-OS3.1]
(2)[F10-OS3.7]
(3)(a), (b), (d), (e) [F20, F30-OS3.1] [F10, F81-OS3.7]
3.4.6.16. Door Release HardwareN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7]
(4)[F10-OS3.7]
(5)[F10, F81-OS3.7]
(7)[F10-OS3.7] [F73-OA1]
(10)[F02-OS1.2] [F10-OS3.7]
3.4.6.18. Emergency Crossover Access to Floor AreasN/A
(1)[F10-OS3.7]
(3)[F10-OS3.7]
(4)[F10, F12-OS3.7] [F12-OP1.2] [F12-OS1.2, OS1.5]
(5)[F10-OS3.7]
3.4.6.19. Floor Numbering and Identification of Stair ShaftsN/A
(1)[F12-OS1.2] [F73-OA1] [F12-OP1.2] [F12-OS1.2] [F10, F12,F73-OS3.7]
(2)[F12-OP1.2] [F12-OP1.2] [F10, F12,F73-OS3.7]
3.4.7.1. ScopeN/A
(1)[F10, F12-OS3.7]
(2)[F12-OS1.2] [F10-OS1.5] [F30-OS3.1] [F10-OS3.7]
3.4.7.2. Fire Escape ConstructionN/A
(1)[F06-OS1.2] [F05-OS1.5] Applies to the combustibility of materials used in the construction of fire escapes. [F20-OS3.1] [F10, F12-OS3.7] Applies to the type and construction of fire escapes. [F20-OS2.1] Applies to the type and construction of fire escapes.
3.4.7.3. Access to Fire EscapesN/A
(1)[F10-OS3.7] Applies to portion of Code text: “Access to fire escapes shall be from corridors through doors at floor level...”
(2)[F30-OS3.1] [F10-OS3.7]
3.4.7.4. Protection of Fire EscapesN/A
(1)[F05, F06-OS1.5]
3.4.7.5. StairsN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7] Applies to the reduction in width permitted under certain conditions.
(4)[F30-OS3.1] [F10-OS3.7]
3.4.7.6. Guards and RailingsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1]
(5)[F30-OS3.1]
3.5.2.1. Required ElevatorN/A
(1)[F12-OS3.7] [F73-OA1]
(2)[F82-OS3.1, OS3.3, OS3.6]
3.5.2.2. Barrier-Free DesignN/A
(1)[F73-OA1]
3.5.3.1. Fire Separations for Elevator HoistwaysN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.5.3.2. Vertical Service Spaces for DumbwaitersN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.5.3.3. Fire Separations for Elevator Machine RoomsN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.5.4.1. Elevator Car DimensionsN/A
(1)[F12-OS3.7]
(3)[F12-OS3.7]
3.6.1.4. Storage Use ProhibitionN/A
(1)[F01-OS1.1] [F02-OS1.2]
3.6.1.5. Appliances Installed Outside a BuildingN/A
(1)[F03-OS1.2] (a) [F03-OP3.1] (b) [F03-OP1.2]
3.6.1.6. Fixed Access LaddersN/A
(1)[F20-OS2.1] [F30-OS3.1]
3.6.2.1. Fire Separations around Service RoomsN/A
(1)[F03-OP1.2, OP1.4] [F03-OS1.2, OS1.4]
(3)[F01-OP1.1] [F03-OP1.2] [F01-OS1.1] [F03-OS1.2]
(4)[F03-OP1.2, OP1.4] [F03-OS1.2, OS1.4]
(5)[F03-OP1.2, OP1.4] [F03-OS1.2, OS1.4]
(6)[F03-OP1.2, OP1.4] [F03-OS1.2, OS1.4]
(7)[F03-OP1.2, OP1.4] [F03-OS1.2, OS1.4]
3.6.2.2. Service Rooms under ExitsN/A
(1)[F02-OS1.2] [F05, F06-OS3.7]
3.6.2.4. Incinerator RoomsN/A
(1)[F02-OS1.2]
3.6.2.5. Combustible Refuse StorageN/A
(1)[F03-OP1.2] [F03-OS1.2]
3.6.2.6. Door Swing for Service RoomsN/A
(1)[F10-OS1.5] Applies to portion of Code text: “A swing- type door from a service room containing a boiler or incinerator shall swing outward from the room ...” [F30-OS3.1] Applies to portion of Code text: “A swing- type door from a service room containing a boiler or incinerator shall swing ... inward if the door opens onto corridor or any room used for an assembly occupancy.”
3.6.2.7. Electrical Equipment VaultsN/A
(1)[F03-OP1.2, OP1.4] [F03-OS1.2, OS1.4]
(2)[F02-OP1.2] [F03-OP1.4] [F02-OS1.2] [F03-OS1.4] [F11-OS1.5]
(3)[F02, F04-OS1.3] [F02, F04-OP1.3]
(4)[F02, F04-OS1.3] [F02, F04-OP1.3]
(5)[F03-OP1.2, OP1.4] [F03-OS1.2, OS1.4]
(7)[F32-OS3.3] [F34-OS4.1]
(8)[F02-OS1.2, OS1.3] [F02-OP1.2, OP1.3]
(9)[F81-OS1.1]
(10)[F81-OS1.1]
(11)[F81-OS1.1]
(12)[F81-OS1.1] (b) [F30-OS3.1] (d) [F03-OS1.2] (d) [F03-OP1.2]
(13)[F81-OS1.1] [F34-OS3.3] [F81-OP1.1]
(14)[F01-OS1.1] [F03-OS1.2] [F01-OP1.1] [F03-OP1.2]
(15)[F01-OS1.1] [F03-OS1.2] [F01-OP1.1] [F03-OP1.2]
(16)[F02-OS1.1 OS1.3] [F02-OP1.1, OP1.3]
(17)[F01-OS1.1] [F01-OP1.1]
(18)(a) [F30-OS3.1] [F10-OS3.7] (b) (c) [F32-OS3.3]
3.6.2.8. Emergency Power InstallationsN/A
(1)[F03, F06-OS1.2] [F03-OS1.4] [F06-OS1.5] [F03, F06-OP1.2] [F03-OP1.4]
3.6.2.9. Storage of Oxygen ContainersN/A
(1)[F01-OS1.1] [F03-OS1.2] [F43-OS3.4] [F01-OP1.1] [F03-OP1.2]
3.6.3.1. Fire Separations for Vertical Service SpacesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
(5)[F03-OP1.2] [F03-OS1.2]
3.6.3.2. Foamed Plastic ProtectionN/A
(1)[F02-OS1.2]
3.6.3.3. Linen and Refuse ChutesN/A
(1)(a), (b), (c) [F41-OH2.4, OH2.5] (d), (e) [F02-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OS1.2]
(4)(a) [F41-OH2.4, OH2.5] (b) [F03-OS1.2]
(5)(a) [F03, F81-OP1.2] (a) [F03, F81-OS1.2] (a) [F41, F81-OH2.4, OH2.5] (b) [F03-OP1.2] (b) [F03-OS1.2] (c) [F01, F02-OP1.2] (c) [F01, F02-OS1.2] (d) [F06-OS1.2] [F05, F06-OS1.5] (d) [F06-OP1.2]
(6)[F02-OP1.2] [F02-OS1.2]
(7)[F03-OP1.2] [F03-OS1.2]
(8)[F02-OS1.2] [F41-OH2.4, OH2.5]
(9)[F03-OP1.2] [F03-OS1.2]
(10)[F41-OH2.4, OH2.5] Applies to portion of Code text: “The room or bin into which a refuse chute discharges shall be ...impervious to moisture and be equipped with a water connection and floor drain for washing-down purposes:” [F03, F81-OS1.2] Applies to portion of Code text: “The room or bin into which a refuse chute discharges shall be of sufficient size to contain the refuse between normal intervals of emptying ...” [F41, F81-OH2.4, OH2.5] Applies to portion of Code text: “The room or bin into which a refuse chute discharges shall be of sufficient size to contain the refuse between normal intervals of emptying ...”
(11)[F01, F02-OS1.2]
3.6.3.4. Exhaust Duct Negative PressureN/A
(1)[F03-OS1.2]
3.6.3.5. Grease Duct EnclosuresN/A
(1)[F02, F03-OS1.2] [F03, F02-OP1.2]
(2)[F02, F03-OS1.2] [F03, F02-OP1.2]
3.6.4.2. Fire Separations for Horizontal Service SpacesN/A
(2)[F03-OP1.2] [F03-OS1.2]
3.6.4.3. Plenum RequirementsN/A
(1)[F02-OS1.2]
(2)[F03-OP1.2, OP1.3] [F03-OS1.2, OS1.3]
3.6.4.4. Attic or Roof Space AccessN/A
(1)[F01, F02, F12-OP1.2] [F01, F02, F12-OS1.2]
3.6.4.5. Horizontal Service Space AccessN/A
(1)[F01, F02, F12-OP1.2] [F01, F02, F12-OS1.2]
3.6.4.6. Crawl Space AccessN/A
(1)[F01, F02, F12-OP1.2] [F01, F02, F12-OS1.2]
3.6.5.1. Duct MaterialN/A
(1)[F01, F02-OS1.2]
(2)[F02-OS1.2]
(4)[F02-OS1.2]
(5)[F02-OS1.2]
3.6.5.2. Vibration Isolation ConnectorsN/A
(1)[F01, F02-OS1.2]
(2)[F02-OS1.2]
3.6.5.3. TapeN/A
(1)[F02-OS1.2]
3.6.5.4. Coverings, Lining, Adhesives and InsulationN/A
(1)[F02-OS1.2]
(2)[F02-OS1.2]
(3)[F02-OS1.2]
(4)[F02-OS1.2]
(5)[F02-OS1.2]
(6)[F02-OS1.2]
(7)[F01, F02-OS1.2]
3.6.5.5. Insulation and CoveringsN/A
(1)[F01, F02-OS1.2]
(2)[F02-OS1.2]
(3)[F02-OS1.2]
(4)[F02-OS1.2]
3.6.5.6. Clearance of Ducts and PlenumsN/A
(2)[F02-OS1.2]
(3)[F02-OS1.2]
(4)[F02-OS1.2]
(5)[F02-OS1.2]
3.6.5.7. Supply, Return, Intake and Exhaust-Air OpeningsN/A
(1)[F02-OS1.2]
3.6.5.8. Return-Air SystemN/A
(1)[F02-OS1.2]
(2)[F01, F02-OS1.2]
(3)[F01, F02-OS1.2]
(4)[F01, F02-OS1.2]
3.7.1.1. Room and Space HeightN/A
(1)[F30-OS3.1]
3.7.1.3. Sleeping Areas in Group B and Child Care FacilitiesN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
(3)[F30-OS3.1]
3.7.1.4. Sleeping Areas in CampsN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
3.7.2.1. Window AreasN/A
(1)[F102-OH7]
(2)[F102-OH7]
(3)[F102-OH7]
3.7.3. ReservedN/A
3.7.4.1. Plumbing and Drainage SystemsN/A
(1)[F72-OH2.1] [F70-OH2.2] [F71-OH2.3]
(2)[F72-OH2.1]
3.7.4.2. Plumbing Fixtures, GeneralN/A
(3)[F72-OH2.1] Applies to portion of Code text: “water closets shall be provided”
(5)[F71-OH2.3]
(7)[F74-OA2]
(10)[F30-OS3.1]
(11)[F71-OH2.3]
3.7.4.3. Plumbing Fixtures for Assembly OccupanciesN/A
(1)[F72-OH2.1]
(2)[F72-OH2.1]
(3)[F72-OH2.1]
(4)[F72-OH2.1]
(5)[F72-OH2.1]
(6)[F72-OH2.1] [F71-OH2.3]
(7)[F72-OH2.1]
(8)[F72-OH2.1] (b) [F101-OH6]
(10)[F72-OH2.1]
(11)[F72-OH2.1]
(12)[F72-OH2.1]
(13)[F72-OH2.1]
(14)[F72-OH2.1]
(15)[F72-OH2.1]
(16)[F72-OH2.1]
3.7.4.4. Plumbing Fixtures for Care or Detention OccupanciesN/A
(1)[F72-OH2.1] [F71-OH2.3]
(2)[F72-OH2.1] [F71-OH2.3]
(3)[F72-OH2.1]
3.7.4.5. Plumbing Facilities for Dwelling UnitsN/A
(1)[F72-OH2.1] [F70-OH2.2] [F71-OH2.3]
3.7.4.6. Plumbing Fixtures for Other Residential OccupanciesN/A
(1)[F72-OH2.1]
(2)[F72-OH2.1]
(3)[F71-OH2.3]
(4)[F50-OH1.1] [F71-OH2.3]
3.7.4.7. Plumbing Fixtures for Business and Personal Service OccupanciesN/A
(1)[F72-OH2.1]
3.7.4.8. Plumbing Fixtures for Mercantile OccupanciesN/A
(1)[F72-OH2.1]
(2)[F72-OH2.1]
(4)[F72-OH2.1] [F71-OH2.3]
3.7.4.9. Plumbing Fixtures for Industrial OccupanciesN/A
(1)[F72-OH2.1]
3.7.4.10. GlazingN/A
(1)[F20-OS3.1]
3.7.4.11. Surface ProtectionN/A
(1)[F72-OH2.1] [F40-OH2.4]
(2)[F72-OH2.1] [F40-OH2.4]
3.7.4.12. Floor DrainsN/A
(1)[F30-OS3.1] [F40, F41-OH2.4, OH2.6]
3.7.4.13. Grab Bar InstallationN/A
(1)[F20-OS3.1]
3.7.4.14. Clearances for Water ClosetsN/A
(1)[F30-OS3.1]
3.7.4.15. PrivacyN/A
(1)[F101-OH6]
(2)[F101-OH6]
3.7.4.67. Water Temperature ControlN/A
(1)N/A
3.7.4.17. Drinking WaterN/A
(1)[F70-OH2.2]
3.7.4.18. PharmaciesN/A
(1)[F40-OH2.4]
3.7.4.19. Plumbing Fixtures for Mobile Home FacilitiesN/A
(1)[F72-OH2.1] [F71-OH2.3]
(2)[F72-OH2.1]
(3)[F71-OH2.3] Applies to the minimum number of laundry trays or similar facilities, and of bathtubs or showers for each sex.
3.7.5.1. Electrical SystemsN/A
(1)[F01-OS1.1] [F32-OS3.3] [F01-OP1.1]
3.7.5.2. Medical Gas PipingN/A
(1)[F43, F81, F82-OS3.4] (b) [F01, F02-OS1.1] (b) [F01, F02-OP1.1]
3.7.5.3. Shielding of X-Ray EquipmentN/A
(1)[F44-OS3.4]
3.7.6.2. Room FinishesN/A
(1)[F41-OH2.4]
(3)[F41-OH2.4]
3.7.6.3. Location of Plumbing FixturesN/A
(1)[F40-OH2.1, OH2.4]
(2)[F72-OH2.1] [F71-OH2.3]
3.7.6.4. Lavatories, Appliances and SinksN/A
(1)[F71-OH2.3]
(2)[F40-OH2.4]
3.7.6.5. Hot and Cold Water SupplyN/A
(1)(a) [F71-OH2.3] [F40-OH2.4] (b) [F70-OH2.2] (c) [F40-OH2.4]
3.7.6.6. Employee FacilitiesN/A
(1)[F41-OH2.4] [F101-OH6]
(2)[F71-OH2.3]
3.7.6.7. Sleeping QuartersN/A
(1)[F40-OH2.4]
3.8.1.2. EntrancesN/A
(1)[F73-OA1]
(2)[F73-OA1]
(5)[F73-OA1]
3.8.1.3. Barrier-Free Path of TravelN/A
(1)[F73-OA1]
(2)(a), (b) [F30-OS3.1] (a), (b) [F73-OA1] (c) [F30-OS3.1] (c) [F73-OA1] (d), (e) [F30-OS3.1] (d), (e) [F73-OA1]
(3)[F73-OA1]
(4)[F73-OA1]
(5)[F30-OS3.1]
(6)[F73-OA1]
3.8.1.4. Escalators and Moving WalksN/A
(1)[F73-OA1]
(2)[F73-OA1]
(3)[F73-OA1]
3.8.1.5. ControlsN/A
(1)[F10-OS3.7] [F73-OA1] [F74-OA2]
(2)[F74-OA2]
3.8.2.1. Areas Requiring Barrier-Free Path of TravelN/A
(1)[F73-OA1]
(4)[F74-OA2]
(5)[F73-OA1] [F74-OA2]
(6)[F74-OA2]
3.8.2.2. Barrier-Free Paths of Travel to Building Entrances, Exterior Passenger Loading Zones, and Access to Parking AreasN/A
(1)[F73-OA1]
(2)[F73-OA1]
(3)(a) [F74-OA2] (b) [F73-OA1] (c) [F74-OA2]
3.8.2.3. Washrooms Required to be Barrier-FreeN/A
(1)[F74-OA2]
(2)[F72-OH2.1] [F71-OH2.3]
(3)[F72-OH2.1] [F71-OH2.3]
(6)[F72-OH2.1] [F71-OH2.3] [F74-OA2]
3.8.2.4. HotelsN/A
(1)[F73-OA1] [F74-OA2]
(3)[F74-OA2]
(4)[F74-OA2]
(5)[F74-OA1]
(6)[F74-OA1]
(7)[F74-OA2]
(8)[F73-OA1]
3.8.3.1. Accessibility SignsN/A
(1)[F74-OA2]
(2)[F74-OA2]
(3)[F74-OA2]
(4)[F74-OA2]
(5)[F74-OA2]
(6)[F74-OA2]
(7)[F73-OA1] [F74-OA2]
(8)[F73-OA1] [F74-OA2]
3.8.3.2. Exterior WalksN/A
(1)[F73-OA1] [F30-OS3.1]
(3)[F73-OA1] [F30-OS3.1]
3.8.3.3. Doorways and DoorsN/A
(1)[F73-OA1]
(2)[F74-OA2]
(3)[F10-OS3.7] [F74-OA2]
(4)[F73-OA1]
(4.1)[F73-OA1]
(5)[F73-OA1]
(6)[F71-OH2.3] [F74-OA1]
(7)[F73-OA1]
(9)[F30-OS3.1] [F73-OA1]
(10)[F73-OA1]
(11)[F30-OS3.1] [F73-OA1]
(13)[F73-OA1]
(14)[F30-OS3.1]
(15)[F30-OS3.1]
(17)[F73-OA1]
(18)[F30-OS3.1]
(19)[F73-OA1]
3.8.3.4. RampsN/A
(1)(b), (c), (d), (e), (h) [F73-OA1] (b), (c), (d), (f), (g), (h) [F30-OS3.1] (e)(iii) [F30-OS3.1] (e)(v) [F30-OS3.1]
3.8.3.5. Passenger Elevating DevicesN/A
(1)[F30-OS3.1] [F10-OS3.7] [F73-OA1] [F74-OA2]
3.8.3.6. Wheelchair Spaces and Adaptive SeatingN/A
(1)[F30-OS3.1] Applies to portion of Code text: “... level, or level with removable seats ...” [F74-OA2] Applies to entire Sentence except for portion of Code text: “... without infringing on egress from any row of seating or any aisle requirements ...” (d) [F10-OS3.7]
(2)[F74-OA2]
(3)[F73-OA1]
3.8.3.7. Assistive Listening DevicesN/A
(1)[F11-OS3.7] [F74-OA2]
(2)[F74-OA2]
(3)[F74-OA2]
3.8.3.8. Water Closet Stalls and EnclosuresN/A
(1)[F72-OH2.1] [F74-OA2] (c) [F101-OH6] (c)(i) [F74-OA2] (c)(vii) [F36-OS3.6] (e) [F30-OS3.1] Applies to portion of Code text: “... be equipped with a coat hook ... projecting not more than 50 mm from the wall ...”
(2)[F74-OA2]
(3)[F72-OH2.1] [F74-OA2]
(4)[F72-OH2.1] [F74-OA2]
(5)[F30-OS3.1] [F74-OA2]
(6)[F30-OS3.1] [F74-OA2]
(7)[F20-OS3.1] [F74-OA2]
(8)[F20-OS3.1] [F74-OA2]
(9)[F74-OA2]
(10)[F74-OA2] (b)(vi) [F36-OS3.6] (d) [F30-OS3.1]
3.8.3.9. Water ClosetsN/A
(1)[F72-OH2.1] [F74-OA2]
3.8.3.10. UrinalsN/A
(1)[F74-OA2]
(2)[F74-OS2] (b) [F30-OS3.1]
(3)[F74-OA2] [F101-OH3.2]
(4)[F74-OA2]
3.8.3.11. Lavatories, Mirrors and Washroom AccessoriesN/A
(1)[F71-OH2.3] [F74-OA2] (d) [F31-OS3.2]
(2)[F74-OA2]
(5)[F74-OA2]
3.8.3.12. Universal WashroomsN/A
(1)[F72-OH2.1] [F71-OH2.3] [F74-OA2] (b) [F74-OA2] Applies to portion of Code text: “... a door that is capable of being locked from the inside ...” (b) [F10-OS3.7] (g) [F30-OS3.1] Applies to the requirement for a coat hook. (j) [F73-OA1] (k) [F131-OR2]
(2)[F36-OS3.6]
(4)[F20-OS3.1]
(5)[F74-OA2.1] [F71-OH2.3] (b) [F20-OS3.1]
3.8.3.13. Showers and BathtubsN/A
(1)[F74-OA2]
(2)[F74-OA2] (f)(iii) [F20-OS3.1]
(4)[F74-OA2]
(5)[F74-OA2] [F71-OH2.3] (a) [F73-OA1] (b) [F10-OS3.7] [F74-OA2] (g) [F74-OA2]
(7)[F74-OA2]
(8)[F74-OA2]
3.8.3.14. Service CountersN/A
(1)[F74-OA2]
(2)[F74-OA2]
3.8.3.15. Shelves or Counters for TelephonesN/A
(1)[F74-OA2]
(2)[F74-OA2]
(3)[F74-OA2]
(4)[F74-OA2]
3.8.3.16. Drinking FountainsN/A
(1)[F74-OA2]
(2)[F74-OA2]
(3)[F74-OA2]
3.8.3.16.A. Water-Bottle Filling StationN/A
(1)[F74-OA2]
(2)[F74-OA2]
3.8.3.17. PlatformsN/A
(1)[F30-OS3.1]
3.8.3.18. Tactile Attention IndicatorsN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
3.9.2.1. Flame-Spread RatingN/A
(1)[F02-OP1.2] [F02-OS1.2]
3.9.3.1. Building AreasN/A
(1)[F02-OP1.1] [F02-OS1.1]
3.9.3.2. Spatial SeparationsN/A
(1)[F03-OP3.1] [F03-OS1.1]
(2)[F03-OP3.1] [F03-OS1.1]
3.9.3.3. Fire Alarm SystemsN/A
(1)[F12-OS1.2, OS1.5]
3.9.3.4. Provisions for FirefightingN/A
(1)[F12-OP1.2] [F12-OS1.2, OS1.5]
3.9.3.5. Portable Fire ExtinguishersN/A
(1)[F02, F12, F81-OP1.2] [F02, F12, F81-OS1.2]
3.9.3.7. Fuel-Fired AppliancesN/A
(1)[F05-OS1.5] [F43-OS3.7]
(2)[F03-OP1.2, OP1.4] [F03-OS1.2, OS1.4]
3.10.2.1. Occupancy ClassificationN/A
(1)[F02, F03-OS1.2] [F10-OS1.5] Applies to portion of Code text: “(b) shall not contain a Group F, Division 1 occupancy.”
3.10.2.3. Structural Fire ProtectionN/A
(2)[F02, F03, F04-OP1.2] [F02, F04-OP1.3] [F02, F03, F04-OS1.2] [F02, F04-OS1.3]
3.10.2.4. Safety Requirements Within Floor AreasN/A
(5)[F10-OS1.5] [F30-OS3.1, OS3.7]
(6)[F10-OS1.5] [F30-OS3.1, OS3.7]
(7)[F10-OS1.5]
(8)[F10-OS1.5] [F30-OS3.1, OS3.7]
(9)[F02, F03-OS1.2]
(10)[F02, F03-OS1.2]
3.10.2.5. Exit RequirementsN/A
(2)[F10-OS3.7]
3.10.2.6. Service FacilitiesN/A
(2)[F03-OP1.2] [F03-OS1.2]
3.10.2.7. Sanitary FacilitiesN/A
(2)[F72-OH2.1] [F71-OH2.3]
3.10.3.2. Spatial SeparationsN/A
(2)[F03-OP3.1] [F03-OS1.1]
3.10.3.3. Fire Alarm SystemsN/A
(2)[F11-OS1.5]
3.10.3.4. Provisions for FirefightingN/A
(2)[F12-OP1.2] [F12-OS1.2]
(3)[F12-OP1.2] [F12-OS1.2]
3.10.4.3. Spatial SeparationsN/A
(3)[F03-OP3.1] [F03-OS1.1]
(4)[F03-OP3.1] [F03-OS1.1]
3.10.4.5. Provisions for FirefightingN/A
(2)[F12-OP1.2] [F12-OS1.2]
(3)[F12-OP1.2] [F12-OS1.2]
(5)[F02-OP1.2] [F02-OP3.1] [F02-OS1.2]
3.11.3.1. Construction RequirementsN/A
(4)[F30, F120-OS3.1]
(5)[F30, F120-OS3.1]
(6)[F30, F121-OS3.1]
(7)[F30, F121-OS3.1]
(8)[F30, F121-OS3.1]
(9)(a) [F12, F30, F121-OS3.1] [F123-OS3.7] (b), (c) [F122-OH2.3]
(10)[F30, F121-OS3.1]
(11)(a) [F123-OS3.7] (b), (c) [F122-OH2.3] (d) [F122-OH2.3] (d) [F30-OS3.1]
(12)[F30, F123-OS3.1]
(13)[F40-OH2.3] [F30-OS3.1]
(14)[F40-OH2.3] [F30-OS3.1]
(15)[F30-OS3.1]
(16)[F122-OH2.3] [F30-OS3.1]
(17)[F40, F41, F122-OH2.3]
(18)[F40, F122-OH2.3]
(19)[F30, F120-OS3.1] (b) [F74-OA2]
(20)[F40, F41, F122-OH2.3]
(21)[F123-OS3.1]
(22)[F123-OS3.1]
(23)[F122-OH2.3] [F34-OS3.1]
(24)[F30, F123-OS3.1]
(25)[F30, F120, F121-OS3.1]
(26)[F30, F120-OS3.1]
(27)[F30, F36, F120-OS3.1]
(28)[F30, F36, F120-OS3.1]
3.11.3.2. Barrier-Free Path of Travel for Outdoor Pool DeckN/A
(1)[F74-OA2]
3.11.3.3. Access into Public PoolsN/A
(1)[F74-OA2]
(2)[F74-OA2] [F121-OS3.1]
(3)[F74-OA2]
(4)[F74-OA2]
(5)[F30-OS3.1]
(6)[F20-OP2.1]
3.11.4.1. Diving Boards or PlatformsN/A
(2)[F30-OS3.1]
(3)[F30-OS3.1]
(4)[F30-OS3.1]
(6)[F30, F120-OS3.1]
(7)[F30, F120-OS3.1]
(8)[F30, F120-OS3.1]
(9)[F30, F120-OS3.1]
(10)[F30-OS3.1]
(11)[F30-OS3.1]
(12)[F30-OS3.1]
(13)[F30-OS3.1]
(14)[F30-OS3.1]
(15)[F30, F120-OS3.1]
(16)[F30, F34-OS3.1]
(17)[F30, F120-OS3.1]
3.11.5.1. Ramps into Public PoolsN/A
(1)[F74-OA2]
(2)[F30, F120-OS3.1] (d) [F40, F41-OH2.3, OH2.4]
(3)[F74-OA2] [F30, F120, F121-OS3.1] (b) [F41-OH2.3] (d) [F32-OS3.7]
(4)[F74-OA2] [F30, F120, F121-OS3.1] (c) [F34-OS3.7]
3.11.5.2. Public Pools in Group B, Division 2 or 3 Major OccupanciesN/A
(2)[F30, F120-OS3.1]
(3)[F30, F34-OS3.1]
(4)[F30, F34-OS3.1]
3.11.6.1. Construction RequirementsN/A
(3)[F40, F41-OH2.3, OH2.4]
(4)[F30, F121-OS3.1]
(5)[F30-OS3.1]
(6)[F122-OH2.3] [F123-OS3.1]
(7)[F30, F124-OS3.1]
(8)[F30, F123-OS3.1]
(9)[F30, F121-OS3.1]
3.11.7.1. Construction RequirementsN/A
(3)[F30, F121-OS3.1]
(4)[F30, F121-OS3.1]
(5)[F30, F123-OS3.1] [F122-OH2.3]
(6)[F30, F123-OS3.1]
(7)[F30, F120-OS3.1]
(8)[F30, F34-OS3.1]
(9)[F122-OH2.3]
(10)[F30, F123-OS3.1]
(11)[F12, F123-OS3.1]
3.11.8.1. Recirculation SystemsN/A
(1)[F122-OH2.3]
(3)[F46-OH2.2] [F122-OH2.3]
(5)[F122-OH2.3]
(6)[F40, F41-OH2.3] [F124-OS3.1]
(7)[F40, F41-OH2.3]
(8)[F122-OH2.3]
(9)[F122-OH2.3] [F43, F122-OS3.4]
(10)[F43, F81-OS3.4]
(11)[F43, F81-OS3.4]
(12)[F40, F41-OH2.3]
(13)[F40, F41-OH2.3]
(14)[F30, F121, F124 -OS3.1]
(15)[F30, F124-OS3.1]
(16)[F30, F120-OS3.1]
(17)[F30, F124-OS3.1]
(18)[F30, F121, F124-OS3.1]
(20)[F30, F124-OS3.1]
3.11.9.1. Dressing Rooms and Sanitary FacilitiesN/A
(1)[F72-OH2.1] [F70-OH2.2] [F71-OH2.3] [F101-OH6]
(5)[F40, F71, F122-OH2.3]
(6)[F40, F122-OH2.3]
(7)[F40, F71, F122-OH2.2]
(8)[F31-OS3.2]
(9)[F41, F45-OH2.3] [F30-OS3.1]
(10)[F40, F41-OH2.3]
(11)[F40, F41-OH2.3]
(12)[F101-OH6]
(13)[F40, F41-OH2.3] [F101-OH6]
(14)[F40, F41-OH2.3] [F30-OS3.1]
3.11.10.1. Lighting and Emergency ProvisionsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30, F123-OS3.1] [F10-OS3.7]
(4)[F30, F123-OS3.1] [F10-OS3.7]
(5)[F30, F123-OS3.1] [F10-OS3.7]
(7)[F30-OS3.1]
(8)[F30-OS3.1]
(9)[F30-OS3.1] [F11-OS3.7]
(10)[F30-OS3.1] [F11, F12-OS3.7]
(11)[F30-OS3.1] [F11, F12-OS3.7]
(12)[F30, F124-OS3.1]
(13)[F11, F10, F30-OS3.1]
(14)[F11-OS3.1]
3.11.11.1. Service Rooms and Storage FacilitiesN/A
(2)[F50-OH1.1] [F04-OS1.3] [F03-OS2.1] [F43, F44-OS3.4] [F10-OS3.7]
(3)[F01-OS1.1] [F43-OS3.4]
(4)[F50-OH1.1] [F40, F41-OH2.3] [F43-OS3.4]
(5)[F50-OH1.1] [F32, F34-OS3.3] [F34, F43-OS3.4]
3.12.2.1. Construction RequirementsN/A
(2)[F30, F121-OS3.1]
(3)[F30, F121-OS3.1]
(4)(a), (b) [F12, F30, F121-OS3.1] [F123-OS3.7] (c), (d) [F122-OH2.3]
(6)[F30, F121-OS3.1]
(7)[F30, F120, F121-OS3.1]
(8)[F70, F71, F72-OH2.3]
(9)[F30, F36-OS3.1]
3.12.3.1. Ramps into Public SpasN/A
(1)[F123-OS3.1]
3.12.3.2. Access into Public SpasN/A
(2)[F74-OA2]
(3)[F30, F120-OS3.1] [F74-OA2]
(4)[F74-OA2]
(5)[F74-OA2]
3.12.4.1. Water Circulation SystemsN/A
(2)[F40, F41-OH2.3]
(3)[F40, F41, F81-OH2.3] [F122-OH2.2]
(4)[F30, F124-OS3.1]
(5)[F30, F124-OS3.1]
(6)[F30, F124-OS3.1]
(7)[F30, F81, F121, F124-OS3.1]
(8)[F30, F124-OS3.1]
(10)[F30, F124 - OS3.1]
(11)[F30, F81, F124-OS3.1]
(12)[F30, F81, F124-OS3.1]
(13)[F30, F124-OS3.1]
(14)[F40, F41-OH2.3] [F43-OS3.4]
(15)[F40, F41, F81-OH2.3] [F81-OS3.1]
(16)[F30, F124-OS3.1]
(17)[F30, F121-OS3.1] [F31-OS3.2] [F31-OH1.2]
(18)[F40, F41-OH2.3] [F30-OS3.1]
3.12.5.1. Lighting and Emergency ProvisionsN/A
(2)[F13, F30-OS3.1]
(3)[F30, F124-OS3.1]
(4)[F11, F30-OS3.1]
(5)[F30, F124-OS3.1]
3.13.2.1. Requirements for StationsN/A
(3)[F02-OP1.2] Applies to portion of Code text: “... shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... shall be of noncombustible construction,” (a), (c) [F03, F04-OP1.2] [F04-OP1.3] (a), (c) [F03, F04-OS1.2] [F04-OS1.3] (b), (c) [F04–OP1.3] (b), (c) [F04-OS1.3]
(5)[F02-OP1.2] Applies to portion of Code text: “... shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... shall be of noncombustible construction,” [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,” and to Clause (d). (b), (d) [F04-OP1.3] [F04-OS1.3] (c), (d) [F04-OP1.3] [F04-OS1.3]
(6)[F02-OP1.2] Applies to portion of Code text: “... shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... shall be of noncombustible construction,” [F03, F04-OP1.2] [F04-OP1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (d). [F03, F04-OS1.2] [F04-OS1.3] Applies to portion of Code text: “(a) ... floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,” and to Clause (d). (b), (d) [F04-OP1.3] [F04-OS1.3] (c), (d) [F04-OP1.3] [F04-OS1.3]
(10)[F03-OP1.2] [F03-OS1.2]
(11)[F03-OP1.2] [F03-OS1.2]
3.13.3.1. ApplicationN/A
(6)[F10-OS3.7]
3.13.3.2. Booths and KiosksN/A
(1)[F02-OP1.2] Applies to portion of Code text: “... shall be of noncombustible construction,” [F02-OS1.2] Applies to portion of Code text: “... shall be of noncombustible construction,”
(2)[F02, F03-OP1.2] [F02, F03-OS1.2]
3.13.3.3. Service Rooms and Ancillary SpacesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F10-OS1.5]
(4)[F10-OS1.5]
3.13.3.4. Leased AreasN/A
(1)[F02, F03-OP1.2] [F02, F03-OS1.2]
(3)[F10-OS1.5]
(4)[F02-OP1.2] [F02-OS1.2]
(5)[F02-OP1.2] [F02-OS1.2]
(7)(a), (b) [F10-OS1.5] (c) [F10, F36-OS1.5]
3.13.3.5. Vehicle TerminalN/A
(1)(a) [F02-OP1.2] (a) [F02-OS1.2] (b) [F03-OP1.2] (b) [F03-OS1.2]
3.13.3.6. Access to Adjacent BuildingN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OS1.2] [F10-OS1.5]
(3)[F10-OS1.5]
(4)[F03-OP1.2] [F03-OS1.2] [F10-OS1.5]
(5)[F10-OS1.5]
3.13.3.7. Emergency LightingN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
3.13.4.2. General RequirementsN/A
(2)[F10-OS3.7]
(4)[F10-OS3.7]
(5)[F10-OS3.7]
(7)[F03, F06-OS1.2] [F05, F06-OS1.5] [F03, F06-OP1.2]
3.13.4.3. Number and Location of Means of EgressN/A
(1)[F05, F10-OS1.2]
(3)[F05, F10-OS1.5]
(5)[F10-OS3.7]
3.13.4.4. Egress CapacityN/A
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1] [F10-OS3.7]
3.13.4.5. Width of Means of EgressN/A
(4)[F10-OS3.7]
(6)[F30-OS3.1] [F10-OS3.7]
(7)[F30-OS3.1] [F10-OS3.7]
(8)[F30-OS3.1] [F10-OS3.7]
3.13.4.6. Egress FacilitiesN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7]
(4)(a), (c) [F10-OS3.7] (b) [F81-OS3.7]
(5)[F10, F40-OS1.5]
3.13.5.3. Fire DetectorsN/A
(1)[F11-OS1.5]
3.13.5.4. Central Supervising StationN/A
(1)[F13, F81-OP1.2] [F13, F81-OS1.2, OS1.5]
3.13.5.5. AnnunciatorsN/A
(1)[F12-OS1.2, OS1.5]
3.13.5.6. Annunciator IndicationN/A
(1)[F12-OS1.2, OS1.5]
(2)[F13, F81-OP1.2] [F13, F81-OS1.2, OS1.5]
(3)[F10, F11-OS1.5]
(4)[F10, F11-OS1.5]
3.13.5.8. Communication SystemsN/A
(1)[F11, F12-OS3.7]
(2)[F11, F12-OS3.7]
(3)[F11, F12-OS3.7]
3.13.5.9. Emergency Reporting DevicesN/A
(1)[F30-OS3.1] [F11, F12-OS3.7]
3.13.5.11. Standpipe and Hose SystemsN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F12-OP1.2] [F12-OS1.2]
(3)[F12-OP1.2] [F12-OS1.2]
(4)[F02, F12-OP1.2] [F02, F12-OS1.2]
(5)[F02, F12-OP1.2] [F02, F12-OS1.2]
(6)[F02-OP1.2] [F02-OS1.2]
(7)[F02-OP1.2] [F02-OS1.2]
3.13.6.2. Washrooms RequiredN/A
(1)[F72-OH2.1] [F71-OH2.3]
(2)[F101-OH6] Applies to portion of Code text: “... provided the door to the room can be locked from the inside.”
(4)[F72-OH2.1] [F71-OH2.3]
3.13.7.1. ApplicationN/A
(1)[F06-OP1.2] [F06-OS1.2] [F05, F06-OS1.5]
3.13.8.1. ApplicationN/A
(3)[F73-OA1]
3.13.8.3. Elevator RequirementsN/A
(1)[F73-OA1]
(2)[F73-OA1]
3.13.8.4. Emergency Operation of ElevatorsN/A
(1)[F12-OP1.2] [F12-OS1.2, OS1.5]
(2)[F12-OP1.2] [F12-OS1.2, OS1.5]
(3)[F12-OP1.2] [F12-OS1.2, OS1.5]
(4)[F12-OP1.2] [F12-OS1.2, OS1.5]
3.13.8.5. Washrooms Required to be Barrier-FreeN/A
(1)[F73-OA1]
(2)[F74-OA2]
(3)[F74-OA2]
(4)[F74-OA2]
(5)[F74-OA2]
3.14.1.3. Means of EgressN/A
(3)[F10, F12-OS3.7]
3.14.1.4. Clearance to Other StructuresN/A
(1)[F03-OP3.1]
(2)[F03-OP3.1]
3.14.1.5. Clearances to Flammable MaterialN/A
(1)[F01-OP1.1] [F03-OP1.2] [F01-OS1.1] [F03-OS1.2]
3.14.1.6. Flame ResistanceN/A
(1)[F01, F02-OP1.2] [F01, F02-OS1.2]
3.14.1.9. Provision for FirefightingN/A
(1)[F12-OP1.2] [F12-OS1.2]
3.14.1.10. Electrical SystemsN/A
(1)[F34-OP1.1] [F34-OS1.1] [F34-OS3.3]
(2)[F81-OP1.1] [F81-OS1.1]
3.14.2.2. GeneralN/A
(1)[F01, F02, F36-OS1.5] Applies to portion of Code text: “Air-supported structures shall not be used for ... Group F, Division 1 major occupancies ... “ [F10, F36-OS3.7] Applies to portion of Code text: “Air-supported structures shall not be used for Groups B, C, ... major occupancies or for classrooms. “
(2)[F02, F03-OS1.2]
3.14.2.3. Spatial SeparationN/A
(1)[F03-OP3.1]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
3.14.2.4. Clearances to Flammable MaterialN/A
(1)[F01-OP1.1] [F03-OP1.2] [F01-OS1.1] [F03-OS1.2]
3.14.2.5. Flame ResistanceN/A
(1)F01, [F02-OP1.2] [F01, F02-OS1.2]
3.14.2.6. Emergency Air SupplyN/A
(1)[F20-OS3.7]
3.14.2.7. Electrical SystemsN/A
(1)[F34-OP1.1] [F34-OS1.1] [F34-OS3.3]
(2)[F81-OP1.1] [F81-OS1.1]
3.15.4.1. Combustible Sign FacesN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F02-OP1.2] [F02-OS1.2]
(4)[F02-OP1.2] [F02-OS1.2]
(5)[F02-OP1.2] [F02-OS1.2]
3.15.5.1. Obstructions not PermittedN/A
(1)[F50-OH1.1] [F102-OH7] [F12-OP1.2] [F12-OS1.2] [F10, F12-OS1.5] [F30-OS3.7]
3.15.5.2. Clearance for Exterior SignsN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
(4)[F32-OS3.3]
3.16.1.2. GeneralN/A
(1)[F02, F03-OS1.2] [F10-OS1.5] [F30-OS3.1] [F36-OS3.6]
(3)[F10-OS1.5]
(4)[F10-OS1.5]
3.16.1.3. ConstructionN/A
(2)[F30-OS3.1]
(4)[F02, F12, F81-OP1.2] [F02, F12, F81-OS1.2]
3.16.1.4. SignsN/A
(1)[F20-OP2.1] [F20-OS2.1]
(2)[F01-OP1.1] [F01-OS1.1]
3.16.1.5. LightingN/A
(1)[F30-OS3.1]
(2)[F10-OS3.7]
3.16.1.6. Sprinkler SystemN/A
(1)[F02-OP1.2] [F02-OS1.2]
(2)[F02, F81, F82-OP1.2] [F02, F81, F82-OS1.2]
(3)[F02-OP1.2] [F02-OS1.2]
(4)[F81-OP1.2] [F81-OS1.2]
(5)[F81, F82-OP1.2] [F81, F82-OS1.2]
(6)[F13-OP1.2] [F13-OS1.2, OS1.5]
(8)[F02-OP1.2]
3.16.1.7. Exits and Means of EgressN/A
(1)[F12-OP1.2] [F12-OS1.2] [F10, F12-OS3.7]
(4)[F10-OS3.7]
(5)[F10-OS3.7]
(6)[F10-OS3.7]
(7)[F10-OS3.7]
(8)[F10-OS3.7]
(9)[F10-OS3.7]
(10)[F10-OS3.7]
(11)[F10-OS3.7]
(12)[F30-OS3.1] [F10-OS3.7]
(13)[F30-OS3.1] [F10-OS3.7]
3.16.2.2. ConstructionN/A
(1)(a) [F13-OP1.2] (a) [F13-OS1.2] [F11, F13-OS1.5] (b) [F13-OP1.2] (b) [F13-OS1.2, OS1.5] (c) [F02-OP1.1]
3.16.3.2. ConstructionN/A
(2)[F05-OS1.5]
(3)[F10-OS1.5]
3.17.2.2. Means of EgressN/A
(2)[F06, F12-OP1.2] [F06, F12-OS1.2] [F05, F06, F10, F12-OS3.7]
(4)[F10-OS3.7]
(6)[F05, F10-OS1.5]
(8)[F30-OS3.1] [F10-OS3.7]
3.17.2.3. GuardsN/A
(1)[F30-OS3.1]
(3)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1]
3.17.2.4. Clearance to Other StructuresN/A
(1)[F03-OP3.1]
3.17.2.5. Flame ResistanceN/A
(1)[F01, F02-OS1.2] [F01, F02-OP1.2]
3.17.2.6. Provision for FirefightingN/A
(1)[F12-OP1.2] [F12-OS1.2]
3.17.2.7. Electrical SystemsN/A
(1)[F34-OP1.1] [F34-OS1.1] [F34-OS3.3]
(2)[F81-OP1.1] [F81-OS1.1]
3.17.2.8. Structural ProvisionsN/A
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(4)[F20-OS2.1] [F20-OP2.1] [F20-OH4] Applies to footings that support floors and other elements that support floors. [F20-OS3.1] Applies to footings that support floors and other elements that support floors. [F20-OS3.7] Applies to footings that support access to egress facilities.
3.18.2.1. Change of Use and Compensating ConstructionN/A
(1)3.2.6. Applies to additional requirements for high buildings. [F03, F06, F12, F13, F82-OP1.2] [F03-OP3.1] [F02, F03, F06, F12, F13, F82-OS1.2] [F02, F03, F05, F06, F10, F11, F12, F82-OS1.5] [F30-OS3.1] [F11, F12-OS3.7] 3.7. Applies to health requirements for buildings. [F74-OA2] [F50-OH1.1] [F40, F72-OH2.1] [F70-OH2.2] [F71-OH2.3] [F40, F41-OH2.4] [F101-OH6] [F102-OH7] [F01-OP1.1] [F01-OS1.1] [F20, F30-OS3.1] [F32-OS3.3] [F43, F44-OS3.4] 3.11. Applies to public pools. [F74-OA2] [F50- OH1.1] [F72-OH2.1] [F46, F70-OH2.2] [F40, F41, F45, F71, F122 - OH2.3] [F40, F41-OH2.4] [F101-OH6] [F01-OS1.1] [F04-OS1.3] [F03-OS2.1] [F12, F30, F34, F36, F120, F121, F123, F124-OS3.1] [F31- OS3.2] [F32, F34 - OS3.3] [F34, F43, F44, F81, F122-OS3.4] [F10, F11, F12, F34, F123-OS3.7] 3.12. Applies to public spas. [F74-OA2] [F46-OH2.2] [F40, F41, F70, F71, F72, F81, F122 - OH2.3] [F40, F41-OH2.4] [F11, F12, F13, F30, F34, F36, F81, F120, F121, F123, F124-OS3.1] [F43, F81, F122-OS3.4] [F10, F34, F123-OS3.7]
3.18.2.2. Performance Level and Compensating ConstructionN/A
(1)[F140-OC]

Table 4 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 4 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 4 of Division B
Acceptable SolutionsObjectives and Functional Statements
4.1.1.3. Design RequirementsN/A
(1)[F20-OS2.1]
(2)[F22-OH4] [F22-OP2.4]
(3)[F20-OS2.1] Applies to structural members where temporary overloading during construction may result in impairment of that or any other member.
(5)[F20-OS2.3, OS2.4] [F20-OP2.1] [F22-OP2.4]
4.1.1.5. Design BasisN/A
(2)[F20-OS2.1] [F22-OS2.4, OS2.5] [F20-OP2.1] [F22-OP2.4, OP2.5] [F22-OH4]
4.1.2.1. Loads and EffectsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(2)[F20-OS2.1]
(3)[F20-OS2.1]
4.1.2.2. Loads Not ListedN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.3.2. Strength and StabilityN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F22-OS2.4, OS2.5] Applies to the stabilizing resistance of the dead load. [F20-OP2.1] [F22-OP2.4, OP2.5]
(3)[F20-OS2.1] [F22-OS2.4, OS2.5] Applies to the stabilizing resistance of the dead load. [F20-OP2.1] [F22-OP2.4, OP2.5]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F22-OS2.4, OS2.5] [F20-OP2.1] [F22-OP2.4, OP2.5]
(8)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(9)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(11)[F20-OS2.1] [F22-OS2.4, OS2.5]
(12)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.3.3. FatigueN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F20, F22-OP2.4] [F22-OH4]
4.1.3.4. ServiceabilityN/A
(1)[F22-OP2.4] [F22-OH4]
(2)[F22-OP2.4] [F22-OH4]
(3)[F22-OP2.4] [F22-OH4]
(4)[F22-OP2.4] [F22-OH4]
(5)[F22-OH4] [F22-OP2.4] (b), (c), (d) [F22-OP2.4]
(6)[F21-OS2.5] [F21-OP2.4, OP2.5] [F22-OH4]
4.1.3.5. DeflectionN/A
(1)[F22-OH4] [F22-OP2.4] (b), (c), (d) [F22-OP2.4]
(2)[F22-OS2.3, OS2.4] [F22-OP2.4]
(3)[F22-OP2.4]
(5)[F22-OS2.3, OS2.4] [F22-OP2.3, OP2.4]
4.1.3.6. VibrationN/A
(1)[F22-OH4] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F20, F22-OP2.4] [F22-OH4]
(3)[F20-OS2.1] [F20-OP2.1] [F20, F22-OP2.4] [F22-OH4]
4.1.4.1. Dead LoadsN/A
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F22-OS2.4, OS2.5]
4.1.5.1. Loads Due to Use of Floors and RoofsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.5.2. Uses Not StipulatedN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.5.3. Full and Partial LoadingN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.5.4. Loads for Occupancy ServedN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.5.5. Loads on Exterior AreasN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.5.7. More Than One OccupancyN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.5.8. Variation with Tributary AreaN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.5.9. Concentrated LoadsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.5.10. Sway Forces in Assembly OccupanciesN/A
(1)[F20-OS2.1] [F20-OP2.1, OP2.4]
4.1.5.11. Crane-Supporting Structures and Impact of Machinery and EquipmentN/A
(1)[F20-OS2.1] [F20-OP2.1] [F20, F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1, OP2.4]
(4)[F20-OS2.1] [F20-OP2.1, OP2.4]
(5)[F20-OS2.1] [F20-OP2.1, OP2.4]
4.1.5.12. BleachersN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.4]
4.1.5.13. Helicopter Landing AreasN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.5.14. Loads on Guards and HandrailsN/A
(1)[F20-OS2.1]
(2)[F20-OS2.1]
(3)[F20-OS2.1, OS2.4]
(4)[F22-OS2.4]
(6)[F20-OS2.1]
(7)[F20-OS2.1]
4.1.5.15. Loads on Vehicle GuardrailsN/A
(1)[F20-OS2.1]
4.1.5.16. Loads on Walls Acting as GuardsN/A
(1)[F20-OS2.1]
4.1.5.17. FirewallsN/A
(1)[F20-OS1.2] [F20-OP1.2] [F20-OP3.1]
(2)[F04-OS1.2] [F04-OP1.2] [F04-OP3.1]
4.1.6.2. Specified Snow LoadN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(8)[F20-OS2.1] Applies to portion of Code text: "The accumulation factor, Ca, shall be 1.0, …" [F20-OP2.1] [F22-OP2.4] Applies to portion of Code text: "The accumulation factor, Ca, shall be 1.0, …" (a) to (f) [F20-OS2.1] Applies to roof shapes and configurations that call for a higher accumulation factor. (a) to (f) [F20-OP2.1] [F22-OP2.4] Applies to roof shapes and configurations that call for a higher accumulation factor.
(9)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.3. Full and Partial LoadingN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.4. Specified Rain LoadN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.5. Multi-Level RoofsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.6. Horizontal Gap Between a Roof and a Higher RoofN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.7. Areas Adjacent to Roof ProjectionsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.8. Snow Drift at CornersN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.9. Gable RoofsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.10. Arch Roofs, Curved Roofs and DomesN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(9)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.11. Snow Loads Due to SlidingN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.12. Valleys in Curved or Sloped RoofsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.13. Specific Weight of SnowN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.14. Snow RemovalN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.15. Ice Loading of StructuresN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.6.16. Roofs with Solar PanelsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.7.1. Specified Wind LoadN/A
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.7.2. Classification of BuildingsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.7.3. Static ProcedureN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(8)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(10)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.7.4. Topographic FactorN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.7.5. External Pressure CoefficientsN/A
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(5)[F20-OS2.1]
(6)[F20-OS2.1]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(8)[F20-OS2.1]
(9)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.7.6. External Pressure Coefficients for Low BuildingsN/A
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(8)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(9)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.7.7. Internal Pressure CoefficientN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.7.8. Dynamic ProcedureN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.7.9. Full and Partial Wind LoadingN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.7.10. Interior Walls and PartitionsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.7.11. Exterior Ornamentations, Equipment and AppendagesN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.7.12. Attached Canopies on Low Buildings with a Height H ≤ 20 mN/A
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.7.13. Roof-Mounted Solar Panels on Buildings of Any HeightN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1]
(4)[F20-OS2.1]
(5)[F20-OS2.1]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.7.14. Wind Tunnel ProcedureN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4]
4.1.8.1. AnalysisN/A
(2)(a) [F20-OS2.1] (a) [F20-OP2.1, OP2.3] [F22-OP2.4] (b) [F20-OS2.1] (b) [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1, OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(8)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(9)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(10)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(11)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(12)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(13)[F20-OS2.1] [F20-OP2.3] [F22-OP2.3, OP2.4]
(14)[F20-OS2.1] [F20-OP2.3] [F22-OP2.3, OP2.4]
4.1.8.3. General RequirementsN/A
(2)[F20-OS2.1] [F20-OP2.1, OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(8)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.4. Site PropertiesN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.5. Importance Factor and Seismic CategoryN/A
(1)[F20-OS2.1] [F20-OP2.1, OP2.3] [F22-OP2.4]
4.1.8.6. Structural ConfigurationN/A
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.7. Methods of AnalysisN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.8. Direction of LoadingN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.9. Force Reduction Factors, System Overstrength Factors and General RestrictionsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.10. Additional System RestrictionsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)(a) [F20-OP2.3] [F22-OP2.4] (b) [F20-OP2.3] [F22-OP2.4] (c) [F20-OP2.3] [F22-OP2.4] (d) [F20-OP2.3] [F22-OP2.4]
(3)(a) [F20-OP2.3] [F22-OP2.4] (b) [F20-OP2.3] [F22-OP2.4] (c) [F20-OP2.3] [F22-OP2.4] (d) [F20-OP2.3] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(8)[F22-OS2.3, OS2.4] [F22-OP2.3, OP2.4]
(9)[F22-OS2.1] [F20-OP2.1] [F22-OP2.4]
(10)(a) [F20-OS2.1] (a) [F20-OP2.1] [F22-OP2.4] (b) [F20-OS2.1] (b) [F20-OP2.1] [F22-OP2.4]
4.1.8.11. Equivalent Static Force Procedure for Structures Satisfying the Conditions of Article 4.1.8.7.N/A
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(8)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(9)(a) [F20-OS2.1] (a) [F20-OP2.1] [F22-OP2.4] (b) [F20-OS2.1] (b) [F20-OP2.1] [F22-OP2.4]
(10)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(11)(a) [F20-OP2.1] [F22-OP2.4] (a) [F20-OS2.1] (b) [F20-OS2.1] (b) [F20-OP2.1] [F22-OP2.4]
(12)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.12. Dynamic Analysis ProcedureN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)(a) [F20-OS2.1] (a) [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1, OP2.3] [F22-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1, OP2.3] [F22-OP2.4]
(8)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(9)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(10)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(12)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.13. Deflections and Drift LimitsN/A
(1)[F22-OS2.3, OS2.4] [F22-OP2.3, OP2.4]
(2)[F22-OS2.3, OS2.4] [F22-OP2.3, OP2.4]
(3)[F22-OS2.3, OS2.4] [F22-OP2.3, OP2.4]
4.1.8.14. Structural SeparationN/A
(1)[F22-OS2.3, OS2.4] [F22-OP2.3, OP2.4] [F22-OP4.3]
(2)[F20-OS2.1, OS2.3, OS2.4] [F20-OP2.1, OP2.3, OP2.4] [F20-OP4.3]
(3)[F20-OS2.1, OS2.3, OS2.4] [F20-OP2.1, OP2.3, OP2.4] [F20-OP4.3]
(4)[F20-OS2.1, OS2.3, OS2.4] [F20-OP2.1, OP2.3, OP2.4] [F20-OP4.3]
4.1.8.15. Design ProvisionsN/A
(1)[F20-OS2.1] [F20-OP2.1, OP2.3, OP2.4]
(2)[F20-OS2.1] [F20-OP2.1, OP2.3, OP2.4]
(3)[F20-OS2.1] [F20-OP2.1, OP2.3, OP2.4]
(4)[F20-OS2.1] [F20-OP2.1, OP2.4]
(5)[F20-OS2.1, OS2.4] [F20-OP2.1, OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.16. Foundation ProvisionsN/A
(1)[F20-OS2.2, OS2.4] [F20-OP2.2, OP2.4]
(2)[F20-OS2.1] [F20-OP2.1]
(5)[F20-OS2.2, OS2.4] [F20-OP2.2, OP2.4]
(6)(a) [F22-OS2.4] (a) [F22-OP2.4] (b) [F22-OS2.4] (b) [F22-OP2.4] (c) [F20-OS2.4] (c) [F20-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1, OP2.4]
(8)(a) [F20-OS2.1] (a) [F20-OP2.1] (b) [F22-OS2.4] (b) [F22-OP2.4]
(9)[F20-OS2.4] [F20-OP2.4]
(10)[F20-OS2.2] [F22-OS2.4] [F20-OP2.2] [F22-OP2.4]
4.1.8.17. Site StabilityN/A
(1)[F20-OP2.1] [F22-OP2.4] [F20-OS2.1]
4.1.8.18. Elements of Structures, Non-structural Components and EquipmentN/A
(1)[F20, F22-OS2.4] [F20-OP2.3] [F22-OP2.3, OP2.4]
(4)[F20, F22-OS2.4] [F20, F22-OP2.3, OP2.4]
(5)[F20, F22-OS2.1] [F20, F22-OP2.1, OP2.4]
(6)[F20, F22-OS2.4] [F20, F22-OP2.3, OP2.4]
(7)[F20, F22-OS2.4] Applies to portion of Code text: "Connections to the structure of elements and components listed in Table 4.1.8.18. shall be designed to support the component or element for gravity loads, shall conform to the requirements of Sentence 4.1.8.18.(1) …" [F20, F22-OP2.3, OP2.4] Applies to portion of Code text: "Connections to the structure of elements and components listed in Table 4.1.8.18. shall be designed to support the component or element for gravity loads, shall conform to the requirements of Sentence 4.1.8.18.(1)…" (a) [F20, F22-OS2.4] (a) [F20, F22-OP2.3, OP2.4] (b), (c) [F20, F22-OS2.4] (b), (c) [F20, F22-OP2.3, OP2.4] (d) [F20, F22-OS2.4] (d) [F20, F22-OP2.3, OP2.4] (e) [F20, F22-OS2.4] (e) [F20, F22-OP2.3, OP2.4]
(9)[F22-OS2.3, OS2.4] [F22-OP2.3, OP2.4]
(10)[F22-OS2.1, OS2.3, OS2.4] [F22-OP2.1, OP2.3, OP2.4]
(11)[F20-OS2.1] [F22-OS2.4] [F20, F22-OP2.3, OP2.4]
(12)[F20-OS2.1] [F22-OS2.3] [F20-OP2.1] [F22-OP2.3]
(14)[F20, F22-OS2.4]
(16)[F20, F22-OS2.4] [F20-OP2.3] [F22-OP2.3, OP2.4]
4.1.8.19. Seismic IsolationN/A
(2)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.20. Seismic Isolation Design ProvisionsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(2)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(7)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(9)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(10)[F22-OS2.4] [F22-OP2.3, OP2.4]
4.1.8.21. Supplemental Energy DissipationN/A
(2)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.1.8.22. Supplemental Energy Dissipation Design ConsiderationN/A
(1)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(3)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(4)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(5)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(6)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
(7)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
(8)[F20-OS2.1] [F22-OS2.4] [F20-OP2.1] [F22-OP2.4]
4.1.8.23. Additional Performance Requirements for Post-Disaster Buildings, High Importance Category Buildings, and a Subset of Normal Importance Category BuildingsN/A
(2)[F20-OS2.1] [F22-OP2.3, OP2.4]
(3)[F20-OS2.1] [F22-OP2.3, OP2.4]
(4)[F20-OS2.1]
4.2.2.1. Subsurface InvestigationN/A
(1)[F20-OS2.2] [F20, F21-OS2.6] [F20-OP2.2] [F21-OP2.6] [F21-OP4.1, OP4.4]
4.2.2.3. Field ReviewN/A
(1)[F20-OS2.2, OS2.6] [F21-OS2.6] [F20-OP2.2] [F21-OP2.5] [F21-OP4.1, OP4.4]
4.2.2.4. Altered Subsurface ConditionN/A
(1)[F20-OP2.2] [F21-OP2.6] [F21-OP4.1, OP4.4] [F20-OS2.2] [F20, F21-OS2.6]
(2)[F20-OP2.2] [F21-OP2.6] [F21-OP4.1, OP4.4] [F20-OS2.2] [F20, F21-OS2.6]
4.2.3.2. Preservation Treatment of WoodN/A
(1)[F80-OS2.3] [F80-OP2.3]
(2)[F80-OS2.3] [F80-OP2.3]
4.2.3.4. Prevention of Deterioration of MasonryN/A
(1)[F80-OS2.3] [F80-OP2.3]
4.2.3.6. Protection Against Chemical AttackN/A
(1)[F80-OS2.3] [F80-OP2.3]
4.2.3.8. Steel PilesN/A
(1)[F20-OS2.3] [F20-OP2.3]
4.2.3.9. High Strength Steel TendonsN/A
(1)[F20, F80-OS2.5, OS2.6] [F20, F80-OP2.5, OP2.6] [F20, F80-OP4.1, OP4.4]
4.2.3.10. Corrosion of SteelN/A
(1)[F80-OS2.3] [F80-OP2.3] [F80-OP4.1]
4.2.4.1. Design BasisN/A
(1)[F20-OS2.2] [F20, F21-OS2.6] [F20-OP2.2] [F21-OP2.5] [F21-OP4.1, OP4.4]
(5)[F21-OS2.5] [F21-OP2.4, OP2.5]
4.2.4.2. Subsurface InvestigationN/A
(1)[F20-OS2.2] [F20, F21-OS2.6] [F20-OP2.2] [F21-OP2.6] [F21-OP4.1, OP4.4]
4.2.4.3. IdentificationN/A
(1)[F20-OS2.2] [F20, F21-OS2.6] [F20-OP2.2] [F21-OP2.6] [F21-OP4.1, OP4.4]
4.2.4.4. Depth of FoundationsN/A
(1)[F21-OP2.4] Applies to portion of Code text: "… the bearing surface of a foundation shall be below the level of potential damage, including damage resulting from frost action …" [F21-OP2.4] Applies to portion of Code text: "… the foundation shall be designed to prevent damage resulting from adfreezing and frost jacking."
(2)[F21-OP2.4]
4.2.4.5. Sloping GroundN/A
(1)[F21-OS2.2] [F21-OP2.2, OP2.4, OP2.6]
4.2.4.6. Eccentric and Inclined LoadsN/A
(1)[F20-OS2.1, OS2.2] [F20-OP2.1, OP2.2, OP2.4]
4.2.4.7. Dynamic LoadingN/A
(1)[F20-OS2.2] [F20-OP2.2, OP2.4, OP2.6] [F20-OH4]
4.2.4.8. Hydrostatic UpliftN/A
(1)[F22-OP2.1, OP2.4]
4.2.4.9. Groundwater Level ChargeN/A
(1)[F21-OP4.1]
4.2.4.10. PermafrostN/A
(1)[F20-OS2.2] [F21-OS2.5] [F20-OP2.2] [F20, F21-OP2.4] [F21-OP2.6]
4.2.4.11. Swelling and Shrinking SoilsN/A
(1)[F21-OP2.4, OP2.6]
4.2.4.12. Expanding and Deteriorating RockN/A
(1)[F21-OP2.4, OP2.6]
4.2.4.13. Construction on FillN/A
(1)(a) [F20-OS2.2] [F21-OS2.5] (b) [F20-OP2.2] [F20, F21-OP2.4] [F21-OP2.6] (c) [F01-OS1.1]
4.2.5.2. Excavation ConstructionN/A
(1)[F21-OP4.1]
(2)[F20-OS2.6] [F20-OP2.3] [F20, F21-OP4.1]
4.2.5.3. Supported ExcavationsN/A
(1)[F20-OS2.6] [F21-OP4.1]
4.2.5.4. Unsupported ExcavationsN/A
(1)[F20-OS2.6] [F21-OP4.1]
4.2.5.5. Control of Water Around ExcavationsN/A
(1)[F60-OS2.6] [F60-OP4.1, OP4.4]
4.2.5.6. Loss of GroundN/A
(1)[F21-OP4.1]
4.2.5.7. Protection and Maintenance at ExcavationsN/A
(1)[F80-OS2.6] [F80-OP4.1]
4.2.5.8. BackfillingN/A
(1)[F21-OP4.1] (a) [F21-OP2.1, OP2.4] (a) [F21-OS2.1]
(2)[F21-OP2.4]
4.2.6.2. Support of Shallow FoundationsN/A
(1)[F20-OS2.2] [F20-OP2.2] [F20, F21-OP2.4]
4.2.6.3. Incorrect Placement of Shallow FoundationsN/A
(1)[F20-OS2.2] [F20-OP2.2, OP2.4] [F21-OP2.4]
4.2.6.4. Damaged Shallow FoundationsN/A
(1)[F20-OS2.1] [F20-OP2.1, OP2.4] [F22-OP2.4]
4.2.7.2. Design for Deep FoundationsN/A
(3)[F20-OS2.1, OS2.2] [F21-OS2.5] [F20-OP2.1, OP2.2] [F21, F22-OP2.4]
(5)[F20-OS2.1] [F20-OP2.1] [F20, F22-OP2.4]
(6)[F20-OP2.1, OP2.4]
4.2.7.3. Tolerance in Alignment and LocationN/A
(1)[F20-OS2.1] [F20-OP2.1] [F20, F22-OP2.4]
4.2.7.4. Incorrect Alignment and LocationN/A
(1)[F20-OS2.1] [F20-OP2.1, OP2.4] [F22-OP2.4]
4.2.7.5. Installation of Deep FoundationsN/A
(1)[F81-OS2.1] [F21-OS2.2, OS2.6] (a), (b) [F81-OP2.1] [F21-OP2.2] [F21, F81-OP2.4] (c) [F21-OP4.1]
4.2.7.6. Damaged Deep Foundation UnitsN/A
(1)[F20-OS2.1] [F20-OP2.1] [F22-OP2.4]
4.2.8.2. Use of Existing FoundationsN/A
(1)[F20-OS2.1, OS2.2] [F20-OP2.1, OP2.2] [F22-OP2.4]
4.3.1.1. Design Basis for WoodN/A
(1)[F20-OS2.1] [F80-OS2.3] [F20-OP2.1] [F80-OP2.3] [F21, F22, F80-OP2.4] [F21, F22, F80-OH4]
4.3.1.2. Glued-Laminated MembersN/A
(1)[F20-OS2.1] [F20-OP2.1] [F21, F22-OP2.4] [F21, F22-OH4]
4.3.2.1. Design Basis for Plain and Reinforced MasonryN/A
(1)[F20-OS2.1] [F80-OS2.3] [F20-OP2.1] [F80-OP2.3] [F21, F22, F80-OP2.4] [F21, F22, F80-OH4]
4.3.3.1. Design Basis for Plain, Reinforced and Prestressed ConcreteN/A
(1)[F20-OS2.1] [F80, F81-OS2.3] [F20-OP2.1] [F80, F81-OP2.3] [F21, F22, F80, F81-OP2.4] [F21, F22, F80, F81-OH4]
4.3.4.1. Design Basis for Structural SteelN/A
(1)[F20-OS2.1] [F80-OS2.3] [F20-OP2.1] [F80-OP2.3] [F20, F22, F80-OP2.4] [F22, F80-OH4]
4.3.4.2. Design Basis for Cold Formed SteelN/A
(1)[F20-OS2.1] [F80-OS2.3] [F20-OP2.1] [F80-OP2.3] [F20, F22, F80-OP2.4] [F22, F80-OH4]
4.3.5.1. Design Basis for AluminumN/A
(1)[F20-OS2.1] [F80-OS2.3] [F20-OP2.1] [F80-OP2.3] [F20, F22, F80-OP2.4] [F22, F80-OH4]
4.3.6.1. Design Basis for GlassN/A
(1)[F20-OS2.1] [F20-OP2.1]
4.4.1.1. Design Basis for Air-, Cable- and Frame-Supported Membrane StructuresN/A
(1)[F20-OS2.1] [F80-OS2.3] [F20-OP2.1] [F80-OP2.3] [F22-OP2.4] [F22-OH4]
4.4.2.1. Design Basis for Storage Garages and Repair GaragesN/A
(1)[F21, F61, F80-OS2.3] [F21, F61, F80-OP2.3, OP2.4] [F21, F61, F80-OH4]
4.4.4.1. Guards Over Retaining WallsN/A
(1)[F30-OS3.1]
4.4.5.1. Anchor Systems on Building ExteriorN/A
(1)[F30-OS3.1]
(2)[F20-OS2.1] [F30-OS3.1]
(4)[F81-OS2.3]

Table 5 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 5 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 5 of Division B
Acceptable SolutionsObjectives and Functional Statements
5.1.4.1. Structural and Environmental LoadsN/A
(1)[F61-OH4] (a) [F20, F51, F55-OS1.4] Applies where required life safety systems are incorporated in environmental separators. (a) [F60, F61, F63-OS2.2, OS2.3] (a) [F55, F61, F63-OH1.1, OH1.2, OH1.3] (b) [F20-OS2.1] [F21, F22-OS2.3, OS2.4] Applies to snow fences and sloped glazing. (b) [F20-OS3.1] Applies to snow fences and sloped glazing. (b) [F20, F21, F22-OH1.1, OH1.2, OH1.3] (b) [F20-OH4]
(4)[F20-OS2.1] [F21, F22-OS2.3, OS2.4] [F20, F21, F22-OH1.1, OH1.2, OH1.3]
(5)(a) [F20-OS2.1] [F21, F22-OS2.3, OS2.4] (a) [F20, F21, F22-OH1.1, OH1.2, OH1.3] (b) [F20-OS2.1] [F21, F22-OS2.3, OS2.4] (b) [F20, F21, F22-OH1.1, OH1.2, OH1.3]
(6)[F20, F21, F22-OH1.1, OH1.2, OH1.3] (a) [F20-OS2.1, OS2.3] (b), (c) [F21, F22-OS2.3] (b), (c) [F22-OH4]
5.1.4.2. Resistance to DeteriorationN/A
(1)[F80, F81-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F80, F81-OS2.3] [F80, F81-OS3.1] Applies to floor assemblies. [F80, F81-OH1.1, OH1.2, OH1.3] [F80, F81-OH4] Applies to floor assemblies.
5.2.1.1. Exterior Environmental LoadsN/A
(2)[F20-OS2.1] [F20, F40-OH1.1] [F20-OH1.2, OH1.3]
5.2.1.2. Interior Environmental LoadsN/A
(1)[F51, F55, F61, F63-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F55, F61, F63-OS2.3] [F51, F55, F61, F63-OH1.1, OH1.2]
5.2.1.3. Environmental Load and Transfer CalculationsN/A
(1)[F51, F61, F63-OS2.3] Applies to heat, air and moisture transfer calculations. [F51, F55, F61, F63-OH1.1, OH1.2] [F51, F61-OH1.3] Applies to heat, air and moisture transfer calculations. [F56-OH3.1] Applies to sound transmission calculations.
(3)[F20-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F20-OS2.1] [F55, F61, F63-OH1.1, OH1.2] [F55, F61-OH1.3]
5.2.2.1. Determination of Structural Loads and EffectsN/A
(1)[F20-OS2.1] [F21, F22-OS2.3, OS2.4] [F20, F21, F22-OH1.1, OH1.2, OH1.3] [F20, F21, F22-OH4]
(3)[F20-OS2.1] [F21, F22-OS2.3, OS2.4] [F20, F21, F22-OH1.1, OH1.2, OH1.3] [F20, F21, F22-OH4]
5.2.2.2. Determination of Wind LoadN/A
(2)[F20-OS2.1] [F22-OS2.3, OS2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4]
(3)[F20-OS2.1] [F22-OS2.3, OS2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4]
(4)[F20, F55, F61-OS2.1, OS2.3] [F20, F55, F61-OH1.1, OH1.2, OH1.3]
5.2.2.3. Design ProceduresN/A
(1)[F20-OS2.1] [F22-OS2.3, OS2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4]
5.3.1.1. Required Resistance to Heat TransferN/A
(1)[F51, F63-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F63-OS2.3] [F63-OH1.1] [F51, F63-OH1.2]
5.3.1.2. Properties to Resist Heat Transfer or Dissipate HeatN/A
(1)(a), (b) [F51, F63-OH1.1] (b) [F51, F63-OS1.4] Applies where required life safety systems are incorporated in environmental separators. (b), (d) [F51, F63-OS2.3] (c) [F51-OH1.2] (d) [F30-OS3.1]
5.3.1.3. Location and Installation of Materials Providing Thermal ResistanceN/A
(1)[F63-OS2.3] [F51, F63-OH1.1]
(2)[F51, F63-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F63-OS2.3] [F51, F63-OH1.1, OH1.2]
5.4.1.1. Required Resistance to Air LeakageN/A
(1)(a), (b), (c), (e) [F40, F55-OH1.1] (a), (b), (f) [F51, F52, F54, F55-OH1.2] (c) [F55, F61, F63-OH1.3] (c), (d) [F55, F61, F62, F63-OS2.3] (d) [F55, F62-OS3.1] (f) [F55, F62-OS1.4] Applies where required life safety systems are incorporated in environmental separators.
(2)[F51, F55-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F61, F63-OS2.3] [F40, F51, F55, F61, F63-OH1.1] [F51, F52, F54, F55, F61, F63-OH1.2] [F51, F55, F61, F63-OH1.3]
(3)[F55-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F55-OS2.3] [F55-OH1.1, OH1.2, OH1.3]
(4)[F51, F61, F63-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F61, F63-OS2.3] [F51, F55, F61, F63-OH1.1, OH1.2] [F55, F61-OH1.3]
5.4.1.2. Air Barrier AssembliesN/A
(1)[F55-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F55-OS2.3] [F55-OH1.1, OH1.2, OH1.3]
(2)[F55-OS1.4] Applies where required life safety systems are incorporated in environmental separators. [F55-OS2.3] [F55-OH1.1, OH1.2, OH1.3]
(4)[F55-OH1.1]
5.5.1.1. Required Resistance to Vapour DiffusionN/A
(1)[F63-OS2.3] [F63-OH1.1, OH1.2]
(2)[F63-OS2.3] [F63-OH1.1, OH1.2]
5.5.1.2. Vapour Barrier Properties and InstallationN/A
(1)[F63-OS2.3] [F63-OH1.1, OH1.2]
(2)[F63-OS2.3] [F63-OH1.1, OH1.2]
(3)[F63-OS2.3] [F63-OH1.1, OH1.2]
5.6.1.1. Required Protection from PrecipitationN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
5.6.1.2. Installation of Protective MaterialsN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
5.6.2.1. Sealing and DrainageN/A
(1)[F61, F62-OS2.3] [F61, F62-OH1.1, OH1.2, OH1.3]
5.6.2.2. Accumulation and DisposalN/A
(1)[F30-OS3.1]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(3)[F21-OS2.2] [F60-OS2.3] [F61-OH1.1, OH1.2, OH1.3] (b) [F21-OP2.6]
(4)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
5.7.1.2. Required ProtectionN/A
(1)[F60-OS2.3] [F60-OH1.1, OH1.2, OH1.3]
(2)[F60-OS2.2, OS2.3] [F60-OH1.1, OH1.2, OH1.3]
5.7.3.2. Required ProtectionN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
5.7.3.3. WaterproofingN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
5.7.3.4. Where Dampproofing is PermittedN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
5.8.1.1. Required ProtectionN/A
(1)[F56-OH3.1]
(2)[F56-OH3.1]
5.8.1.2. Determination of Sound Transmission RatingsN/A
(1)[F56-OH3.1]
(2)[F56-OH3.1]
5.8.1.4. Detailed Method for Calculating ASTCN/A
(1)[F56-OH3.1]
(2)[F56-OH3.1]
(3)[F56-OH3.1]
(4)[F56-OH3.1]
(5)[F56-OH3.1]
(6)[F56-OH3.1]
(7)[F56-OH3.1]
5.8.1.5. Simplified Method for Calculating ASTCN/A
(1)[F56-OH3.1]
(2)[F56-OH3.1]
(3)[F56-OH3.1]
(4)[F56-OH3.1]
(5)[F56-OH3.1]
(6)[F56-OH3.1]
5.9.1.1. Compliance with Applicable StandardsN/A
(1)[F20, F80-OS2.1] [F20-OS2.2] [F20, F22, F51, F61, F63, F80-OS2.3] [F51-OS2.5] [F61, F63, F80-OS3.1] [F61, F63, F80-OH4] Applies to floor assemblies. [F55-OH1.1] [F20, F22, F51, F54, F55, F61, F63, F80-OH1.1, OH1.2] [F55, F61, F80-OH1.3] [F42-OH2.5] [F61, F63, F80-OH4] Applies to floor assemblies. [F20, F80-OP2.1, OP2.3] [F22, F80-OP2.4] (a) [F61, F63-OS1.4] Applies where required life safety systems are incorporated in environmental separators.
5.9.2.2. Applicable StandardsN/A
(1)[F20, F55, F61-OS2.3] [F20, F55, F61, F63-OH1.1, OH1.3] [F20, F55, F61, F63, F81-OH1.2] [F20, F55, F61-OP2.3]
5.9.2.4. Heat TransferN/A
(2)[F63-OS2.3] [F63-OH1.1, OH1.2]
5.9.3.3. Heat TransferN/A
(2)[F63-OS2.3] [F63-OH1.1, OH1.2]
5.9.3.4. Air LeakageN/A
(2)[F55-OS1.4] Applies where required life safety systems are incorporated in environmental separation. [F55, F63-OS2.3] [F55, F63-OH1.1, OH1.2, OH1.3]
5.9.3.5. Water PenetrationN/A
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
5.9.4.1. Structural Loads, Heat Transfer, Air Leakage, Vapour Diffusion and Water PenetrationN/A
(1)(b) [F61, F62-OS2.3] (b) [F61, F62-OH1.1, OH1.2, OH1.3]

Table 6 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 of Division B
Acceptable SolutionsObjectives and Functional Statements
6.2.1.1. Good Engineering PracticeN/A
(1)[F31, F50, F51, F52, F54, F63-OS3.2, OS3.4] (a) to (e) [F31, F51-OP1.1] (a) to (c), (e) to (i) [F40, F50, F51, F52, F54, F63-OH1.1] (a) to (c), (e) to (h) [F50, F51, F52, F54, F63-OH1.2, OH1.3] (d) [F01-OS1.1]
6.2.1.1A. Design Indoor Air TemperaturesN/A
(1)[F51-OH1.2]
(2)[F51-OH1.2]
6.2.1.2. Outdoor Design ConditionsN/A
(2)[F40, F50-OH1.1]
(3)[F40, F43, F44, F50-OH1.1] [F44-OS3.4]
6.2.1.3. Expansion, Contraction and System PressureN/A
(1)[F20-OS3.2]
6.2.1.4. Structural MovementN/A
(1)[F23-OS3.1] [F50, F51, F63-OH1.1, OH1.2, OH1.3]
6.2.1.5. Installation StandardsN/A
(1)[F43-OP1.1] [F43-OS1.1] [F43-OS3.4]
(2)[F43-OP1.1] [F43-OS1.1] [F43-OS3.4]
(3)[F41, F50, F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F44-OS3.4]
(4)[F41, F50, F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F44-OS3.4]
(5)[F43-OP1.1] [F43-OS1.1] [F43-OS3.4]
(6)[F51, F63-OH1.2, OH1.3] [F31, F51-OP1.1] [F31, F51, F63-OS3.2, OS3.4]
(7)[F110-OE]
6.2.1.6. Installation — GeneralN/A
(1)[F82-OS1.1] [F82-OS3.4] [F82-OP1.1]
(2)[F31-OS3.1]
(3)[F81-OS3.2, OS3.3, OS3.4] [F81-OS1.1]
6.2.1.7. AsbestosN/A
(1)[F43-OH1.1]
6.2.2.1. Applicable StandardN/A
(1)[F81-OS1.1]
6.2.3.1. Solid Fuel Storage BinsN/A
(1)[F30-OH2.1]
(2)[F01-OS1.1] [F01-OP1.1]
6.3.1.1. Required VentilationN/A
(2)[F41, F50, F52, F53, F63-OH1.1]
(3)[F40, F41, F50, F52, F53, F63-OH1.1]
6.3.1.1.A. Natural VentilationN/A
(1)[F50-OH1.1]
(2)[F50-OH1.1]
6.3.1.2. Crawl Spaces and Attic or Roof SpacesN/A
(1)[F61, F63, F641-OH1.1, OH1.3]
6.3.1.3. Ventilation of Storage and Repair GaragesN/A
(1)[F44, F50-OS3.4]
(2)[F44-OS3.4]
(3)[F44-OS3.4]
(4)[F44, F50-OS3.4]
(5)[F44, F50-OH1.1] [F44, F50-OS3.4]
(7)[F44, F50-OH1.1] [F44, F50-OS3.4]
(8)[F44, F50-OH1.1] [F44, F50-OS3.4]
(9)[F44, F50-OH1.1] [F44, F50-OS3.4]
6.3.1.5. Indoor Air ContaminantsN/A
(1)[F44-OH1.1] [F44-OS3.4]
(2)[F44-OH1.1]
(3)[F52-OH1.1]
6.3.1.6. Commercial Cooking EquipmentN/A
(1)[F01, F44-OP1.1] [F01, F44-OS1.1]
6.3.2.2. Drain PansN/A
(1)[F41, F44, F50, F82-OH1.1]
(2)[F40, F41, F44, F50-OH1.1]
6.3.2.3. Materials in Air Duct SystemsN/A
(2)[F20, F80-OH1.1, OH1.2]
(3)[F44, F81-OS3.4] [F81-OH1.1]
(4)[F20, F80-OH1.1, OH1.2]
6.3.2.4. Connections in Air Duct SystemsN/A
(1)[F81-OH1.1, OH1.2] [F44, F81-OS3.4]
6.3.2.5. Duct Coverings, Linings, Adhesives and InsulationN/A
(2)[F81-OH1.1, OH1.2] [F81-OS1.1] [F81-OP1.1]
6.3.2.6A. Construction and Installation of Ducts and PlenumsN/A
(1)[F20-OH4] [F20-OP2.4] [F20-OS2.3]
(2)[F03-OP1.1] [F03-OS1.1]
(3)[F63-OH1.1] [F51, F52-OH1.2] [F01-OS1.1] [F20, F63-OS2.3] [F20-OS3.1]
(4)[F43, F63-OH1.1] [F51, F52-OH1.2] [F01-OP1.1] [F01-OS1.1] [F63-OS2.3]
(5)[F43, F63-OH1.1] [F51, F52-OH1.2] [F01-OP1.1] [F01-OS1.1] [F63-OS2.3]
(6)[F63-OH1.1] [F51, F52-OH1.2] [F01-OP1.1] [F01-OS1.1] [F63-OS2.3]
(7)[F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F20-OS3.1]
(8)[F80-OH1.1, OH1.2] [F80-OS2.3]
(9)[F44, F81-OH1.1] [F81-OH1.2]
6.3.2.7. Interconnection of SystemsN/A
(1)[F40-OH1.1] [F44-OS1.1]
(2)[F44, F81-OH1.1] [F44, F81-OP1.1] [F44, F81-OS1.1]
(3)[F44, F81-OH1.1]
(4)[F40-OH1.1] [F44-OS1.1] [F10-OS3.7]
6.3.2.8. Make-up AirN/A
(1)[F50, F81-OH1.1] [F44, F81-OS3.4]
(2)[F81-OH1.1] [F44, F81-OS3.4]
(3)[F81-OH1.2]
6.3.2.9. Supply, Return, Intake and Exhaust Air OpeningsN/A
(1)[F81-OH1.2] [F30-OS3.1]
(2)[F41, F44, F81-OH1.1] [F44, F81-OS3.4]
(3)[F44, F81-OH1.1] [F44, F81-OS3.4]
(4)[F81-OH1.1]
(5)[F82, F81-OH1.1] [F82-OS3.4]
6.3.2.10. Exhaust Ducts and OutletsN/A
(1)[F44-OH1.1]
(2)[F44-OH1.1]
(3)[F81-OH1.1, OH1.2]
(4)[F81-OH1.1, OH1.2]
(5)[F81-OH1.1]
(6)[F81-OH1.1]
(7)[F81-OS1.1]
(8)[F52-OH1.1] [F01-OS1.1] [F01-OP1.1]
(9)[F52-OH1.1]
(10)[F81-OH1.1]
(11)[F44, F81-OH1.1] [F44, F81-OS1.1]
(12)[F44, F81-OH1.1]
(13)[F44, F81-OH1.1] [F81-OH1.2]
(14)[F40, F50-OH1.1]
(15)[F40, F50-OH1.1]
(16)[F40, F50-OH1.1]
6.3.2.11. Return-Air SystemN/A
(3)[F10-OS1.5]
(4)[F40-OH1.1] [F44-OS1.1] [F10-OS3.7]
(5)[F50, F81-OH1.1] [F44, F81-OS3.4]
6.3.2.12. Underground DuctsN/A
(1)(a) [F44, F81-OH1.2, OH1.3] (b) [F44, F81-OH1.1] (c) [F44, F81-OH1.1]
(2)[F81-OH1.1, OH1.2, OH1.3]
6.3.2.13. FiltersN/A
(1)[F80-OS1.1] [F80-OP1.1]
(2)[F30-OS3.3] [F4381, F4381-OH1.1]
6.3.2.14. Cleaning DevicesN/A
(1)[F40, F50-OH1.1]
(2)[F40, F43, F44, F50-OH1.1] [F44-OS3.4]
6.3.2.15. Evaporative Heat Rejection SystemN/A
(1)[F40, F41, F50-OH1.1]
(2)[F40, F41, F50-OH1.1]
(3)[F40, F41, F50-OH1.1]
(4)[F40, F41, F50-OH1.1]
(5)[F40, F41-OH1.1]
(6)[F40, F41-OH1.1]
(7)[F40, F41-OH1.1]
(8)[F46-OH2.2]
(9)[F40, F41-OH1.1]
(10)[F46, F81-OH2.1]
(11)[F41, F82-OH1.1] [F82-OS3.1]
6.3.2.16. Evaporative Air Coolers, Misters, Atomizers, Air Washers and HumidifiersN/A
(1)[F44, F50-OH1.1]
(2)[F40, F41, F50-OH1.1]
(3)[F40, F41, F50-OH1.1]
(4)[F40, F41, F50-OH1.1] [F40, F41, F50, F82-OH1.1]
(5)[F40, F41, F50-OH1.1]
(6)[F46-OH2.2]
6.3.2.17. Fans and Associated Air-Handling EquipmentN/A
(1)[F44, F81-OH1.1] [F44, F81-OS3.4]
(2)[F81-OH1.1]
6.3.3.1. Requirement for VentingN/A
(2)[F40, F44, F50-OH1.1]
6.3.3.2. Masonry or Concrete ChimneysN/A
(2)[F01-OS1.1] [F01-OP1.1]
6.3.3.3. Metal Smoke StacksN/A
(1)[F01-OS1.1] [F01-OP1.1]
6.3.3.4. Access LaddersN/A
(1)[F20, F80-OS3.1]
(2)[F30-OS3.1]
6.3.4.2. General VentilationN/A
(1)[F01-OS1.1] [F01-OP1.1] [F02-OP1.2] [F81, F82-OS1.1] [F02-OS1.2]
(2)[F11, F81-OS1.1]
6.3.4.3. Enclosure Exhaust VentilationN/A
(1)(a), (c), (d) [F01-OS1.1] (a) [F02-OS1.2] (a) [F02-OP1.2] (b) [F02-OS1.2] [F81-OS1.1] (e) [F12-OS1.1, OS1.2] (e) [F12-OP1.1, OP1.2]
6.3.4.4. Enclosure ConstructionN/A
(1)(a) [F01-OS1.1] Applies to portion of Code text: "… be constructed of … materials compatible with … the dangerous goods vapours and particles being exhausted," (a) [F80-OS1.1] Applies to portion of Code text: "… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted," (a) [F02-OS1.2] Applies to portion of Code text: "… be constructed of noncombustible materials …" (a) [F80-OS3.4] Applies to portion of Code text: "… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted," (a) [F02-OP1.2] Applies to portion of Code text: "… be constructed of noncombustible materials …" (b) [F82-OS1.1] [F02-OS1.2] (b) [F02-OP1.2]
(3)[F02-OS1.2] [F02-OP1.2]
6.4.1.2. Appliances Installed Outside the BuildingN/A
(1)[F81-OS1.1] [F81-OH1.1] [F81-OP1.1]
6.4.2.1. ClearancesN/A
(1)[F01-OS1.1] [F01-OP1.1]
6.4.3.1. Lining or BackingN/A
(1)[F01-OS1.1] [F01-OP1.1]
(2)[F01-OS1.1]
6.5.1.1. Insulation and CoveringsN/A
(2)[F20, F30-OS3.2, OS3.4]
(3)[F31-OS3.2]
6.6.1.1. Cooling UnitsN/A
(1)[F43, F81-OS3.4]
6.7.1.1. Piping Materials and InstallationN/A
(1)[F20-OS3.2, OS3.4]
(2)[F21-OH1.1]
(3)[F20-OS2.2]
6.7.1.2. ClearancesN/A
(1)[F01-OS1.1] [F01-OP1.1]
6.7.1.3. Surface TemperatureN/A
(1)[F31-OS3.2]
6.7.1.4. ProtectionN/A
(1)[F01-OS1.1] [F01-OP1.1]
6.7.2.1. Storage BinsN/A
(1)[F30, F31, F43-OS3.2, OS3.4]
(2)[F01-OS1.1] [F01-OP1.1]
6.8.1.1. Access OpeningsN/A
(1)[F36-OS3.6]
6.8.1.2. Openings in Air Duct SystemsN/A
(1)[F44, F81-OS3.4] [F81-OH1.1, OH1.2]
(2)[F82-OS1.1]
6.8.1.3. Odour Removal EquipmentN/A
(1)[F82-OH1.1]
(2)[F82-OH1.1]
6.9.1.2. Hazardous Gases, Dusts or LiquidsN/A
(1)[F01-OS1.1] [F01-OP1.1]
(2)[F01-OS1.1] [F01-OP1.1]
6.9.1.3. Commercial Cooking EquipmentN/A
(1)[F02, F81-OS1.2] [F02, F81-OP1.2]
6.9.3.1. Carbon Monoxide AlarmsN/A
(2)(a), (b), (d) [F44-OS3.4] (c) [F81-OS3.4]
(3)[F44-OS3.4]
(4)[F44-OS3.4]
(5)[F44-OS3.4]
6.9.4.1. Ash Storage BinsN/A
(1)[F01-OS1.1] [F01-OP1.1]
(2)[F01-OS1.1] [F01-OP1.1]

Table 7 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 7 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 7 of Division B
Acceptable SolutionsObjectives and Functional Statements
7.1.1B.2. Floor DrainsN/A
(1)[F62-OH1.3] [F62-OH2.1] [F62, F72-OP5]
(3)[F62-OH1.3] [F62-OH2.1] [F41-OH2.4] Applies to floor drains in garbage rooms. [F62, F72-OP5]
7.1.2.1. Sanitary Drainage SystemsN/A
(1)[F72-OH2.1]
(2)[F72-OH2.1] [F72-OP5]
7.1.2.2. Storm Drainage SystemsN/A
(1)[F72-OP5]
7.1.2.3. Water Distribution SystemsN/A
(1)[F46, F70-OH2.2]
7.1.2.4. Separate ServicesN/A
(1)[F70-OH2.1] [F81-OH2.2] Applies to water service pipe. [F81-OH2.6] Applies to drainage pipe. [F81-OP5]
(2)[F81-OH2.2] Applies to water service pipe. [F81-OH2.6] Applies to drainage pipe. [F81-OP5]
7.1.2.5. Private Sewers and Private Water SupplyN/A
(1)[F62, F70-OH2.1] [F81-OH2.2] [F81-OP5]
(2)[F62, F70-OH2.1] [F81-OH2.6] [F81-OP5]
7.1.3.1. Lighting and Ventilation RequirementsN/A
(1)[F30-OS3.1] Applies to the requirement for lighting. [F40, F41, F50-OH1.1] Applies to the requirement for ventilation.
7.1.3.2. AccessibilityN/A
(1)[F40-OH2.1] [F71-OH2.3] [F41, F81-OH2.4] [F82-OH2.1, OH2.2, OH2.3, OH2.4] Applies to the need for maintenance. [F81-OP5]
7.1.3A.1. Structural MovementN/A
(1)[F23-OS3.1] [F81-OH1.3, OH2.1, OH2.4, OH2.6]
7.2.1.1. Exposure of MaterialsN/A
(1)[F80-OH2.1, OH2.2, OH2.3, OH2.4] [F80-OP5]
(2)[F80-OH2.1] [F80-OP5]
7.2.1.2. Restrictions on Re-UseN/A
(1)[F41, F81-OH1.1] Applies to vent pipes. [F81-OH1.3] Applies to water pipes. [F81, F113-OH2.1] [F46, F70-OH2.2] [F71, F72-OH2.3] Applies to equipment. [F43-OS3.4] Applies to equipment. [F81, F113-OP5] Applies to drainage pipes. [F81-OP5] Applies to water pipes.
(2)[F70-OH2.2]
7.2.1.5. Withstanding PressureN/A
(1)[F20, F81, F113-OE] [F20, F81, F113-OH2.1, OH2.3] [F20, F81, F113-OP5]
7.2.1.6. Working Pressure of a Water Service PipeN/A
(1)[F20, F81-OH2.3] [F20-OP5]
7.2.2.1. Surface RequirementsN/A
(1)[F41-OH2.4]
7.2.2.2. Conformance to StandardsN/A
(0.1)[F80, F81-OH2.1, OH2.4] [F80, F81-OP5]
(1)[F80, F81-OH2.1, OH2.4] [F80, F81-OP5]
7.2.2.3. ShowersN/A
(1)[F80-OH2.1] [F80-OP5]
(2)[F80-OH2.1, OH2.4] [F40-OP5]
(3)[F45-OH2.1]
(4)[F45-OH2.1]
7.2.2.4. Concealed OverflowsN/A
(1)[F41, F81-OH2.1, OH2.4]
7.2.2.5. Water Closets in Public WashroomsN/A
(1)[F40-OH2.4]
7.2.2.6. LavatoriesN/A
(1)[F41, F81-OH2.1, OH2.4]
7.2.2.7. Trough UrinalsN/A
(1)[F40-OH2.1, OH2.4]
7.2.3.1. TrapsN/A
(1)[F40, F81-OH1.1]
(2)[F44, F81-OH1.1]
(3)[F81-OH2.1, OH2.3, OH2.4] [F81-OP5]
(4)[F81-OH1.1]
(5)[F81-OH1.1]
(6)[F81-OH1.1]
(8)[F81-OH1.1] [F81-OP5]
7.2.3.2. InterceptorsN/A
(1)[F81, F82-OH2.1, OH2.3, OH2.4]
(2)[F81-OH2.1, OH2.3, OH2.4]
(4)[F81-OP5]
7.2.3.3. Tubular TrapsN/A
(1)[F82-OH2.1, OH2.4] [F82-OP5]
7.2.4.1. T and Cross FittingsN/A
(1)[F81-OH2.1, OH2.4] [F81-OP5]
(2)[F81-OH2.1, OH2.4] [F81-OP5]
7.2.4.2. Sanitary T FittingsN/A
(1)[F81-OH2.1, OH2.4] [F81-OP5]
(2)[F81-OH2.1, OH2.4] [F81-OP5]
7.2.4.3. 90° ElbowsN/A
(1)[F81-OH2.1, OH2.4] [F81-OP5]
7.2.4.4. Fittings Restricted in UseN/A
(1)[F81-OH2.1, OH2.4] [F81-OP5]
7.2.4.5. Assembled Pipe or TubingN/A
(1)[F81-OH2.1, OH2.4] [F81-OP5]
7.2.5.1. Fibrocement Pipe and FittingsN/A
(1)[F20-OH2.1] [F20-OP5]
7.2.5.2. Concrete Pipe and FittingsN/A
(1)[F20, F80, F81-OH2.1, OH2.6] [F20, F80, F81-OP5]
(2)[F20, F80, F81-OH2.1, OH2.6] [F20, F80, F81-OP5]
(3)[F20, F80, F81-OH2.1, OH2.6] [F20, F80, F81-OP5]
(4)[F20, F80, F81-OH2.1, OH2.6] [F20, F80, F81-OP5]
(5)[F20, F80, F81-OH2.1, OH2.6] [F20, F80, F81-OP5]
7.2.5.3. Vitrified Clay Pipe and FittingsN/A
(1)[F20, F80, F81-OH2.1, OH2.6] [F20, F80, F81-OP5]
(2)[F20, F80, F81-OH2.1, OH2.6] [F20, F80, F81-OP5]
(3)[F20, F80, F81-OH2.1, OH2.6] [F20, F80, F81-OP5]
7.2.5.4. Polyethylene Pipe and FittingsN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5]
(2)[F20, F81-OH2.2] [F20, F81-OP5]
(3)[F20, F81-OH2.2] [F20, F81-OP5]
7.2.5.5. Polyethylene Pipe Used UndergroundN/A
(1)[F20, F81-OH2.1, OH2.6] [F20, F81-OP5]
7.2.5.6. Crosslinked Polyethylene Pipe and FittingsN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5]
7.2.5.7. PVC Pipe and FittingsN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5]
(2)[F20, F81-OH2.2] [F20, F81-OP5]
7.2.5.8. CPVC Pipe, Fittings and Solvent CementsN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5]
(2)[F20, F81-OH2.2] [F20, F81-OP5]
7.2.5.9. Plastic Pipe, Fittings and Solvent Cement Used UndergroundN/A
(1)[F20, F80, F81, F113-OH2.1, OH2.6] [F20, F80, F81, F113-OP5]
(2)[F20, F80, F81, F113-OH2.1, OH2.6] [F20, F80, F81, F113-OP5]
7.2.5.10. Transition Solvent CementN/A
(1)[F20, F80, F81, F113-OH2.1, OH2.6] [F20, F80, F81, F113-OP5]
(2)[F20, F80, F81, F113-OH2.1, OH2.6] [F20, F80, F81, F113-OP5]
7.2.5.11. Plastic Pipe, Fittings and Solvent Cement Used in BuildingsN/A
(1)[F20, F43, F81-OH1.1] Applies to venting system. [F20, F80, F81, F113-OH2.1] [F20, F80, F81, F113-OP5]
(1.1)[F20, F80, F81-OH1.3] [F20, F80, F81-OP5]
(1.2)[F20-OH1.3] [F20-OP5]
7.2.5.12. Polyethylene/Aluminum/Polyethylene Composite Pipe and FittingsN/A
(1)[F20-OH2.1, OH2.2, OH2.3] [F20-OP5]
(2)[F20-OH2.1, OH2.2, OH2.3] [F20-OP5]
(3)[F20-OH2.1, OH2.2, OH2.3] [F20-OP5]
(4)[F20-OH2.1, OH2.2, OH2.3] [F20-OP5]
7.2.5.13. Crosslinked Polyethylene/Aluminum/Polyethylene Composite Pipe and FittingsN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5]
7.2.5.14. Polypropylene Pipe and FittingsN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5] [F20, F43, F81-OH1.1] Applies to venting system. [F20, F80, F81, F113-OH2.1] [F20, F80, F81, F113-OP5]
(2)[F20, F81-OH2.2] [F20, F81-OP5]
7.2.5.15. Polyethylene of Raised Temperature Tube and FittingsN/A
(1)[F20, F70, F80-OH2.2] [F20, F70, F80-OP5]
(2)[F80, F81-OH2.1] [F20, F70, F80-OP5]
7.2.5.16. Cellular Core PVC Pipe and FittingsN/A
(1)[F20-OH2.1, OH2.2, OH2.3] [F20-OP5]
(2)[F20-OH2.1] [F20-OP5]
7.2.6.1. Cast-Iron Drainage and Vent Pipe and FittingsN/A
(1)[F20-OH2.1, OH2.3]
(2)[F20-OH2.2]
7.2.6.2. Maintenance Holes and Catch BasinsN/A
(1)[F81-OH1.1] [F20-OS3.1]
7.2.6.3. Threaded Cast Iron Drainage FittingsN/A
(1)[F20, F80, F81, F113-OH2.1, OH2.6] [F20, F80, F81, F113-OP5]
(2)[F20, F81-OH2.2] [F20, F81-OP5]
7.2.6.4. Cast Iron Water PipeN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5]
(2)[F20, F81-OH2.2] [F20, F81-OP5]
(3)[F20, F81-OH2.2] [F20, F81-OP5]
(4)[F20, F81-OH2.2] [F20, F81-OP5]
7.2.6.5. Screwed Cast Iron Water FittingsN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5]
(2)[F20, F81-OH2.2] [F20, F81-OP5]
(3)[F81-OH2.1]
7.2.6.6. Screwed Malleable Iron Water FittingsN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5]
(2)[F20, F81-OH2.2] [F20, F81-OP5]
(3)[F81-OH2.1]
7.2.6.7. Steel PipeN/A
(1)[F43, F81-OH1.1] Applies to venting system. [F80, F81, F113-OH2.1] Applies to drainage system. [F46, F80, F81-OH2.2] Applies to water piping. [F80, F81, F113-OP5] Applies to drainage system. [F46, F80, F81-OP5] Applies to water piping.
(3)[F46, F80, F81-OH2.2] [F46, F80, F81-OP5]
(4)[F43, F81-OH1.1] Applies venting system. [F80, F81, F113-OH2.1] Applies to drainage system. [F80, F81, F113-OP5] Applies to drainage system.
(5)[F80, F81, F113-OH2.1] [F80, F81, F113-OP5]
(6)[F43, F81-OH1.1] Applies to venting system. [F80, F81, F113-OH2.1] Applies to drainage system. [F80, F81, F113-OP5] Applies to drainage system.
7.2.6.8. Corrugated Steel Pipe and CouplingsN/A
(1)[F20, F80, F81-OH1.3] [F20, F80, F81-OP5]
(2)[F80, F81-OH1.3] [F80, F81-OP5]
(3)[F80, F81-OH1.3] [F80, F81-OP5] (b) [F20-OH1.3] (b) [F20-OP5]
7.2.6.9. Sheet Metal LeadersN/A
(1)[F80, F81-OH1.3] [F80, F81-OP5]
7.2.6.10. Stainless Steel PipeN/A
(1)[F80-OH2.1] Applies to drainage systems and venting systems. [F46, F80-OH2.2] Applies to water systems. [F80-OP5]
(2)[F20-OP5] [F80-OH2.1] Applies to drainage systems and venting systems. [F46, F80-OH2.2] Applies to water systems.
7.2.6.11. Stainless Steel Butt Weld Pipe FittingsN/A
(1)[F80-OH2.1] Applies to drainage systems and venting systems. [F46, F80-OH2.2] Applies to water systems. [F80-OP5]
(2)[F80-OH2.1] Applies to drainage systems and venting systems. [F46, F80-OH2.2] Applies to water systems. [F80-OP5]
7.2.6.12. Stainless Steel Pipe FlangesN/A
(1)[F80-OH2.1] Applies to drainage systems and venting systems. [F46, F80-OH2.2] Applies to water systems. [F80-OP5]
(2)[F80-OH2.1] Applies to drainage systems and venting systems. [F46, F80-OH2.2] Applies to water systems. [F80-OP5]
7.2.6.13. Stainless Steel Threaded FittingsN/A
(1)[F20-OP5] [F80-OH2.1] Applies to drainage systems and venting systems. [F46, F80-OH2.2] Applies to water systems.
(2)[F20-OP5] [F80-OH2.1] Applies to drainage systems and venting systems. [F46, F80-OH2.2] Applies to water systems.
7.2.6.14. Stainless Steel TubeN/A
(1)[F46-OH2.2] [F80-OP5]
(2)[F46-OH2.2] [F80-OP5]
7.2.6.15. Stainless Steel Pipe and TubeN/A
(1)[F80-OH2.1, OH2.2, OH2.3]
7.2.7.1. Copper and Brass PipeN/A
(1)[F43, F81-OH1.1] Applies to venting system. [F80, F81, F113-OH2.1] Applies to drainage system. [F46, F80, F81-OH2.2] Applies to water piping. [F80, F81, F113-OP5] Applies to drainage system. [F46, F80, F81-OP5] Applies to water piping.
(2)[F43, F81-OH1.1] Applies to venting system. [F80, F81, F113-OH2.1] Applies to drainage system. [F46, F80, F81-OH2.2] Applies to water piping. [F80, F81, F113-OP5] Applies to drainage system. [F46, F80, F81-OP5] Applies to water piping.
7.2.7.2. Brass or Bronze Pipe Flanges and Flanged FittingsN/A
(1)[F43, F81-OH1.1] Applies to venting system. [F80, F81, F113-OH2.1] Applies to drainage system. [F46, F80, F81-OH2.2] Applies to water piping. [F80, F81, F113-OP5] Applies to drainage system. [F46, F80, F81-OP5] Applies to water piping.
7.2.7.3. Brass or Bronze Threaded Water FittingsN/A
(1)[F46, F80, F81-OH2.2] [F46, F80, F81-OP5]
(2)[F80-OH2.1]
7.2.7.4. Copper TubeN/A
(1)[F20, F43, F81-OH1.1] Applies to venting system. [F20, F80, F81, F113-OH2.1] Applies to drainage system. [F20, F46, F80, F81-OH2.2] Applies to water piping. [F20, F80, F81, F113-OP5] Applies to drainage system. [F20, F46, F80, F81-OP5] Applies to water piping.
(2)[F20, F43, F81-OH1.1] Applies to venting system. [F20, F80, F81, F113-OH2.1] Applies to drainage system. [F20, F46, F80, F81-OH2.2] Applies to water piping. [F20, F80, F81, F113-OP5] Applies to drainage system. [F20, F46, F80, F81-OP5] Applies to water piping.
(3)[F80-OH2.1, OH2.4]
(4)[F20, F46, F80, F81, F113-OH2.1, OH2.2] [F20, F46, F80, F81, F113-OP5]
(5)[F20, F46, F80, F81, F113-OH2.1, OH2.2] [F20, F46, F80, F81, F113-OP5]
7.2.7.5. Solder-Joint Drainage FittingsN/A
(1)[F20, F80, F81, F113-OH2.1] [F20, F80, F81, F113-OP5]
(2)[F20, F80, F81-OH2.2] [F20, F80, F81-OP5]
7.2.7.6. Solder-Joint Water FittingsN/A
(1)[F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OP5]
(2)[F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OP5]
7.2.7.7. Flared-Joint Fittings for Copper Tube Water SystemsN/A
(1)[F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OP5]
(2)[F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OP5]
7.2.7.8. Lead Waste Pipe and FittingsN/A
(1)[F20, F80, F81, F113-OH2.1] Applies to building sewer. [F20, F46, F80, F81-OH2.2] Applies to water piping. [F20, F80, F81, F113-OP5] Applies to drainage system. [F20, F46, F80, F81-OP5] Applies to water piping.
(2)[F81, F113-OH2.1] [F81, F113-OP5]
7.2.8.1. Pipe and FittingsN/A
(1)[F20, F43, F81-OH1.1] Applies to venting system. [F20, F80, F81, F113-OH2.1] Applies to drainage system. [F20, F80, F81, F113-OP5] Applies to drainage system.
7.2.9.1. Cement MortarN/A
(1)[F20, F43, F81-OH1.1] Applies to venting system. [F20, F80, F81, F113-OH2.1] Applies to drainage system. [F20, F46, F80, F81-OH2.2] Applies to water piping. [F20, F80, F81, F113-OP5] Applies to drainage system. [F20, F46, F80, F81-OP5] Applies to water piping.
7.2.9.2. Solder and FluxesN/A
(1)[F20, F43, F81-OH1.1] Applies to venting system. [F20, F80, F81, F113-OH2.1] Applies to drainage system. [F20, F46, F80, F81-OH2.2] Applies to water piping. [F20, F80, F81, F113-OP5] Applies to drainage system. [F20, F46, F80, F81-OP5] Applies to water piping.
(2)[F46-OH2.2]
(3)[F80-OH2.1, OH2.2]
(4)[F80-OH2.1, OH2.3]
7.2.10.1. Floor FlangesN/A
(1)[F20, F80, F81, F113-OH2.1] [F20, F80, F81, F113-OP5]
(2)[F20, F80, F81, F113-OH2.1] [F20, F80, F81, F113-OP5]
(3)[F20, F80, F81, F113-OH2.1] [F20, F80, F81, F113-OP5]
(4)[F20, F80, F81, F113-OH2.1] [F20, F80, F81, F113-OP5]
7.2.10.2. Screws, Bolts, Nuts and WashersN/A
(1)[F80-OH2.1] [F80-OP5]
7.2.10.3. Cleanout FittingsN/A
(1)[F80-OH2.1, OH2.3] Applies to drainage systems. [F46-OH2.2] Applies to water systems.
(2)[F43, F81-OH1.1] Applies to venting system. [F81-OH2.1] Applies to drainage system. [F81-OP5] Applies to drainage system.
(3)[F80-OH2.1]
7.2.10.4. Mechanical CouplingsN/A
(1)[F20, F43, F81-OH1.1] Applies to venting system. [F20, F80, F81, F113-OH2.1] Applies to drainage system. [F20, F46, F80, F81-OH2.2] Applies to water piping. [F20, F80, F81, F113-OP5] Applies to drainage system. [F20, F46, F80, F81-OP5] Applies to water piping.
(2)[F20, F43, F81-OH1.1] Applies to venting system. [F20, F80, F81, F113-OH2.1] Applies to drainage system. [F20, F80, F81, F113-OP5] Applies to drainage system.
7.2.10.5. Saddle HubsN/A
(1)[F81-OH2.1] [F81-OP5]
7.2.10.6. Valves, Supply and Waste FittingsN/A
(1)[F80-OP5]
(2)[F131-O1.2]
(6)[F80-OH2.1, OH2.3]
(7)[F81-OP5] [F46-OH2.2]
7.2.10.7. Water Temperature ControlN/A
(1)[F31-OS3.2]
(4)[F31-OS3.2]
(5)[F31-OS3.2]
7.2.10.7A. Temperature Control DevicesN/A
(1)[F31-OH1.2] [F31-OS3.2]
7.2.10.7B. ShowersN/A
(1)[F31-OH1.2] [F30-OS3.1] [F31-OS3.2]
(4)[F31-OH1.2] [F31-OS3.2]
7.2.10.7C. Linings and Coatings of Domestic Water TanksN/A
(1)[F20, F46, F80, F81-OH2.1, OP5]
7.2.10.8. Direct Flush ValvesN/A
(1)(a), (b), (c) [F130-OR1] (a), (b) [F80, F81-OP5] (c), (d) [F80-OH2.1] [F81-OH2.4] (d) [F46-OH2.2]
7.2.10.9. Drinking Fountain BubblersN/A
(1)[F40, F46-OH2.4]
(2)[F41, F46-OH2.2] [F130-OR1]
7.2.10.10. Back-Siphonage Preventers and Backflow PreventersN/A
(1)[F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OP5]
(2)[F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OP5]
7.2.10.11. Relief ValvesN/A
(1)[F20, F46, F80, F81-OH2.2] [F20, F31, F46, F80, F81-OP5] [F31-OS3.2]
7.2.10.12. Reducing ValvesN/A
(1)[F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OP5]
7.2.10.13. Solar Domestic Hot WaterN/A
(1)[F46-OH2.2] [F80, F81-OP5] [F81-OS3.2]
7.2.10.14. Vent Pipe FlashingN/A
(1)[F61, F80-OH1.3] [F61, F80-OP2.3]
(2)[F61, F80-OH1.3] [F61, F80-OP2.3]
7.2.10.15. Water Hammer ArrestersN/A
(1)[F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OP5]
7.2.10.16. Air Admittance ValvesN/A
(1)[F20, F43, F81-OH1.1]
7.2.10.17. Drinking Water Treatment SystemsN/A
(1)[F46-OH2.2] [F40-OS3.4] [F70-OP5]
7.2.10.18. Flexible Water ConnectorsN/A
(1)[F81-OP5] [F46-OH2.2]
7.2.11.1. Design, Construction, Installation and TestingN/A
(1)[F20, F46, F80, F81-OH2.2] [F12-OP1.4] [F20, F46, F80, F81-OP5] [F12-OS1.4]
7.2.11.2. Certification or ConformanceN/A
(1)[F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OP5]
7.2.11.3. Tracer WireN/A
(1)[F82-OH2.2] [F82-OP5]
7.2.11.4. Required Check ValveN/A
(1)[F46-OH2.2]
(2)[F46-OH2.2]
7.3.2.1. Caulked Lead Drainage JointsN/A
(1)[F43, F81-OH1.1] Applies to venting system. [F80, F81-OH2.1] Applies to drainage system. [F80, F81-OP5] Applies to drainage system.
(2)[F80-OH2.1]
(3)[F80, F81-OH2.1] Applies to drainage system. [F80, F81-OP5] Applies to drainage system.
(4)[F81-OH2.1]
7.3.2.2. Wiped JointsN/A
(1)[F43, F80, F81-OH1.1] Applies to venting system. [F80, F81-OH2.1] Applies to drainage system. [F80, F81-OP5] Applies to drainage system.
(2)[F43, F80, F81-OH1.1] Applies to venting system. [F80, F81-OH2.1] Applies to drainage system. [F80, F81-OP5] Applies to drainage system.
(3)[F43, F80, F81-OH1.1] Applies to venting system. [F80, F81-OH2.1] Applies to drainage system. [F80, F81-OP5] Applies to drainage system.
7.3.2.3. Screwed JointsN/A
(1)[F81-OH2.1] Applies to drainage system. [F46, F81-OH2.2] Applies to water piping. [F81-OP5] Applies to drainage system.
(2)[F46, F81-OH2.2] Applies to water piping.
7.3.2.4. Solder JointsN/A
(1)[F43, F80, F81-OH1.1] Applies to venting system. [F80, F81-OH2.1] Applies to drainage system. [F20, F46, F81-OH2.2] Applies to water piping. [F20, F46, F81-OP5] Applies to water piping. [F20, F80, F81-OP5] Applies to drainage system.
7.3.2.5. Flared JointsN/A
(1)[F43, F81-OH1.1] Applies to venting system. [F81-OH2.1] Applies to drainage system. [F20, F46, F81-OH2.2] Applies to water piping. [F20, F46, F81-OP5] Applies to water piping. [F20, F81-OP5] Applies to drainage system.
(2)[F43, F81-OH1.1] Applies to venting system. [F81-OH2.1] Applies to drainage system. [F20, F46, F81-OH2.2] Applies to water piping. [F20, F46, F81-OP5] Applies to water piping. [F20, F81-OP5] Applies to drainage system.
7.3.2.6. Mechanical JointsN/A
(1)[F43, F81-OH1.1] Applies to venting system. [F81-OH2.1] Applies to drainage system. [F20, F46, F81-OH2.2] Applies to water piping. [F20, F46, F81-OP5] Applies to water piping. [F20, F81-OP5] Applies to drainage system.
7.3.2.7. Cold-Caulked JointsN/A
(1)[F20, F43, F81-OH1.1] Applies to bell and spigot joints in venting systems. [F20, F81-OH2.1] Applies to bell and spigot joints in drainage systems. [F20, F46, F81-OH2.2] Applies to water piping. [F20, F46, F81-OP5] Applies to water piping. [F20, F81-OP5] Applies to bell and spigot joints in drainage systems.
(2)[F20, F43, F81-OH1.1] Applies to bell and spigot joints in venting systems. [F20, F81-OH2.1] Applies to bell and spigot joints in drainage systems. [F20, F46, F81-OH2.2] Applies to water piping. [F20, F46, F81-OP5] Applies to water piping. [F20, F81-OP5] Applies to bell and spigot joints in drainage systems.
(3)[F20, F81-OH2.1] Applies to bell and spigot joints in drainage systems. [F20, F81-OP5] Applies to bell and spigot joints in drainage systems.
7.3.2.8. Stainless Steel Welded JointsN/A
(1)[F20, F81-OH2.1, OH2.2, OH2.3]
(2)[F20, F81-OH2.1, OH2.2, OH2.3]
7.3.3.1. Drilled and Tapped JointsN/A
(1)[F81-OH2.1] Applies to drainage piping. [F20, F46, F81-OH2.2] Applies to water piping. [F20, F46, F81-OP5] Applies to water piping. [F20, F81-OP5] Applies to drainage piping.
(4)[F81-OH2.1] [F81-OP5]
7.3.3.2. Extracted TeesN/A
(1)[F81-OH2.1, OH2.3] [F20-OP5]
7.3.3.3. Prohibition of Welding of Pipes and FittingsN/A
(1)[F20-OH1.1] [F20-OH2.1, OH2.2]
(2)[F80-OH2.2] [F80-OP5]
7.3.3.4. Unions and Slip JointsN/A
(1)[F81-OH1.1] [F81-OH2.1]
(2)[F81-OH1.1] [F81-OH2.1]
7.3.3.5. Increaser or ReducerN/A
(1)[F81-OH1.1] [F70, F80-OH2.2]
7.3.3.6. Dissimilar MaterialsN/A
(1)[F80-OH1.1] [F80-OH2.1] [F80-OP5]
7.3.3.7. Connection of Roof Drain to LeaderN/A
(1)[F21, F61, F81-OP5]
7.3.3.8. Connection of Floor Outlet FixturesN/A
(1)[F80-OH2.1] [F80-OP5]
(2)[F80-OH2.1] [F80-OP5]
(4)[F20-OH2.1] [F20-OP5] [F20-OS3.1]
(5)[F20, F43-OH2.1] [F20, F30-OS3.1]
(6)[F81-OH2.1]
(7)[F21-OH2.1] [F21-OP5]
7.3.3.9. Expansion and ContractionN/A
(1)[F21-OH1.1] [F21-OH2.1] [F21-OH2.2] [F21-OP5]
7.3.3.10. Copper TubeN/A
(1)[F20-OH1.1] [F20-OH2.1] [F20-OH2.2] [F20-OP5]
(2)[F20-OH1.1] [F20-OH2.1] [F20-OH2.2] [F20-OP5]
7.3.3.11. Indirect ConnectionsN/A
(1)[F81-OH2.2, OH2.4]
(2)[F81-OH2.2, OH2.4]
7.3.3.12. Copper Joints Used UndergroundN/A
(1)[F20, F80, F81, F113-OP5] Applies to drainage pipe. [F20, F46, F80, F81-OP5] Applies to water pipe.
(2)[F80-OP5]
7.3.4.1. Capability of SupportN/A
(1)[F20-OH1.1] [F20-OH2.1, OH2.2] [F20-OP5] [F20-OS3.1]
(2)[F20-OH2.1] [F20-OP5] [F20-OS3.1]
(3)[F20-OH2.1] [F20-OP5] [F20-OS3.1]
7.3.4.2. Independence of SupportN/A
(1)[F20-OH2.1] [F20-OP5] [F20-OS3.1]
7.3.4.3. Insulation of SupportN/A
(1)[F80-OH1.1] [F80-OH2.1, OH2.2] [F80-OP5] [F80-OS3.1]
(2)[F80-OH2.1, OH2.3] [F80-OS3.1] [F80-OP5]
7.3.4.4. Support for Vertical PipingN/A
(1)[F20-OH1.1] Applies to vent piping. [F20-OH2.1] Applies to drainage piping. [F20-OH2.2] Applies to water piping. [F20-OP5] [F20-OS3.1]
(2)[F20-OH1.1] Applies to vent piping. [F20-OH2.1] Applies to drainage piping. [F20-OH2.2] Applies to water piping. [F20-OP5] [F20-OS3.1]
7.3.4.5. Support for Horizontal PipingN/A
(1)[F20-OH1.1] Applies to vent piping. [F20, F81-OH2.1] Applies to drainage piping. [F20-OH2.2] Applies to water piping. [F20-OP5] [F20-OS3.1]
(2)[F20-OH1.1] Applies to vent piping. [F20, F81-OH2.1] Applies to drainage piping. [F20-OH2.2] Applies to water piping. [F20-OP5] [F20-OS3.1]
(3)[F20-OH1.1] Applies to vent piping. [F20, F81-OH2.1] Applies to drainage piping. [F20-OH2.2] Applies to water piping. [F20-OP5] [F20-OS3.1]
(4)[F81-OP5] [F81-OS3.1]
(5)[F20-OH1.1] Applies to vent piping. [F20, F81-OH2.1] Applies to drainage piping. [F20-OH2.2] Applies to water piping. [F20-OP5] [F20-OS3.1]
(6)[F20-OH1.1] Applies to vent piping. [F20, F81-OH2.1] Applies to drainage piping. [F20-OH2.2] Applies to water piping. [F20-OP5] [F20-OS3.1]
7.3.4.6. Support for Underground Horizontal PipingN/A
(1)[F20-OE] Applies to drainage piping. [F20, F81-OH2.1] Applies to drainage piping. [F20-OH2.2] Applies to water piping. [F20-OP5] [F20-OS3.1]
(2)[F20-OE] Applies to drainage piping. [F20-OH1.1] Applies to vent piping. [F20, F81-OH2.1] Applies to drainage piping. [F20-OH2.2] Applies to water piping. [F20-OP5] [F20-OS3.1]
7.3.4.7. Support for Vent Pipe Above a RoofN/A
(1)[F20-OH1.1] [F61, F81-OP2.3] [F81-OS3.1]
7.3.4.8. Compression FittingsN/A
(1)[F20-OH2.1, OH2.2] [F20-OP5] [F20-OS3.1]
7.3.4.9. Thrust Restraint of Water Service PipesN/A
(1)[F20, F81-OH2.2] [F20, F81-OP5]
(2)[F20, F81-OH2.2]
(3)[F20, F81-OH2.2]
(4)[F20, F81-OH2.2]
7.3.5.1. Backfill of Pipe TrenchN/A
(1)[F20-OE] [F81-OH2.1] [F81-OP5]
7.3.5.2. Protection of Non-Metallic PipeN/A
(1)[F20-OE] [F81-OH2.1] [F81-OP5]
7.3.5.3. Isolation from LoadsN/A
(1)[F20-OE] Applies to underground drainage piping. [F81-OH2.1] [F81-OP5]
7.3.5.4. Protection from FrostN/A
(1)[F20-OE] Applies to underground drainage piping. [F81-OH2.1] [F81-OP5]
7.3.5.5. Protection from Mechanical DamageN/A
(1)[F81-OH1.1] Applies to venting system. [F81-OH2.1] Applies to drainage system. [F81-OH2.2] Applies to water system. [F81-OP5]
7.3.5.6. Protection from CondensationN/A
(1)[F63-OH2.4] [F63-OP2.3]
7.3.5.7. Spatial SeparationN/A
(1)[F46-OH2.2] [F46-OP5]
(2)[F46-OH2.2] [F46-OP5]
(4)[F46-OH2.2] [F46-OP5]
7.3.6.1. Tests and Inspection of Drainage or Venting SystemsN/A
(1)[F81-OH1.1] Applies to venting systems. [F81-OH2.1] Applies to drainage systems. [F81-OP5] Applies to drainage systems.
(2)[F81-OH1.1] Applies to venting systems. [F81-OH2.1] Applies to drainage systems. [F81-OP5] Applies to drainage systems.
(3)[F81-OH1.1] Applies to venting systems. [F81-OH2.1] Applies to drainage systems. [F81-OP5] Applies to drainage systems.
(4)[F81-OH1.1] Applies to venting systems. [F81-OH2.1] Applies to drainage systems. [F81-OP5] Applies to drainage systems.
(5)[F81-OH2.1] Applies to drainage systems.
(6)[F22-OS2.6] [F36-OS3.6]
7.3.6.2. Tests of Pipes in drainage systemsN/A
(1)[F81-OE] Applies to underground drainage piping. [F81-OH2.1] [F81-OP5] Applies to drainage systems.
7.3.6.3. Tests of Venting SystemsN/A
(1)[F81-OH1.1]
7.3.6.4. Water Pressure TestsN/A
(1)[F81-OH1.1] Applies to venting systems. [F81-OH2.1] Applies to drainage systems. [F81-OP5] Applies to drainage systems.
(2)[F81-OH1.1] Applies to venting systems. [F81-OH2.1] Applies to drainage systems. [F81-OP5] Applies to drainage systems.
7.3.6.5. Air Pressure TestsN/A
(1)[F81-OH1.1] Applies to venting systems. [F81-OH2.1] Applies to drainage systems. [F81-OP5] Applies to drainage systems.
7.3.6.6. Final TestsN/A
(1)[F81-OH1.1] Applies to venting systems. [F81-OH2.1] Applies to drainage systems. [F81-OP5] Applies to drainage systems.
7.3.6.7. Ball TestsN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
7.3.7.1. Application of TestsN/A
(1)[F81-OP5]
(3)[F81-OP5]
(4)[F81-OP5]
7.3.7.2. Tests of Potable Water SystemsN/A
(1)[F20-OP5]
7.3.7.3. Water TestsN/A
(1)[F81-OP5]
(2)[F46-OH2.2]
7.4.2.1. Connections to Sanitary Drainage SystemsN/A
(1)[F81-OH1.1] [F41, F43-OH2.1, OH2.4]
(2)[F81-OH1.1] [F43-OH2.1, OH2.4]
(3)[F81-OH1.1]
(4)[F81-OH1.1]
(5)[F81-OH1.1]
7.4.2.2. Connection of Overflows from Rainwater TanksN/A
(1)[F40-OE]
7.4.2.3. Direct ConnectionsN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1, OH2.4]
(3)[F81-OH2.4]
(4)[F81-OH2.4]
7.4.3.1. Plumbing FixturesN/A
(1)[F41-OH1.1] [F40, F41-OH2.1, OH2.4] [F80-OP2.3]
7.4.3.2. Restricted Locations of Indirect Connections and TrapsN/A
(1)[F81-OH2.1, OH2.4]
7.4.3.3. Equipment Restrictions Upstream of InterceptorsN/A
(1)[F81-OH2.1]
7.4.3.4. Fixtures Located in Chemical Storage LocationsN/A
(1)[F44-OE] [F44-OH5] [F01-OP1.1] [F81-OP2.3] [F01, F81-OS1.1] [F32-OS3.3] [F44-OS3.4]
7.4.3.5. Macerating ToiletN/A
(1)[F72-OH2.3]
7.4.3.6. Drains Serving Elevator PitsN/A
(1)[F43-OH1.1] [F43-OH2.1] [F62-OP2.3] [F62-OP5]
7.4.4.1. Sewage TreatmentN/A
(1)[F81-OE] Applies to underground drainage piping. [F81-OH2.1] [F81-OP2.3] [F81-OP5] [F44-OS3.4]
7.4.4.2. Protection for Drainage SystemN/A
(1)[F81-OE] Applies to underground drainage piping. [F81-OH2.1] [F81-OH5]
7.4.4.3. InterceptorsN/A
(1)[F81, F112-OE]. [F111-OE] Applies to drainage systems served by a sewage system. [F81-OH2.1]
(2)[F44, F81, F112-OE]. [F111-OE] Applies to drainage systems served by a sewage system. [F81-OH2.1] [F44-OH5] [F01-OP1.1] [F01-OS1.1]
(3)[F81-OH2.1] [F111-OE] Applies to drainage systems served by a sewage system.
(4)[F44-OE] Applies to oil interceptors. [F81, F112-OE] [F111-OE] Applies to drainage systems served by a sewage system. [F81-OH2.1] [F44-OH5] Applies to oil interceptors. [F01-OP1.1] Applies to oil interceptors. [F01-OS1.1] Applies to oil interceptors.
(5)[F44-OE] Applies to oil interceptors. [F81, F112-OE] [F111-OE] Applies to drainage systems served by a sewage system. [F81-OH2.1] [F44-OH5] Applies to oil interceptors. [F01-OP1.1] Applies to oil interceptors. [F01-OS1.1] Applies to oil interceptors.
(6)[F81, F112-OE] [F111-OE] Applies to drainage systems served by a sewage system. [F81-OH2.1]
(7)[F81, F112-OE] [F111-OE] Applies to drainage systems served by a sewage system. [F81-OH2.1]
(8)[F44-OE] Applies to oil interceptors. [F81, F112-OE] [F111-OE] Applies to drainage systems served by a sewage system. [F81-OH2.1] [F44-OH5] Applies to oil interceptors. [F01-OP1.1] Applies to oil interceptors. [F01-OS1.1] Applies to oil interceptors.
7.4.4.4. Neutralizing and Dilution TanksN/A
(1)[F40-OE] [F80-OH2.1] [F40-OH5] [F81-OP2.3] [F80-OP5] [F40, F80-OS3.4]
(2)[F40-OE] [F80-OH2.1] [F40-OH5] [F81-OP2.3] [F80-OP5] [F40, F80-OS3.4]
7.4.5.1. Traps for Sanitary Drainage SystemsN/A
(1)[F81-OH1.1] [F42-OH2.5]
(6)[F81-OH1.1] [F42-OH2.5]
7.4.5.2. Traps for Storm Drainage SystemsN/A
(1)[F81-OH1.1]
(2)[F81-OH1.1]
7.4.5.3. Connection of Subsoil Drainage Pipe to a Sanitary Drainage SystemN/A
(1)[F40-OH1.1] [F40-OH2.1]
(3)[F81-OH1.1] [F81-OH2.1]
7.4.5.4. Location and Cleanout for Building TrapsN/A
(1)[F81-OH2.1]
7.4.5.5. Trap SealsN/A
(1)[F81-OH1.1] [F42-OH2.5]
(2)[F81-OH1.1] [F42-OH2.5]
7.4.6.1. Separate SystemsN/A
(1)[F40-OR1]
(3)[F81-OH1.1] [F41, F81-OH2.1]
7.4.6.2. Location of Soil or Waste PipesN/A
(1)[F81-OH2.1, OH2.2, OH2.4] (a), (b) [F46-OH2.2]
7.4.6.3. Sumps or TanksN/A
(1)[F81-OH2.1]
(2)[F81-OH1.1] [F81-OH2.1]
(3)[F40, F81-OH2.1] [F40, F81-OH1.1]
(4)[F72-OH2.1] [F81-OH2.1]
(5)[F81-OH2.1]
(6)[F81-OH2.1]
(7)[F81-OH2.1]
(8)[F81-OH2.1]
(9)[F81-OH2.1]
7.4.6.4. Protection from BackflowN/A
(1)[F81-OH1.1] [F81-OH2.1]
(2)[F81-OH1.1] [F81-OH2.1]
(3)[F81-OH2.1]
(5)[F40-OH1.1] [F40-OH2.1]
7.4.6.5. Mobile Home Sewer ServiceN/A
(1)[F81-OH2.1]
7.4.7.1. Cleanouts for Drainage SystemsN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
(3)[F81-OH2.1]
(4)[F81-OH2.1]
(5)[F81-OH2.1]
(6)[F81-OH2.1]
(7)[F81-OH2.1]
(8)[F81-OH2.1]
(9)[F81-OH2.1]
(10)[F81-OH2.1]
7.4.7.2. Size and Spacing of CleanoutsN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
(3)[F81-OH2.1]
(4)[F81-OH2.1]
(5)[F81-OH2.1]
(6)[F81-OH2.1]
(7)[F81-OH2.1]
7.4.7.3. ManholesN/A
(1)[F20-OS3.1]
(2)(a), (c) [F81-OH1.1] (a), (c) [F81-OS1.1] (b) [F20, F30, F80-OS3.1]
(3)[F30-OS3.1] [F36-OS3.6]
(4)[F81-OH2.1]
7.4.7.4. Location of CleanoutsN/A
(1)[F81-OH2.1]
(2)[F81-OH1.1] [F30-OS3.1]
(4)[F81-OH2.1]
(4.1)[F81-OH2.1]
(5)[F43-OH2.1] [F43-OH5]
7.4.8.1. Minimum SlopeN/A
(1)[F81-OH2.1]
(3)[F81-OH2.1]
7.4.8.2. Length of Fixture Outlet PipesN/A
(1)[F81-OH1.1]
7.4.9.1. No Reduction in SizeN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
7.4.9.2. Serving Water ClosetsN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
(3)[F81-OH2.1]
(4)[F81-OH2.1]
(5)[F81-OH1.1, OH2.1, OP5]
7.4.9.3. Size of Fixture Outlet PipesN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
(3)[F81-OH1.1] [F81-OP5]
7.4.9.4. Minimum Size of Building Drains and SewersN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
7.4.9.5. Offset in LeadersN/A
(1)[F81-OH2.1, OH2.3]
(2)[F81-OH2.1]
7.4.10.3. Hydraulic Loads from Fixtures with Continuous or Semi-continuous FlowN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
7.4.10.4. Hydraulic Loads from Roofs or Paved SurfacesN/A
(2)[F20, F81-OP5] (a), (d), (e) [F41, F81-OH2.4, OH2.5] (b), (c) [F20, F81-OS2.1]
(4)[F20, F81-OP5]
7.4.10.5. Conversion of Fixture Units to Litres and Gal/minN/A
(1)[F81-OH2.1]
7.4.10.6. Hydraulic Loads to Soil or Waste PipesN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
(3)[F81-OH2.1]
7.4.10.7. Hydraulic Loads on BranchesN/A
(1)[F81-OH2.1]
7.4.10.8. Hydraulic Loads on Sanitary Horizontal DrainN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
7.4.10.9. Hydraulic Loads on Horizontal Storm DrainsN/A
(1)[F81-OH2.1]
7.4.10.10. Rain LeadersN/A
(2)[F62, F81-OH1.3]
(3)[F62, F81-OH1.3]
2.4.10.11. Hydraulic Loads on LeadersN/A
(1)[F81-OP5]
2.4.10.12. Hydraulic Loads from Fixtures with a Semi-Continuous FlowN/A
(1)[F81-OP5]
7.5.1.1. Venting for TrapsN/A
(1)[F81-OH1.1]
(2)[F81-OH1.1]
7.5.2.1. Wet VentingN/A
(1)[F40, F81-OH1.1]
7.5.3.1. Circuit VentingN/A
(1)[F40, F81-OH1.1]
(2)[F40, F81-OH1.1]
(3)[F40, F81-OH1.1]
(4)[F40, F81-OH1.1]
(5)[F40, F81-OH1.1]
(6)[F40, F81-OH1.1]
(7)[F40, F81-OH1.1]
(8)[F40, F81-OH1.1]
(9)[F40, F81-OH1.1]
(10)[F40, F81-OH1.1]
7.5.4.1. Stack VentsN/A
(1)[F40, F81-OH1.1]
7.5.4.2. Vent StacksN/A
(1)[F40, F81-OH1.1]
(3)[F40, F81-OH1.1]
(4)[F40, F81-OH1.1]
7.5.4.3. Yoke VentsN/A
(1)[F40, F81-OH1.1]
(2)[F40, F81-OH1.1]
(3)[F40, F81-OH1.1]
7.5.4.4. Offset Relief VentsN/A
(1)[F40, F81-OH1.1]
7.5.4.5. Fixtures Draining into Vent PipesN/A
(1)[F40, F81-OH1.1]
7.5.5.1. Venting of Sanitary Sewage SumpsN/A
(1)[F40, F81-OH1.1]
7.5.5.2. Venting of InterceptorsN/A
(1)[F40, F81-OH1.1] [F81-OH2.1] [F01, F40, F81-OP1.1] [F01, F40, F81-OS1.1]
(2)[F40, F81-OH1.1] [F81-OH2.1] [F01, F40, F81-OP1.1] [F01, F40, F81-OS1.1]
(3)[F40, F81-OH1.1] [F01, F40, F81-OP1.1] [F01, F40, F81-OS1.1]
(4)[F40, F81-OH1.1] [F01, F40, F81-OP1.1] [F01, F40, F81-OS1.1]
(5)[F40, F81-OH1.1] [F01, F40, F81-OP1.1] [F01, F40, F81-OS1.1]
(6)[F40, F81-OH1.1] [F81-OH2.1]
(7)[F40, F81-OH1.1] [F81-OH2.1] [F01, F40, F81-OP1.1] [F01, F40, F81-OS1.1]
7.5.5.3. Venting of Drain Piping and Dilution Tanks for Corrosive WasteN/A
(1)[F81-OS3.4]
7.5.5.4. Fresh Air InletsN/A
(1)[F81-OH1.1]
7.5.5.5. Provision for Future InstallationsN/A
(1)[F81-OH1.1] Applies to venting systems. [F81-OH2.1] Applies to drainage systems.
(2)[F40, F81-OH1.1]
7.5.6.1. Drainage of Vent PipesN/A
(1)[F81-OH1.1]
(2)[F81-OH1.1]
7.5.6.2. Vent Pipe ConnectionsN/A
(1)[F81-OH1.1]
(2)[F81-OH1.1]
(3)[F40, F81-OH1.1]
7.5.6.3. Location of Vent PipesN/A
(1)[F81-OH1.1]
(2)[F81-OH2.1]
(3)[F81-OH1.1]
(4)[F40, F81-OH1.1]
7.5.6.4. Connection of Vents Above Fixtures ServedN/A
(1)[F81-OH1.1]
(2)[F81-OH1.1]
7.5.6.5. TerminalsN/A
(1)[F81-OH1.1]
(2)[F81-OH1.1]
(4)[F81-OH1.1]
(5)[F81-OH1.1]
(6)[F81-OH1.1]
(7)[F20, F81-OH1.1]
(8)[F61, F80-OH1.3] [F61, F80-OP2.3]
(9)[F61-OH1.3] [F61-OP2.3]
(10)[F81-OH1.1]
7.5.7.1. GeneralN/A
(1)[F81-OH1.1]
7.5.7.2. Size RestrictionN/A
(1)[F81-OH1.1]
(2)[F81-OH1.1]
(3)[F81-OH1.1]
7.5.7.3. Additional Circuit Vents and Relief VentsN/A
(2)[F81-OH1.1]
7.5.7.4. Offset Relief VentsN/A
(1)[F81-OH1.1]
7.5.7.5. Yoke VentsN/A
(1)[F81-OH2.1]
7.5.7.6. Vent Pipes for ManholesN/A
(1)[F81-OH2.1]
7.5.7.7. Vents for Sewage Sumps, Neutralizing and Dilution Tanks, and Macerating Toilet SystemsN/A
(1)[F81-OH2.1]
(2)[F81-OH2.1]
(3)[F81-OH1.1]
7.5.8.1. Hydraulic Loads Draining to Wet VentsN/A
(1)[F81-OH1.1]
(2)[F81-OH1.1]
7.5.8.2. Individual Vents and Dual VentsN/A
(1)[F81-OH1.1]
7.5.8.3. Branch Vents, Headers, Continuous Vents and Circuit VentsN/A
(1)[F81-OH1.1]
7.5.8.4. Vent Stacks or Stack VentsN/A
(1)[F81-OH1.1]
(3)[F81-OH1.1]
(4)[F81-OH1.1]
(5)[F81-OH1.1]
7.5.9.2. Air Admittance ValvesN/A
(1)[F40, F81-OH1.1] (a) [F140-OC]
(2)[F40, F81-OH1.1]
(3)[F40, F81-OH1.1]
7.5.9.3. Installation ConditionsN/A
(1)[F40, F81-OH1.1]
(2)[F40, F81-OH1.1]
(3)[F40, F81-OH1.1]
(4)[F40, F81-OH1.1]
(5)[F40, F81-OH1.1]
7.6.1.1. DesignN/A
(1)[F31-OS3.2]
(2)[F31-OS3.2]
(3)[F71-OH2.3]
7.6.1.2. DrainageN/A
(1)[F81-OP5]
7.6.1.3. Control and Shut-off ValvesN/A
(1)[F81-OP5]
(2)[F81-OP5]
(2.1)[F81-OP5]
(2.2)[F81-OP5]
(3)[F81-OP5]
(4)[F81-OP5]
(5)[F70, F72-OH2.1, OH2.3]
(6)[F70, F72-OH2.1, OH2.3]
(47)[F81-OP5]
(8)[F81-OP5]
(9)[F81-OP5]
7.6.1.3A. Public WashroomsN/A
(1)[F81-OP5]
7.6.1.3B. TanksN/A
(1)[F81-OP5]
7.6.1.4. Protection for Exterior Water SupplyN/A
(1)[F81-OP5]
7.6.1.5. Check ValvesN/A
(1)[F20, F81-OP5]
7.6.1.6. Flushing DevicesN/A
(1)[F72-OH2.1]
(2)[F72-OH2.1]
(3)[F130-OE1.2]
(4)[F81-OH2.1]
(5)[F130-OE1.2]
7.6.1.7. Relief ValvesN/A
(1)[F20, F81-OP1.1] [F20, F81-OS1.1] [F20, F81-OS2.3] [F31, F81-OS3.2] Applies to pressure vessels containing hot water.
(2)[F20, F81-OP1.1] [F20, F81-OS1.1] [F20, F81-OS2.3] [F31, F81-OS3.2]
(4)[F20, F81-OP1.1] [F20, F81-OS1.1] [F20, F81-OS2.3] (b) [F31, F81-OS3.2]
(5)[F20, F81-OP1.1] [F20, F81-OS1.1] [F20, F81-OS2.3] [F31, F81-OS3.2] (b) [F81-OH2.2] Applies to the size of air break.
(6)[F20, F81-OP1.1] [F20, F81-OS1.1] [F20, F81-OS2.3] [F31, F81-OS3.2]
(7)[F20, F81-OP1.1] [F20, F81-OS1.1] [F20, F81-OS2.3] [F31, F81-OS3.2]
7.6.1.8. Solar Domestic Hot Water SystemsN/A
(1)[F61-OH1.3] [F70-OH2.2] [F20-OS2.2, OS2.3] [F31-OS3.2] [F81-OS3.4]
7.6.1.9. Water HammerN/A
(1)[F20-OH4] [F20, F81-OP5] [F20, F81-OS3.2]
7.6.1.10. Mobile Home Water ServiceN/A
(1)[F46, F70-OH2.2]
7.6.1.11. Thermal ExpansionN/A
(1)[F20, F46, F81-OP5]
7.6.2.1. Connection of SystemsN/A
(1)[F81-OH2.1] [F46, F70, F81-OH2.2]
(3)[F70, F81, F82-OH2.2, OH2.3]
(3.1)[F46, F70, F81-OH2.2]
7.6.2.2. Back-SiphonageN/A
(1)[F81-OH2.1] [F46, F70, F81-OH2.2]
(2)[F81-OH2.1] [F46, F70, F81-OH2.2]
7.6.2.3. Backflow Caused by Back PressureN/A
(1)[F81-OH2.1] [F46, F70, F81-OH2.2]
(2)[F81-OH2.1] [F46, F70, F81-OH2.2]
(3)[F81-OH2.1] [F46, F70, F81-OH2.2]
7.6.2.4. Backflow from Fire Protection SystemsN/A
(2)[F81-OH2.1] [F46, F70, F81-OH2.2]
(3)[F02, F12, F81-OP1.2] [F02, F12, F81-OS1.2]
(4)[F81-OH2.1] [F46, F70, F81-OH2.2]
7.6.2.5A. Backflow from Buildings with a Solar Domestic Hot Water SystemN/A
(1)[F70, F81, F46-OH2.1, OH2.2, OH2.3]
7.6.2.6. Premise IsolationN/A
(1)[F81-OH2.1] [F46, F70, F81-OH2.2]
(3)[F46, F70, F81-OH2.2]
7.6.2.7. Hose BibbN/A
(1)[F70, F81, F46-OH2.1, OH2.2, OH2.3]
7.6.2.8. Cleaning of SystemsN/A
(1)[F81-OH2.1] [F46, F70, F81-OH2.2]
7.6.2.9. Air GapN/A
(1)[F81-OH2.1] [F46, F70, F81-OH2.2]
(2)[F81-OH2.1] [F46, F70, F81-OH2.2]
7.6.2.10. Vacuum Breakers and Flood LevelsN/A
(2)[F81-OH2.1] [F46, F70, F81-OH2.2]
(3)[F81-OH2.1] [F46, F70, F81-OH2.2]
(4)[F81-OH2.1] [F46, F70, F81-OH2.2]
7.6.2.11. Tank-Type Water ClosetsN/A
(1)[F70, F81, F46-OH2.1, OH2.2, OH2.3]
7.6.3.1. DesignN/A
(1)[F70, F81-OH2.2]
(2)[F70-OH2.2]
(4)[F70, F81-OH2.2] [F40-OH2.1, OH2.4]
7.6.3.2. Hydraulic LoadN/A
(1)[F70, F81-OH2.2]
(2)[F70, F81-OH2.2]
(3)[F70, F81-OH2.2]
(4)[F70, F81-OH2.2]
7.6.3.3. Static PressureN/A
(1)[F20, F81-OP1.1] [F20, F81-OP5] [F20, F81-OS1.1] [F20, F81-OS2.3] [F31, F81-OS3.2] Applies to pipes containing hot water.
7.6.3.4. SizeN/A
(1)[F70, F81-OH2.2]
(2)[F70, F81-OH2.2]
(4)[F70, F81-OH2.2]
(5)[F71, F72-OH2.1, OH2.3]
(6)[F71, F72-OH2.1, OH2.3]
7.6.4.1. Water Supply FittingsN/A
(31)[F130-OR1]
(2)[F30-OS3.1] [F31-OS3.2]
(3)[F130-OR1]
7.7.1.1. GeneralN/A
(1)[F81-OH2.2]
(2)[F82-OH2.2]
(3)[F40-OH2.2]
(4)[F46-OH2.2]
(5)[F80, F81-OS3.4] [F81-OP5]
7.7.1.2. Identification and MarkingN/A
(0.1)[F46, F81-OH2.2]
(1)[F46, F81-OH2.2]
7.7.1.3. Location of PipesN/A
(1)[F81-OH2.1, OH2.2, OH2.4] (c), (d) [F46-OH2.2]
7.7.1.4. Location of OutletsN/A
(1)[F46-OH2.2] [F40-OH2.4]
7.7.2.2. Permitted ApplicationsN/A
(1)[F46-OH2.2] [F81-OH2.2]
7.7.2.3. Roof DesignN/A
(1)[F41-OH2.2]
(2)[F41-OH2.2]
7.7.2.4. Non-Potable Rainwater Harvesting System DesignN/A
(1)[F46, F80, F81-OH2.2]
(2)[F41-OH2.2]
(3)[F40-OH2.2]
(4)[F41-OH2.2]
(5)[F80, F81-OS3.4] [F81-OP5]
(6)[F81-OH2.2]
(7)[F81-OH2.2] [F81-OP5]
(8)[F81-OH2.2] [F81-OH2.2]
(9)[F46-OH2.2]
(10)[F46-OH2.2]
7.7.3.1. Conformance to StandardsN/A
(1)[F81, F82-OH2.1, OH2.2, OH2.4] [F130-OR1]

Table 8 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 8 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 8 of Division B
Acceptable SolutionsObjectives and Functional Statements
8.1.3.1. DischargeN/A
(1)[F81, F110, F111-OE] [F81, F110, F111-OH5]
(7)[F81, F110, F111-OE] [F81, F110, F111-OH5]
(8)[F81, F111-OE] [F81, F111-OH5]
8.2.1.2. Site EvaluationN/A
(1)[F110, F111, F112-OE] [F110, F111, F112-OH5]
8.2.1.4. ClearancesN/A
(2)[F110, F112-OE] [F110, F112-OH5]
(3)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
(4)[F110, F111, F112-OE] [F110, F111, F112-OH5]
8.2.1.5. Clearance Distances for Class 1, 2 and 3 Sewage SystemsN/A
(1)[F110, F112-OE] [F110, F112-OH5]
8.2.1.6. Clearances for a Class 4 or 5 Sewage SystemN/A
(1)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
(2)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
(3)[F110-OE] [F110-OH2.1] [F110-OH5]
8.2.2.2. TanksN/A
(1)[F110, F111, F112-OE] [F110, F111, F112-OH5] [F20-OP2.3]
(2)[F110, F111, F112-OE] [F110, F111, F112-OH5] [F20-OP2.3]
(5)[F82, F111-OE] [F82, F111-OH2.1] [F82, F111-OH5]
(6)[F20-OP2.3]
(7)[F81-OP2.6]
8.2.2.3. Septic TanksN/A
(1)[F111-OE] [F111-OH2.1] [F111-OH5]
(2)[F111, F112-OE] [F111, F112-OH2.1] [F111, F112-OH5]
(3)[F111, F112-OE] [F111, F112-OH2.1] [F111, F112-OH5]
(4)[F111, F112-OE] [F111, F112-OH2.1] [F111, F112-OH5] (e) [F110-OE] (e) [F110-OH5]
(5)[F111, F112-OE] [F111, F112-OH2.1] [F111, F112-OH5]
(6)[F111, F112-OE] [F111, F112-OH2.1] [F111, F112-OH5]
(7)[F111, F112-OE] [F111, F112-OH2.1] [F111, F112-OH5]
(8)[F111, F112-OE] [F111, F112-OH2.1] [F111, F112-OH5]
(9)[F82, F111-OE] [F82, F111-OH2.1] [F82, F111-OH5]
(10)[F82, F111-OE] [F82, F111-OH2.1] [F82, F111-OH5]
(11)[F82, F111-OE] [F82, F111-OH2.1] [F82, F111-OH5]
8.2.2.4. Holding TanksN/A
(1)[F82, F111-OE] [F82, F111-OH2.1] [F82, F111-OH5]
(2)[F111-OE] [F111-OH2.1] [F111-OH5]
8.3.1.2. ApplicationN/A
(1)[F111, F112-OE] [F111, F112-OH2.1] [F111, F112-OH5]
(3)[F110-OE] [F110-OH5]
8.3.2.1. Construction RequirementsN/A
(1)(a), (b) [F42-OH2.5] (c), (d), (h) [F40-OH2.4] (e) [F101-OH6] (f), (g) [F50-OH1.1] (f), (g) [F42-OH2.5]
8.3.3.1. Construction RequirementsN/A
(1)(a) [F110, F112-OE] (a) [F110, F112-OH5] (b) [F20-OS2.2] (b), (d) [F113-OH2.6] (c) [F112-OE] (c) [F112-OH5] (d) [F110-OE]
8.3.4.1. Construction RequirementsN/A
(1)(a) [F40-OH2.4] [F113-OH2.6] (b) [F113-OH2.6] (c) [F111-OE] (c) [F111-OH5]
8.3.5.1. Construction RequirementsN/A
(1)(a) [F113-OH2.6] (b) [F40-OH2.4] (c) [F20-OS2.1]
8.4.1.2. ApplicationN/A
(1)[F110-OE] [F110-OH5]
8.4.2.1. Construction RequirementsN/A
(1)[F110, F112-OE] [F110, F112-OH5]
(2)[F113-OH2.6] [F20-OS2.2]
(3)[F112-OE] [F112-OH5]
(4)[F82-OE] [F42-OH2.5] [F113-OH2.6] [F82-OH5] [F30-OS3.1]
(5)[F113-OH2.6]
(6)[F111-OE] [F111-OH5]
(7)[F112-OE] [F112-OH5]
8.4.2.2. Maximum Sewage FlowN/A
(1)[F110, F112-OE] [F110, F112-OH5]
8.4.2.3. SizingN/A
(1)[F110, F112-OE] [F110, F112-OH5]
8.5.1.2. ApplicationN/A
(1)[F110, F112-OE] [F110, F112-OH5]
(2)[F112-OE] [F112-OH5]
8.5.2.1. Construction RequirementsN/A
(1)[F110, F112-OE] [F110, F112-OH5]
(2)[F113-OH2.6] [F20-OS2.2]
(3)[F112-OE] [F112-OH5]
(4)[F82-OE] [F42-OH2.5] [F113-OH2.6] [F82-OH5] [F30-OS3.1]
(5)[F30-OS3.1]
(6)[F113-OH2.6]
(7)[F111-OE] [F111-OH5]
(8)[F112-OE] [F112-OH5]
8.6.1.2. General RequirementsN/A
(1)[F112-OE] [F112-OH5]
8.6.1.3. Pumps and SiphonsN/A
(1)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
(2)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(3)[F110, F111, F112-OE] [F110, F111, F112-OH5]
(4)[F111, F113-OE] [F111, F113-OH5]
(5)[F112-OE] [F112-OH5]
(6)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.6.2.1. Septic Tank SystemsN/A
(1)[F110, F111-OE] [F110, F111-OH5]
(2)[F110, F111-OE] [F110, F111-OH5]
(3)[F82-OE] [F82-OH2.1]
8.6.2.2. Other Treatment UnitsN/A
(1)[F110-OE] [F110-OH5]
(2)[F110, F111-OE] [F110, F111-OH5]
(3)[F111-OE] [F111-OH2.1] [F111-OH5]
(4)[F111-OE] [F111-OH2.1] [F111-OH5]
(6)[F82, F111-OE] [F82, F111-OH2.1] [F82, F111-OH5]
8.7.1.1. Application ScopeN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.1.2. Limitation on InstallationN/A
(1)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
8.7.2.1. General RequirementsN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(2)[F104, F110, F111-OE] [F104, F110, F111-OH2.1] [F104, F110, F111-OH5] [F104, F110, F111-OR2]
(3)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(4)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(5)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.2.2. Distribution Pipes within Leaching BedsN/A
(2)[F111-OE]
8.7.2.3. Leaching Chambers within Leaching BedsN/A
(3)[F111, F112-OE] [F111, F112-OH2.1] [F111, F112-OH5]
(4)[F111-OE]
8.7.3.1. Length of Distribution PipeN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(2)[F110-OE] [F110-OH5]
(3)[F110-OE] [F110-OH5]
(4)[F110-OE] [F110-OH5]
8.7.3.2. Length of Leaching ChamberN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(2)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(3)[F110-OE] [F110-OH2.1] [F110-OH5]
(4)[F110-OE] [F110-OH5]
8.7.3.3. Absorption TrenchesN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(2)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.3.4. Distribution PipeN/A
(1)[F111-OE] [F111-OH5]
(2)[F111-OE] [F111-OH5]
(3)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(4)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.3.5. Leaching ChamberN/A
(1)[F111-OE] [F111-OH5]
(2)[F111-OE] [F111-OH5]
(3)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.4.1. Loading RequirementsN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.4.2. Construction RequirementsN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(2)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(3)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(5)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(6)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(7)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(8)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(9)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(10)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(11)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.5.1. ApplicationN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.5.2. Loading RequirementsN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(2)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(3)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
(4)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
(5)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
8.7.5.3. Construction RequirementsN/A
(2)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
(3)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
(4)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
(5)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(6)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
8.7.6.1. Construction RequirementsN/A
(1)[F112-OE] [F112-OH5]
(2)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
(3)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(4)[F20-OS2.2]
(5)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.7.1. Construction RequirementsN/A
(1)[F112-OE] [F112-OH5]
(2)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(3)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
(4)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
(5)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(6)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(7)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(8)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(9)[F111-OE] [F111-OH5]
(10)[F111-OE] [F111-OH5]
(11)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
8.7.7.2. Construction RequirementsN/A
(2)[F111-OE]
8.7.8.1. General RequirementsN/A
(2)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.7.8.2. Construction RequirementsN/A
(1)[F112-OE] [F112-OH5]
(2)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
(3)[F110, F112-OE] [F110, F112-OH5]
(4)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
(5)[F110, F111, F112-OE] [F110, F111, F112-OH2.1] [F110, F111, F112-OH5]
(7)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
(8)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(9)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(10)[F110, F112-OE] [F110, F112-OH2.1] [F110, F112-OH5]
8.7.8.3. Design RequirementsN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(2)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(3)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(4)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.8.1.2. Acceptable InstallationN/A
(1)[F110-OE] [F110-OH5]
(2)[F82, F110-OE] [F82, F110-OH5]
8.8.2.1. Construction RequirementsN/A
(1)[F82, F110-OE] [F82, F110-OH5]
(2)[F82, F110-OE] [F82, F110-OH5]
(3)[F110-OE] [F110-OH5]
(4)[F110-OE] [F110-OH5]
8.8.2.2. Sizing of Holding TanksN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.9.1.2. General Requirements for Operation and MaintenanceN/A
(1)[F110-OE] [F110-OH5]
8.9.2.2. GeneralN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.9.2.3. Class 4 Sewage SystemsN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(2)[F82, F110-OE] [F82, F110-OH5]
8.9.2.4. Sampling of Treatment UnitsN/A
(1)[F82, F110-OE] [F82, F110-OH5]
(2)[F82, F110-OE] [F82, F110-OH5]
(3)[F82, F110-OE] [F82, F110-OH5]
(4)[F82, F110-OE] [F82, F110-OH5]
8.9.2.5. Class 5 Sewage SystemsN/A
(1)[F82, F110-OE] [F82, F110-OH5]
(2)[F110-OE] [F110-OH5]
8.9.3.2. GeneralN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
(2)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.9.3.3. InterceptorsN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.9.3.4. Class 4 Sewage SystemsN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]
8.9.3.5. Pressurized Distribution SystemsN/A
(1)[F110, F111-OE] [F110, F111-OH2.1] [F110, F111-OH5]

Table 9 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 9 of Division B

[F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F21-OH4] Applies to floors and elements that support floors. [F21-OP2.1, OP2.4] [F21-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F21-OS1.2] Applies to assemblies required to provide fire resistance. [F21-OS2.1] [F21-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F21-OS3.1] Applies to floors and elements that support floors.

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 9 of Division B
Acceptable SolutionsObjectives and Functional Statements
9.1.1.7. RadonN/A
(1)[F40, F50-OH1.1]
9.1.1.8. Building in Flood PlainsN/A
(1)(a) [F20-OP2.1] (a) [F20-OS2.1, OS2.3] (a) [F61-OH1.3] (b) [F10, F12-OS3.1] [F10, F30-OS3.7]
9.3.1.1. GeneralN/A
(1)[F20-OP2.1, OP2.4] [F21-OP2.3, OP2.4] [F80-OP2.3] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F80-OH1.1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. [F20, F21, F55, F61, F80-OH1.1, OH1.2] [F20, F21, F80, F61-OH1.3] Applies where concrete supports or is used in an environmental separator. [F20, F21, F80-OH4] Applies where concrete elements support wood-frame floors. [F20, F21, F80-OS1.1] Applies where concrete supports or is used in chimneys or fireplaces. [F20-OS2.1] [F21, F80-OS2.3] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F80-OS3.1] Applies to concrete floors or steps, concrete that supports wood-frame floors or steps, and concrete steps that support guards or handrails. [F20, F21, F80-OS3.4, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces.
(4)[F20-OP2.1, OP2.4] [F21, F80-OP2.3, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F80-OH1.1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. [F20, F21, F55, F80, F61-OH1.1, OH1.2] [F20, F21, F80, F61-OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F80-OH4] Applies to elements that support floors. [F20, F80-OS1.1] Applies where concrete supports or is used in chimneys or fireplaces. [F20-OS2.1] [F80-OS2.3] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to concrete that supports wood- frame floors or steps. [F20, F80-OS3.4, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces.
9.3.1.2. CementN/A
(1)[F20-OP2.1, OP2.4] [F80-OP2.3, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OH1.1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. [F20, F55, F61, F80-OH1.1, OH1.2] [F20, F61, F80- OH1.3] Applies where concrete supports or is used in an environmental separator. [F20, F80-OH4] Applies where concrete elements support wood-frame floors. [F20, F80-OS1.1] Applies where concrete supports or is used in chimneys or fireplaces. [F20-OS2.1] [F80-OS2.3] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to concrete floors or steps, concrete that supports wood-frame floors or steps, and concrete steps that support guards or handrails. [F20, F80-OS3.4, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces.
9.3.1.3. Concrete in Contact with Sulfate SoilN/A
(1)[F20-OP2.1, OP2.4] [F80-OP2.3, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F80-OH1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. [F80-OH1.1, OH1.2, OH1.3] Applies where concrete supports or is used in an environmental separator. [F80-OH4] Applies where concrete elements support wood-frame floors. [F80-OS1.1] Applies where concrete is used in footings for chimneys or fireplaces. [F20-OS2.1] [F80-OS2.3] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F80-OS3.1] Applies to concrete floors or steps, concrete that supports wood-frame floors or steps, and concrete steps that support guards or handrails. [F80-OS3.4, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces.
9.3.1.4. AggregatesN/A
(1)[F20-OP2.1, OP2.4] [F80-OP2.3, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS1.1] Applies to concrete used in chimneys or fireplaces. [F20-OS2.1] [F80-OS2.3] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.4] Applies to concrete used in chimneys or fireplaces. [F20, F55, F61, F80-OH1.1, OH1.2] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F61, F80-OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F80-OH4] Applies to floors and elements that support floors.
9.3.1.5. WaterN/A
(1)[F20-OP2.1, OP2.4] [F80-OP2.3, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS1.1] Applies where concrete supports or is used in chimneys or fireplaces. [F20-OS2.1] [F80-OS2.3] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to concrete floors or steps, concrete that supports wood-frame floors or steps, and concrete steps that support guards or handrails. [F20, F80-OS3.4, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces. [F20, F55, F61, F80-OH1.1, OH1.2] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F61, F80-OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F80-OH4] Applies where concrete elements support wood-frame floors.
9.3.1.6. Compressive StrengthN/A
(1)(a) [F20-OP2.1, OP2.4] (a) [F21-OP2.3, OP2.4] (a) [F80-OP2.3] (a) [F20-OP2.3] Applies to elements that support are part of an environmental separator. (a) [F20, F21, F80-OS1.1] Applies where concrete supports or is used in chimneys or fireplaces. (a) [F20-OS2.1] (a) [F21, F80-OP2.3] (a) [F20-OS2.3] Applies to elements that support or are part of an environmental separator. (a) [F20, F80-OS3.1] Applies to elements that support floors or steps. (a) [F20, F80-OS3.4, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces. (a) [F20, F80-OH1.1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. (a) [F20, F55, F61, F80-OH1.1, OH1.2] [F20, F61, F80- OH1.3] Applies where concrete supports or is used in an environmental separator. (a) [F20, F21, F80-OH4] Applies to elements that support floors. (b) [F20-OP2.1, OP2.4] (b) [F21-OP2.3, OP2.4] (b) [F80-OP2.3] (b) [F20-OP2.3] Applies to elements that support or are part of an environmental separator. (b) [F20-OS2.1] (b) [F21, F80-OS2.3] (b) [F20-OS2.3] Applies to elements that support or are part of an environmental separator. (b) [F20, F21, F80-OS3.1] (b) [F20, F21, F55, F61, F80-OH1.1, OH1.2] [F20, F21, F61, F80-OH1.3], (c) [F20-OP2.1] [F20, F21, F80-OP2.3, OP2.4] (c) [F20-OS2.1] [F20, F21, F80-OS2.3] (c) [F20, F21, F80-OS3.1]
(2)[F80-OS3.1]
9.3.1.7. Concrete MixesN/A
(1)(a) [F20-OP2.1, OP2.4] (a) [F21-OP2.3, OP2.4] (a) [F20, F55, F61-OP2.3] Applies to elements that support or are part of an environmental separator. (a) [F20, F21, F61-OS1.1] Applies where concrete supports or is used in chimneys or fireplaces. (a) [F20-OS2.1] (a) [F21-OS2.3] (a) [F20, F61, F55-OS2.3] Applies to elements that support or are part of an environmental separator. (a) [F20, F21, F61-OS3.1] Applies to concrete floors or steps, concrete that supports wood-frame floors or steps, and concrete steps that support guards or handrails. (a) [F20, F21, F61-OS3.4, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces. (a) [F20, F21, F80-OH1.1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. (a) [F20, F21, F80, F61, F55-OH1.1, OH1.2] [F20, F21, F80, F61-OH1.3] Applies where concrete supports or is used in an environmental separator. (a) [F20, F21, F61-OH4] Applies to elements that support floors. (b) [F20-OP2.1, OP2.4] (b) [F21-OP2.3, OP2.4] (b) [F80-OP2.3] (b) [F20-OP2.3] Applies where concrete is used in an environmental separator. (b) [F20, F21, F55, F61, F80-OH1.1, OH1.2] [F20, F21, F61, F80-OH1.3] (b) [F20-OS2.1] (b) [F21, F80-OS2.3] (b) [F20-OS2.3] Applies where concrete is used in an environmental separator. (b) [F20, F21, F80-OS3.1] (c) [F20, F21, F80-OP2.3, OP2.4] (c) [F20, F21-OS2.1] [F20, F21, F80-OS2.3] (c) [F20, F21, F80-OS3.1]
(2)[F20-OP2.1, OP2.4] [F21-OP2.3, OP2.4] [F20, F61, F55-OP2.3] Applies where concrete supports or is used in an environmental separator. [F20, F21-OS1.1] Applies where concrete supports or is used in chimneys or fireplaces. [F20-OS2.1] [F21-OS2.3] [F20, F55, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to concrete floors or steps, concrete that supports wood-frame floors or steps, and concrete steps that support guards or handrails. [F20, F80-OS3.1, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces. [F20, F21, F55, F61-OH1.1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. [F20, F21-OH1.2, OH1.3] Applies where concrete supports or is used in an environmental separator. [F20, F21, F55, F61-OH4] Applies where concrete elements support wood-frame floors.
9.3.1.8. AdmixturesN/A
(1)[F20-OP2.1, OP2.4] [F21-OP2.3, OP2.4] [F80-OP2.3, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F80-OS1.1] Applies where concrete supports or is used in chimneys or fireplaces. [F20-OS2.1] [F21-OS2.3] [F20, F55, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to concrete floors or steps, concrete that supports wood-frame floors or steps, and concrete steps that support guards or handrails. [F20, F80-OS3.4, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces. [F20, F80-OH1.1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. [F20, F55, F61, F80-OH1.1, OH1.2] [F20, F61, F80- OH1.3] Applies where concrete supports or is used in an environmental separator. [F20, F21, F80-OH4] Applies where concrete elements support wood-frame floors.
9.3.1.9. Cold Weather RequirementsN/A
(1)[F20-OP2.1, OP2.4] [F21, F80-OP2.3, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F80-OS1.1] Applies where concrete supports or is used in chimneys or fireplaces. [F20-OS2.1] [F21-OS2.3] [F20-OS2.3] Applies to elements that support or are part of en environmental separator. [F20, F80-OS3.1] Applies to concrete floors or steps, concrete that supports wood-frame floors or steps, and concrete steps that support guards or handrails. [F20, F80-OS3.4, OS3.7] Applies where concrete supports or is used in chimneys or fireplaces. [F20, F80-OH1.1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. [F20, F55, F61, F80-OH1.1, OH1.2] [F20, F61, F80- OH1.3] Applies where concrete supports or is used in an environmental separator. [F20, F21, F80-OH4] Applies where concrete elements support wood-frame floors.
(2)[F20-OH1.1] Applies where concrete supports or is used in the walls of chimneys or fireplaces. [F20, F55, F61-OH1.1, OH1.2] [F20, F61-OH1.3] Applies where concrete supports or is used in an environmental separator. [F20, F55, F61-OH4] Applies to elements that support floors. [F20-OP2.1, OP2.4] [F20, F55, F61-OP2.3] [F55, F61-OP2.4] Applies to elements that support or are part of an environmental separator. [F20-OS1.1] Applies to concrete that supports or is used in chimneys or fireplaces. [F20-OS2.1] [F20, F55, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F55, F61-OS3.1] Applies to floors and elements that support floors. [F20, F55, F61-OS3.4] Applies to concrete that supports or is used in chimneys or fireplaces.
9.3.2.2. Lumber GradesN/A
(1)[F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, or elements that support walls, that contain doors or windows required for emergency egress.
9.3.2.5. Moisture ContentN/A
(1)[F21, F80-OP2.3, OP2.4] [F21, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F21, F80-OH4] Applies to floors and elements that support floors. [F21, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F21, F80-OS2.3] [F21, F80-OS3.1] Applies to floors and elements that support floors.
9.3.2.8. Undersized LumberN/A
(1)[F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.3.2.9. Termite and Decay ProtectionN/A
(1)[F80, F82-OP2.3, OP2.4] [F80, F82-OS1.2] Applies where wood elements support or are used in assemblies that are required to provide fire resistance. [F80, F82-OS2.3] [F80, F82-OS3.1] Applies where structural wood elements support or are used in floors. [F55, F61, F80, F82-OH1.1, OH1.2] Applies where structural wood elements support or are used in an environmental separator. [F80, F82-OH4] Applies where structural wood elements support or are used in floors.
(2)[F80, F82-OP2.3, OP2.4] [F80, F82-OS2.1] Applies where structural wood elements support or are used in assemblies that are required to provide fire resistance. [F80, F82-OS2.3] [F80, F82-OS3.1] Applies where structural wood elements support or are used in floors. [F55, F61, F82, F80-OH1.1, OH1.2] [F61, F80, F82- OH1.3] Applies where structural wood elements support or are used in an environmental separator. [F80, F82-OH4] Applies where structural wood elements support or are used in floors.
(3)[F80-OP2.3, OP2.4] [F80-OS1.2] Applies where structural wood elements support or are used in assemblies that are required to provide fire resistance. [F80-OS2.3] [F80-OS3.1] Applies where structural wood elements support or are used in floors. [F82,F80,F61,F55-OH1.1,OH1.2] [F82,F80,F61-OH1.3] Applies where structural wood elements support or are used in an environmental separator. [F80-OH4] Applies where structural wood elements support or are used in floors.
(4)[F80-OS2.3,OS2.5] [F80-OP2.3,OP2.4,OP2.5] [F80,F61,F55-OH1.1,OH1.2] [F80,F61-OH1.3] Applies where cribbing or retaining walls support an environmental separator. [F80-OH4] Applies to floors and elements that support floors. [F80-OS3.1] Applies where cribbing or retaining walls support floors. [F80-OS1.2] Applies where cribbing or retaining walls support assemblies that are required to provide fire resistance.
(5)[F80,F81-OS2.3,OS2.4] [F80,F81-OP2.3,OP2.4] [F80,F81-OH4] Applies where structural wood elements support wood-frame floors. [F80,F81-OS3.1] Applies where structural wood elements support or are used in floors. [F55, F61, F80-OH1.1, OH1.2] [F61, F80-OH1.3] Applies where cribbing or retaining walls support an environmental separator. [F80,F81-OS1.2] Applies where structural wood elements support or are used in assemblies that are required to provide fire resistance.
(6)[F20,F60-OS2.3] [F80, F81-OS1.2] Applies where structural wood elements support or are used in assemblies that are required to provide fire resistance. [F20,F61-OP2.3,OP2.4] [F20,F55,F61-OH1.1,OH1.2] [F20,F61-OH1.3] Applies where structural wood elements support or are used in an environmental separator. [F61,F80-OH4] Applies to floors and elements that support floors. [F20,F61-OS3.1] Applies where structural wood elements support or are used in floors.
9.3.3.2. Galvanized Sheet SteelN/A
(1)[F80-OP2.3, OP2.4] [F80-OH1.1, OH1.2, OH1.3] Applies where sheet metal is used in an environmental separator. [F80-OH4.1] Applies where sheet metal is used in assemblies that support floors. [F80-OS2.3] [F80-OS3.1] Applies where sheet metal is used in assemblies that support floors.
(2)[F80-OH1.1, OH1.2, OH1.3] [F80-OP2.3] [F80-OS2.3]
9.4.2.2. Specified Design Snow LoadsN/A
(1)[F20-OP2.1, OP2.3] [F22-OP2.3] [F20-OS2.1, OS2.3] [F22-OS2.3] [F22-OH1.1, OH1.2, OH1.3]
(2)[F20-OP2.1] [F20-OS2.1]
(4)[F20-OS2.1,OS2.3] [F22-OS2.3] [F20-OP2.1,OP2.3] [F22-OP2.3] [F22-OH1.1,OH1.2,OH1.3]
9.4.2.3. Platforms Subject to Snow and Occupancy LoadsN/A
(1)[F20-OP2.1] [F20-OS2.1]
9.4.2.4. Attics and Roof SpacesN/A
(1)[F20-OP2.1] [F20-OS2.1]
9.4.3.1. DeflectionsN/A
(1)[F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F22-OP2.1, OP2.4] [F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.4.4.1. Allowable Bearing PressuresN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to footings that support an environmental separator. [F20-OH4] Applies to footings that support floors and other elements that support floors. [F20-OP2.2, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.2] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to footings that support floors and other elements that support floors. [F20-OS3.7] Applies to footings that support walls that contain doors or windows required for emergency egress.
9.4.4.2. Foundation Capacity in Weaker Soil and RockN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.2, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.2] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.2, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.2] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.4.4.3. High Water TableN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.2, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.2] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.4.4.4. Soil MovementN/A
(1)[F21-OH1.1, OH1.2, OH1.3] Applies to walls that support or are part of an environmental separator. [F21-OH4] Applies to foundations that support floors and other elements that support floors. [F21-OP2.1, OP2.4] [F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F21-OS2.1] [F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F21-OS3.1] Applies to footings that support floors and other elements that support floors. [F21-OS3.7] Applies to footings that support walls that contain doors or windows required for emergency egress.
9.4.4.6. Walls Supporting Drained EarthN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.3, OP2.4] [F20-OS2.1, OS2.3] [F20-OS3.1] Applies to floors and elements that support floors. [F20-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.3, OP2.4] [F20-OS2.1, OS2.3] [F20-OS3.1] Applies to floors and elements that support floors. [F20-OS3.7] Applies to walls, that contain doors or windows required for emergency egress.
9.5.1.2. Combination RoomsN/A
(2)[F10-OS3.7]
9.5.2.3. Stud Wall ReinforcementN/A
(1)[F74-OA2]
9.5.3.1. Ceiling Heights of Rooms or SpacesN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
9.5.3.2. MezzaninesN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.5.3.3. Storage GaragesN/A
9.5.3A.1. Areas of Living Rooms and SpacesN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F10-OS3.7]
9.5.3B.1. Area of Dining Rooms or SpacesN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
9.5.3C.1. Kitchen AreasN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
9.5.3D.1. Areas of BedroomsN/A
(1)[F10-OS3.7]
9.5.3D.2. Areas of Master BedroomsN/A
(1)[F10-OS3.7]
9.5.3D.3. Areas of Combination BedroomsN/A
(1)[F10-OS3.7]
9.5.3D.4. Areas of Other Sleeping RoomsN/A
(1)[F10-OS3.7]
9.5.3D.5. Recreational CampsN/A
(1)[F10-OS3.7]
9.5.3D.6. Camps for Housing WorkersN/A
(1)[F10-OS3.7]
9.5.3E.1. Combined Living, Dining, Bedroom and Kitchen SpacesN/A
(1)[F10-OS3.7]
9.5.3F.1. Space to Accommodate FixturesN/A
(1)[F10-OS3.7]
9.5.3F.2. Doors to Rooms Containing Water ClosetsN/A
(1)[F70, F71-OH2.3] [F101-OH6]
(2)[F101-OH6] Applies to portion of Code text: “to each room containing a water closet”
9.5.4.1. Hallway WidthN/A
(1)[F10-OS3.7]
9.5.5.1. Doorway Opening SizesN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.5.5.2. Doors to Public Water Closet RoomsN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.5.5.3. Doors to BathroomsN/A
(1)[F74-OA2]
9.6.1.2. Material Standards for GlassN/A
(1)[F20-OS2.1] [F63-OS2.3] (e),(i) [F63-OH1.1] [F51,F63-OH1.2] (h) [F03-OS1.2]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
9.6.1.3. Structural Sufficiency of GlassN/A
(1)[F20-OS2.1]
(2)[F20-OS2.1]
(3)[F30-OS3.1] [F10-OS3.7]
9.6.1.4. Types of Glass and Protection of GlassN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7] Applies to portion of Code text: “... except that such partitions shall be suitably marked to indicate their existence and position.”
(5)[F30-OS3.1] [F10-OS3.7]
(6)[F20,F30-OS3.1]
9.7.2.1. Entrance DoorsN/A
(1)[F40, F42, F61-OH1.1] [F51, F54-OH1.2] [F42-OH2.5] Applies to portion of Code text: “at each entrance to a dwelling unit” [F131-OR2] Applies to portion of Code text: “at each entrance to a dwelling unit” [F42, F61-OS2.3] Applies to portion of Code text: “at each entrance to a dwelling unit”
(2)[F35-OS4.2]
9.7.2.3. Minimum Window AreasN/A
(1)[F102-OH7] [F10-OS3.7]
9.7.3.1. General Performance CriteriaN/A
(1)[F42, F55, F61, F62, F63-OH1.1] [F81-OH1.1] Applies to windows that provide required non- heating season ventilation. [F54, F55, F61, F62, F63-OH1.2] [F63, F61, F62-OH1.3] [F20, F55, F61-OS2.1,OS2.3] [F42-OH2.5] [F81-OS3.7] [F34-OS4.1]
(2)[F81-OH1.1] Applies to skylights that provide required non-heating season ventilation. [F20, F22-OH1.3] [F20-OS2.1, OS2.3]
(3)[F42, F55-OH1.1] [F42-OH2.5] [F81-OS3.7] [F34-OS4.1 ]
(4)[F20, F22-OS2.3] [F30-OS3.1] [F20, F61-OH1.1, OH1.2] [F34-OS4.1]
9.7.3.2. Heat Transfer PerformanceN/A
(1)[F51, F63-OH1.1, OH1.2] [F63-OS2.3]
9.7.3.3. Thermal Characteristics of Windows, Doors andN/A
(1)[F63-OH1.1, OH1.2, OH1.3] [F63-OS2.3]
(2)[F63-OS2.3] [F63-OH1.1, OH1.2]
(3)[F63-OH1.1, OH1.2, OH1.3] [F63-OS2.3]
(4)[F63-OH1.1, OH1.2, OH1.3] [F63-OS2.3] [F63-OS3.1]
9.7.4.2. GeneralN/A
(1)[F20, F55, F61, F62, F63-0H1.1] [F81-OH1.1] Applies to windows that provide required non- heating season ventilation. [F54, F55, F61, F62, F63- OH1.2] [F63, F20, F61, F62-OH1.3] [F20, F21, F61-OS2.3] [F10-OS1.5] Applies where windows, doors or skylights serve bedrooms, except bedrooms that have direct access to the exterior through an exit door or bedrooms that are in sprinklered suites.
9.7.4.3. Performance RequirementsN/A
(1)[F20, F55, F61-OH1.1] [F55-OH1.2] [F20, F61, F62-OH1.3]
(4)[F40, F61, F42-OH1.1] [F51, F54-OH1.2] [F61, F42-OS2.3] [F80-OS3.7] [F80-OS4.1] [F42-OH2.5]
9.7.5.2. Resistance to Forced Entry for DoorsN/A
(2)[F34-OS4.1]
(3)[F20-OS4.1]
(4)[F34-OS4.1]
(5)[F34-OS4.1]
(6)[F20-OS4.1]
(7)[F20-OS4.1]
(8)[F34-OS4.1]
(9)[F20-OS4.1]
9.7.5.3. Resistance to Forced Entry for WindowsN/A
(1)[F34-OS4.1]
9.7.6.1. Installation of Windows, Doors and SkylightsN/A
(1)[F20, F54, F55, F61, F63-OH1.1, OH1.2, OH1.3] [F20, F61, F63-OS2.3]
(2)[F54, F55, F61, F63-OH1.1, OH1.2, OH1.3] [F61, F63-OS2.3]
(3)[F55, F61, F63-OS2.3] [F55, F61, F63-OH1.1, OH1.2]
9.7.6.2. Sealants, Trim and FlashingN/A
(1)[F61, F63-OH1.1, OH1.3] [F61, F51, F54, F63-OH1.2] [F61,F63-0S2.3]
(4)[F80-OS2.1, OS2.3] [F80-OP2.1, OP2.3] [F80-OH1.1, OH1.2,OH1.3]
9.8.1.1. GeneralN/A
9.8.2.1. Stair WidthN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
9.8.2.2. Height Over StairsN/A
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
9.8.3.1. Straight and Curved Runs in StairsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
9.8.3.2. Minimum Number of RisersN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.8.3.3. Maximum Height of FlightsN/A
(1)[F30-OS3.1]
9.8.4.1. Dimensions for RisersN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.8.4.2. Dimensions for Runs and Rectangular TreadsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.8.4.3. Dimensions for Tapered TreadsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
9.8.4.4. Uniformity and Tolerances for Risers, Runs and TreadsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1] [F10-OS3.7]
9.8.4.5. Uniformity of Runs in Flights with Mixed Treads within a House or dwelling unitN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.8.4.6. WindersN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.8.4.7. Spiral StairsN/A
(1)[F30-OS3.1]
(3)[F30-OS3.1]
9.8.4.8. Tread NosingsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.8.4.9. Open RisersN/A
(1)[F30-OS3.1]
9.8.4.10. Interior Stairs Extending Through the RoofN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.8.5.2. Ramp WidthN/A
(1), (2)[F30-OS3.1] [F10-OS3.7]
9.8.5.3. Height Over RampsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.8.5.4. Ramp SlopeN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.8.5.5. Maximum RiseN/A
(1)[F30-OS3.1]
9.8.6.2. Required LandingsN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.8.6.3. Dimensions of LandingsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1] [F10-OS3.7]
(6)[F30-OS3.1] [F10-OS3.7]
(7)[F30-OS3.1] [F10-OS3.7]
9.8.6.4. Height Over LandingsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.8.7.1. Required HandrailsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1] [F10-OS3.7]
9.8.7.2. Continuity of HandrailsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.8.7.3. Termination of HandrailsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.8.7.4. Height of HandrailsN/A
(2)[F30-OS3.1] [F10-OS3.7]
9.8.7.5. Ergonomic DesignN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.8.7.6. Projections into Stairs and RampsN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.8.7.7. Design and Attachment of HandrailsN/A
(1)[F20-OS2.1] [F20-OS3.1, OS3.7]
(2)[F20-OS2.1] [F20-OS3.1, OS3.7]
9.8.8.1. Required GuardsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1]
(6)[F30-OS3.1] [F10-OS3.7]
(7)[F30-OS3.1] [F10-OS3.7]
(8)[F30-OS3.1]
9.8.8.2. Loads on GuardsN/A
(1)[F20-OS2.1]
(2)[F20-OS2.4]
9.8.8.3. Height of GuardsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7] (3.1) [F30-OS3.1] [F10-OS3.7]
9.8.8.4. Guards for Floors and Ramps in GaragesN/A
(1)[F10-OS3.1]
(2)[F20-OS2.1]
9.8.8.5. Openings in GuardsN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
(3)[F30-OS3.1]
9.8.8.6. Guards Designed not to Facilitate ClimbingN/A
(1)[F30-OS3.1]
9.8.8.7. Glass in GuardsN/A
(1)[F20-OS2.1] [F20-OS3.1, OS3.7]
9.8.9.1. Loads on Stairs and RampsN/A
(1)[F20-OS2.1] [F22-OH4]
9.8.9.2. Exterior Concrete StairsN/A
(1)[F22-OS3.1, OS3.7]
9.8.9.3. Exterior Wood StepsN/A
(1)[F80-OS2.3] [F80-OS3.1, OS3.7]
9.8.9.4. Wooden Stair StringersN/A
(1)[F20-OS2.1] [F22-OH4]
(2)[F20-OS2.1] [F22-OH4]
9.8.9.5. TreadsN/A
(1)[F20-OS2.1] [F22-OH4]
(2)[F20-OS2.1] [F22-OH4]
9.8.9.6. Finish for Treads, Landings and RampsN/A
(0.1)[F30, F80-OS3.1] [F10-OS3.7]
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F73-OA1]
(4)[F30-OS3.1] [F10-OS3.7]
9.8.10.1. DesignN/A
(1)[F20-OS2.1] [F22-OS3.1, OS3.7]
9.8.10.2. AnchorageN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.1] [F22-OS3.1, OS3.7]
9.8.10.3. Prevention of Damage Due to FrostN/A
(1)[F21-OH1.1, OH1.2, OH1.3] [F21-OS2.1] [F21-OS3.1]
9.9.2.1. Types of ExitsN/A
(2.1)[F04-OP1.2, OP1.3] [F06, F12, F81-OP1.2] [F80-OP2.3] [F04-OS1.2, OS1.3] [F05, F10, F12-OS1.5] [F06-OS1.2] [F20, F80-OS2.1] [F80, F81-OS2.3] [F20, F30-OS3.1] [F10, F12-OS3.7]
9.9.2.2. Purpose of ExitsN/A
(1)[F10-OS3.7] Applies to portion of Code text “An exit shall be designed for no purpose other than exiting ...”
9.9.2.3. Elevators, Slide Escapes and Windows as Means of EgressN/A
(1)[F10-OS3.7]
9.9.2.4. Principle EntrancesN/A
(1)[F10-OS3.7]
9.9.2.5. Front Edge of Stair TreadsN/A
(1)[F30-OS1.5] [F30-OS3.1]
9.9.2.6. Exterior Exit Stairs that Serve a HotelN/A
(1)[F30-OS1.5] [F30-OS3.1]
9.9.3.2. Exit WidthN/A
(1)[F10-OS3.7]
9.9.3.3. Width of CorridorsN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.9.3.4. Clear HeightN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.9.4.2. Fire Separation for ExitsN/A
(1)[F03-OP1.2] [F03-OS1.2] [F05-OS1.5]
(2)[F03-OP1.2] [F03-OS1.2] [F05-OS1.5]
(3)[F05-OS1.5]
(4)[F03-OS1.2] [F05-OS1.5]
9.9.4.3. Wired Glass or Glass BlockN/A
(2)[F05-OS1.5]
9.9.4.4. Openings Near Unenclosed Exit Stairs and RampsN/A
(1)[F05-OS1.5]
9.9.4.5. Openings in Exterior Walls of ExitsN/A
(1)[F05-OS1.5]
9.9.4.6. Openings Near Exit DoorsN/A
(2)[F05-OS1.5]
9.9.4.7. Stairways in Group D or E BuildingsN/A
(1)[F05-OS1.5]
9.9.5.2. Occupancies in CorridorsN/A
(1)[F10-OS3.7]
9.9.5.3. Obstructions in Public CorridorsN/A
(1)[F30-OS3.1]
9.9.5.4. Obstructions in ExitsN/A
(1)[F10-OS3.7]
9.9.5.5. Obstructions in Means of EgressN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
9.9.5.6. Mirrors or DraperiesN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.9.5.7. Fuel-Fired AppliancesN/A
(1)[F10-OS1.5] [F10-OS3.7]
9.9.5.8. Service RoomsN/A
(1)[F30-OS3.1] [F10-OS3.7]
9.9.5.9. Ancillary RoomsN/A
(1)[F05, F06-OS1.5] [F10-OS3.7]
9.9.6.1. Obstructions by DoorsN/A
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
9.9.6.2. Clear Opening Height at DoorwaysN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.9.6.3. Clear Opening Width at DoorwaysN/A
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
9.9.6.4. Door ActionN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
9.9.6.5. Direction of Door SwingN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7]
(4)[F10-OS3.7]
9.9.6.6. Nearness of Doors to StairsN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F10-OS3.7]
9.9.6.7. Door Latching, Locking and Opening MechanismsN/A
(1)(a) [F10-OS3.7] (b) [F10, F81-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7] [F73-OA1]
(4)[F10-OS3.7]
9.9.6.8. Effort Required to OpenN/A
(1)[F10-OS3.7]
9.9.7.1. Egress from Roof Area, Podiums, Terraces, Platforms and Contained Open SpacesN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
9.9.7.2. Means of Egress from SuitesN/A
(1)[F10-OS1.5]
(2)[F10-OS3.7]
9.9.7.3. Dead End CorridorsN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F31-OS1.2] [F05-OS1.5] [F30-OS3.1] [F10-OS3.7]
9.9.7.4. Number and Spacing of Egress DoorsN/A
(1)[F10-OS3.7]
(2)[F10-OS1.5]
9.9.7.5. Independent Access to ExitN/A
(1)[F10-OS3.7]
9.9.8.2. Number of Required ExitsN/A
(1)[F10-OS3.7]
9.9.8.3. Contribution of Each ExitN/A
(1)[F10-OS3.7]
9.9.8.4. Location of ExitsN/A
(1)[F10-OS1.5]
9.9.8.5. Exiting through a LobbyN/A
(1)[F10-OS1.5]
(2)[F10-OS1.5]
(3)[F10-OS1.5]
(3.1)[F10-OS1.5]
(4)[F10-OS1.5]
(5)[F10-OS1.5]
(6)[F10-OS1.5]
9.9.8.6. Mezzanine Means of EgressN/A
(1)[F05-OS1.5]
(4)[F05-OS1.5]
9.9.9.1. Travel Limit to Exits or Egress DoorsN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7]
9.9.9.2. Two Separate ExitsN/A
(1)[F10-OS3.7]
9.9.9.3. Shared Egress FacilitiesN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
9.9.10.1. Egress Windows or Doors for BedroomsN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10-OS3.7]
(4)[F10-OS3.7]
(5)[F10-OS3.7]
9.9.11.2. Visibility of ExitsN/A
(1)[F10-OS3.7] [F10-OS3.7]
9.9.11.3. Exit SignsN/A
(1)[F10-OS3.7]
(2)[F10-OS3.7]
(3)[F10, F81-OS3.7]
(4)[F10, F81-OS3.7]
(5)[F10-OS3.7]
(6)[F10-OS3.7]
(7)[F10-OS3.7]
9.9.11.4. Signs for Stairs and Ramps at Exit LevelN/A
(1)[F10-OS3.7]
9.9.11.5. Floor NumberingN/A
(1)[F10-OS3.7] [F73-OA1]
9.9.12.2. Required Lighting in Egress FacilitiesN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
9.9.12.3. Emergency LightingN/A
(1)[F30-OS3.1] [F10-OS3.7]
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
(4)[F30-OS3.1] [F10-OS3.7]
(5)[F30-OS3.1] [F10-OS3.7]
(6)[F30-OS3.1] [F10-OS3.7]
(7)[F30-OS3.1] [F10-OS3.7]
9.10.1.2. Testing of Integrated Fire Protection and Life Safety SystemsN/A
(1)[F02,F81,F82-OS1.2,OS1.5] [F02,F81,F82-OP1.2]
9.10.1.3. Items Under Part 3 JurisdictionN/A
(5)[F01-OS1.1] Applies to portion of Code text: “ ... facilities for the dispensing of fuel shall not be installed in any building.”
9.10.3.4. Suspended Membrane CeilingN/A
(1)[F03-OP1.3] [F04-OS1.3]
9.10.4.3. Basement Storage GaragesN/A
(1)[F03-OS1.2] [F03-OP1.2]
9.10.5.1. Permitted Openings in Wall and Ceiling MembranesN/A
(1)[F03-OP1.2] [F04-OP1.3] [F03-OS1.2] [F04-OS1.3]
(2)[F04-OP1.3] [F04-OS1.3]
(2.1)[F03-OP1.2] [F03-OS1.2]
(3)[F04-OP1.3] [F04-OS1.2, OS1.3]
9.10.7.1. Protection of Structural Steel MembersN/A
(1)[F03-OP1.2] [F04-OP1.3] [F03-OS1.2] [F04-OS1.3]
9.10.8.1. Fire-Resistance Ratings for Floors and RoofsN/A
(1)[F03-OP1.2] [F04-OP1.2, OP1.3] Applies to portion of Code text: “Except as other wise provided in this Subsection, the fire-resistance ratings of floors and roofs shall conform to Table 9.10.8.1.” [F03-OS1.2] [F04-OS1.2, OS1.3] Applies to portion of Code text: “Except as otherwise provided in this Subsection, the fire-resistance ratings of floors and roofs shall conform to Table 9.10.8.1.”
9.10.8.2. Fire-Resistance Ratings in Sprinklered BuildingsN/A
(1)(a), (b) [F13-OP1.2] [F02, F82-OP1.3] (a), (b) [F13-OS1.2, OS1.5] [F02, F82-OS1.3]
9.10.8.3. Fire-Resistance Ratings for Walls, Columns and ArchesN/A
(1)[F04-OP1.2, OP1.3] [F04-OS1.2, OS1.3]
(2)[F04-OP1.2, OP1.3] [F04-OP1.2,OP1.3]
9.10.8.4. Support of Noncombustible ConstructionN/A
(1)[F04-OS1.3] [F04-OP1.3]
9.10.8.7. Roofs Supporting an OccupancyN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.8.8. Floors of Exterior PassagewaysN/A
(1)[F06-OP1.2] [F04-OP1.3] [F05-OS1.5] [F06-OS1.2, OS1.5]
9.10.9.2. Continuous BarrierN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
(5)[F03-OP1.2] [F03-OS1.2]
9.10.9.3. Openings to be Protected With ClosuresN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
9.10.9.4. Floor AssembliesN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.9.6. General Requirements for Penetration of Fire SeparationsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
9.10.9.7. Piping PenetrationsN/A
(1)[F03-OS1.2] [F04-OS1.2] [F03-OS1.2] [F04-OS1.3] [F03-OP1.2] [F04-OP1.2] [F03-OS1.2] [F03-OS1.2]
(5)[F03-OS1.2] [F04-OS1.2] [F03-OP1.2] [F04-OP1.2]
9.10.9.8. Penetrations by Outlet Boxes or Service Equipment in Concealed SpacesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(6)[F03-OS1.2] [F04-OS1.2] [F03-OP1.2] [F04-OP1.2]
9.10.9.10. Colapse of Combustible ConstructionsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
9.10.9.12. Concealed Spaces Above Fire SeparationN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
9.10.9.13. Separation of Residential OccupanciesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
9.10.9.14. Residential Suites in Industrial BuildingsN/A
(1)[F02-OS1.2]
(2)[F02, F03-OS1.2]
9.10.9.15. Separation of SuitesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F02-OP1.2] [F02-OS1.2]
9.10.9.16. Separation of Residential SuitesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
9.10.9.17. Separation of Public CorridorsN/A
(1)[F03, F06-OP1.2] [F03, F05-OS1.5] [F06-OS1.2, OS1.5]
(2)[F03-OS1.2] [F06, F05-OS1.5] [F03, F06-OP1.2]
(3)[F03-OS1.2] [F05, F06-OS1.5] [F03, F06-OP1.2]
9.10.9.18. Separation of Storage GaragesN/A
(1), (2)[F03-OP1.2] [F03-OS1.2]
(4)[F01-OS1.1] [F44-OS3.4]
(5)[F01-OS1.1] [F44-OS3.4]
9.10.9.19. Separation of Repair GaragesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F44-OH1.1] [F44-OS1.1] [F44-OS3.4]
(5)[F44-OH1.1] [F44-OS1.1] [F44-OS3.4]
9.10.9.20. Exhaust Ducts Serving More Than One Fire (3)N/A
N/ACompartment
(1)[F03-OS1.2]
(2)[F03-OS1.2]
9.10.9.21. Central Vacuum SystemsN/A
(1)[F03-OS1.2]
9.10.10.3. Separation of Service RoomsN/A
(1)[F03-OP1.2] [F03, F81-OP1.4] [F03-OS1.2] [F03, F81-OS1.4]
9.10.10.4. Location of Fuel Fired AppliancesN/A
(1)[F03-OP1.2] [F03, F81-OP1.4] [F03-OS1.2] [F03, F81-OS1.4]
9.10.10.5. IncineratorsN/A
(1)[F03-OP1.2] [F03, F81-OP1.4] [F03-OS1.2] [F03, F81-OS1.4]
(2)[F01-OS1.1]
(3)[F01-OP1.1] [F20-OP2.1] [F80-OP2.3] [F01-OS1.1] [F20-OS2.1] [F80-OS2.3] [F40, F61-OH1.1, OH1.3]
(4)[F01, F02-OS1.2]
9.10.10.6. Storage RoomsN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.11.1. Required FirewallsN/A
(1)[F03-OP1.2] [F03-OP3.1] [F03-OS1.2]
9.10.11.2. Firewalls Not RequiredN/A
(2)[F03-OP3.1] [F03-OS1.2]
(3)[F03-OP3.1] [F03-OS1.2]
9.10.12.1. Termination of Floors or MezzaninesN/A
(1)[F03-OP1.2, OP1.4] [F03-OS1.5]
9.10.12.2. Location of SkylightsN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.12.3. Exterior Walls Meeting at an AngleN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
9.10.12.4. Protection of SoffitsN/A
(2)[F03-OP1.2] [F03-OS1.2] [F03-OP1.2] [F03-OS1.2]
9.10.13.1. ClosuresN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.13.2. Solid Core Wood Door as a ClosureN/A
(2)[F03-OP1.2] [F03-OS1.2]
9.10.13.5. Wired Glass as a ClosureN/A
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
9.10.13.6. Steel Door FramesN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.13.8. Maximum Size of OpeningN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
9.10.13.9. Door LatchN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.13.10. Self-Closing DeviceN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.13.12. Service Room DoorsN/A
(1)[F10-OS1.5] Applies to portion of Code text: “... but shall swing outward from such rooms in all other cases.” [F30-OS3.1] Applies to portion of Code text: “Swing-type doors shall open into service rooms containing fuel-fired equipment where such doors lead to public corridors or rooms used for assembly ...”
9.10.13.13. Fire DampersN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.13.14. Fire Stop FlapsN/A
(1)[F03-OP1.3] [F03-OS1.3]
9.10.13.15. Doors Between Garages and Houses or Dwelling UnitsN/A
(1)[F01-OS1.1] [F44-OS3.4]
(2)[F01-OS1.1] [F44-OS3.4]
9.10.13.16. Door StopsN/A
(1)[F81-OP1.4] [F81-OS1.4]
9.10.14.4. Openings in Exposing Building FaceN/A
(1)[F03-OP3.1]
(2)[F03-OP3.1]
(6)[F03-OP3.1]
(7)[F03-OP3.1]
9.10.14.5. Construction of Exposing Building Face and Walls above Exposing Building FaceN/A
(1)[F02, F03-OP3.1]
(2)[F02, F03-OP3.1]
(4)[F03-OP3.1]
(6)[F03-OP3.1]
(12)[F03-OP3.1]
9.10.15.3A. Inadequate Firefighting FacilitiesN/A
(1)[F03-OP3.1]
9.10.15.4. Glazed Openings in Exposing Building FaceN/A
(1)[F03-OP3.1]
(7)[F03-OP3.1]
(8)[F03-OP3.1]
9.10.15.5. Construction of Exposing Building Face of HousesN/A
(1)[F02, F03-OP3.1]
(1.1)[F02, F03-OP3.1]
(2)[F02, F03-OP3.1]
(5)[F03-OP3.1]
9.10.16.1. Required Fire Blocks in Concealed SpacesN/A
(1)[F03-OP1.2] [F03-OS1.2]
(3)[F03-OP1.2] [F03-OS1.2]
(4)[F03-OP1.2] [F03-OS1.2]
(5)[F03-OP1.2] [F03-OS1.2]
(6)[F02, F03-OP1.2] [F02, F03-OS1.2]
(7)[F02, F03-OP1.2] [F02, F03-OS1.2]
9.10.16.2. Required Fire Blocks in Wall AssembliesN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.16.3. Fire Block MaterialsN/A
(1)[F03-OP1.2] [F03-OS1.2]
(2)[F03-OP1.2] [F03-OS1.2]
(3)[F04-OP1.2] [F04-OS1.2]
9.10.16.4. Penetration of Fire BlocksN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.17.1. Flame-Spread Rating of Interior SurfacesN/A
(1)[F02-OS1.2]
9.10.17.2. Ceilings in Exits or Public CorridorsN/A
(1)[F05-OS1.5]
9.10.17.3. Walls in ExitsN/A
(1)[F05-OS1.5]
(2)[F05-OS1.5]
9.10.17.4. Exterior Exit PassagewaysN/A
(1)[F05-OS1.5]
9.10.17.5. Walls in Public CorridorsN/A
(1)[F05-OS1.5]
9.10.17.9. Combustible SkylightsN/A
(1)[F02, F05-OS1.5]
9.10.17.10. Protection of Foamed PlasticsN/A
(1)[F01, F02, F05-OS1.5]
(2)[F02-OS1.2] [F05-OS1.5] [F02-OP1.2]
(3)[F01, F02-OS1.2]
9.10.18.1. Access Provided through a FirewallN/A
(1)[F11-OS1.5]
9.10.18.2. Fire Alarm System RequiredN/A
(2)[F11-OS1.5]
9.10.18.4. Rooms and Spaces Requiring Heat Detectors or Smoke DetectorsN/A
(1)[F11-OS1.5]
(2)[F11-OS1.5]
(3)[F02-OS1.2] Applies to sprinklered buildings. [F11-OS1.5] Applies to the supervision of the system and flow alarm.
(4)[F11-OS1.5]
9.10.18.5. Smoke Detectors in Recirculating Air Handling SystemsN/A
(1)[F03-OS1.2]
9.10.18.6. Portions of Buildings Considered as Separate BuildingsN/A
(1)[F03-OS1.2]
(2)[F11-OS1.2]
9.10.18.7. Central Vacuum SystemsN/A
(1)[F03-OS1.2]
9.10.18.9. Fire Alarm System in a HotelN/A
(1)[F11-OS1.5]
9.10.18.10. Commissioning of Life Safety and Fire Protection SystemsN/A
(1)[F02, F81, F82-OS1.2, OS1.5] [F02, F81, F82-OP1.2]
9.10.19.1. Required Smoke AlarmsN/A
(1)[F11, F81-OS1.5]
(2)[F11, F81-OS1.5] [F74-OA2]
(4)[F11, F81-OS1.5] [F74-OA2] [F74-OA2]
9.10.19.2. Sound Patterns of Smoke AlarmsN/A
(1)[F11-OS1.5]
9.10.19.3. Location of Smoke AlarmsN/A
(1)[F11-OS1.5]
(1.1)[F11-OS1.5]
(2)[F11, F81-OS1.5]
(3)[F11-OS1.5]
(4)[F11-OS1.5]
(6)[F11, F81-OS1.5] [F74-OA2]
9.10.19.4. Power SupplyN/A
(1)[F81-OS1.5]
(3)[F81-OS1.5]
9.10.19.5. Interconnection of Smoke AlarmsN/A
(1)[F11-OS1.5]
(2)[F11-OS1.5]
9.10.19.6. Silencing of Smoke AlarmsN/A
(1)[F11, F81-OS1.5]
9.10.19.7. Instructions for Maintenance and CareN/A
(1)[F82-OS1.5]
9.10.19.8. Residential Fire Warning SystemsN/A
(1)[F81, F11-OS1.5]
9.10.20.1. Windows or Access Panels RequiredN/A
(1), (2)[F12-OP1.2] [F12-OS1.2, OS1.5]
9.10.20.2. Access to BasementsN/A
(1)[F12-OP1.2] [F12-OS1.2, OS1.5]
(2)[F12-OP1.2] Applies to portion of Code text: “Access required in Sentence (1) ... provides an opening not less than 1 100 mm high and 550 mm wide, the sill of which shall not be more than 900 mm above the floor.” [F12-OS1.2, OS1.5] Applies to portion of Code text: “Access required in Sentence (1) ... provides an opening not less than 1 100 mm high and 550 mm wide, the sill of which shall not be more than 900 mm above the floor.”
9.10.20.3. Fire Department Access to BuildingsN/A
(2)[F12-OP1.2] [F12-OS1.2, OS1.5]
(2)[F12-OP1.2] [F12-OS1.2, OS1.5]
9.10.20.4. Portable Fire ExtinguishersN/A
(1)[F02, F12, F81-OP1.2] [F81, F02, F12-OS1.2]
9.10.20.5. Freeze Protection for Fire Protection SystemsN/A
(1)[F02, F81-OP1.2] [F02, F81-OS1.2]
9.10.21.2. Separation of Sleeping RoomsN/A
(1)[F03-OP1.2] [F03-OS1.2]
9.10.21.3. Floor Assemblies Between the First and Second StoreyN/A
(1)[F03-OP1.2] [F03-OS1.2, OS1.5]
9.10.21.4. Walkways Connecting BuildingsN/A
(1)[F03-OP1.2] [F03-OP3.1] [F03, F06-OS1.2, OS1.5]
9.10.21.5. Spatial SeparationsN/A
(1)[F03-OP3.1]
9.10.21.6. Flame-Spread RatingsN/A
(1)[F05-OS1.2, OS1.5]
9.10.21.7. Smoke DetectorsN/A
(1)[F11-OS1.5]
9.10.21.8. Portable Fire ExtinguishersN/A
(1)[F02, F12, F81-OP1.2] [F02, F12, F81-OS1.2]
9.10.21.9. Hose StationsN/A
(1)[F02, F12, F81-OP1.2] [F02, F12, F81-OS1.2]
(2)[F12-OP1.2] [F12-OS1.2]
(3)[F12-OP1.2] [F12-OS1.2]
9.10.22.2. Vertical Clearances above CooktopsN/A
(1)[F01-OS1.1, OS1.2]
(2)[F01-OS1.1, OS1.2]
9.10.22.3. Protection Around CooktopsN/A
(1)[F01-OS1.1, OS1.2]
(3)[F01-OS1.1, OS1.2]
9.11.1.1 Required ProtectionN/A
(1)[F56-OH3.1]
(3)[F56-OH3.1]
9.11.1.2. Determination of Sound Transmission RatingsN/A
(1)[F56-OH3.1]
(2)[F56-OH3.1]
9.11.1.4. Adjoining ConstructionN/A
(2)[F56-OH3.1]
(3)[F56-OH3.1]
(4)[F56-OH3.1]
9.12.1.1. Removal of Topsoil and Organic MatterN/A
(1)[F20, F40, F41-OH1.1]
(2)[F81-OP2.3, OP2.4] [F81-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F81-OS1.2] Applies to assemblies required to provide fire resistance. [F81-OS2.3] [F81-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OP2.2] [F20, F21-OP2.3, OP2.4] [F20-OS2.2, OS2.3] [F21-OS2.3] [F20, F21-OS3.1] Applies to floors and elements that support floors. [F20, F21, F40, F41-OH1.1] [F20, F21-OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH4] Applies to floors and elements that support floors.
9.12.1.2. Standing WaterN/A
(1)[F60-OP2.2, OP2.3, OP2.4] [F60-OS2.2, OS2.3] [F60-OS3.1] Applies to floors and elements that support floors. [F60-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F60-OH4] Applies to floors and elements that support floors.
9.12.1.3. Protection from FreezingN/A
(1)[F21-OP2.3, OP2.4] [F21-OS2.3] [F21-OS3.1] Applies to floors and elements that support floors. [F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F21-OH4] Applies to floors and elements that support floors.
9.12.1.4. Precautions During ExcavationN/A
(1)[F20-OP2.3] [F20, F21, F22, F62, F80-OP4.1] [F20, F22, F80-OS2.6]
(2)[F20-OP2.3] [F20, F21, F80-OP4.1] [F20, F80-OS2.6]
9.12.2.1. Excavation to Undisturbed SoilN/A
N/A[F20-OP2.2, OP2.3, OP2.4]
(1)[F20-OS2.2, OS2.3] [F20-OS3.1] Applies to floors and elements that support floors. [F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors.
9.12.2.2. Minimum Depth of FoundationsN/A
(1)[F21-OP2.3, OP2.4] [F21-OS2.3] [F21-OS3.1] Applies to floors, elements that support floors, and concrete steps with more than 2 risers. [F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F21-OH4] Applies to floors and elements that support floors.
9.12.3.1. Placement of BackfillN/A
(1)[F81-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F81-OP2.1] [F22-OP2.4] [F81-OP2.3] Applies to elements that support or are part of an environmental separator. [F81-OS2.1] [F81-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.12.3.2. Grading of BackfillN/A
(1)[F60, F61-OH1.1, OH1.2, OH1.3] [F60, F61-OP2.3] [F60, F61-OS2.3]
9.12.3.3. Deleterious Debris and BouldersN/A
(1)[F81-OH1.1, OH1.2, OH1.3] [F81-OP2.3] [F81-OS2.3] [F81-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3] [F20-OS2.1, OS2.3] [F20-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3] [F20-OS2.1, OS2.3] [F20-OS3.1] Applies to floors and elements that support floors.
9.12.3.4. Lateral Support of Foundation WallN/A
(1)[F20, F22-OP2.1] [F20, F22-OS2.1]
9.12.4.1. Support of FootingsN/A
(1)[F21-OH1.1, OH1.2, OH1.3] [F21-OH2.1] Applies to sewer-line locations beneath footings. [F21-OP2.2] [F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F21-OS2.1] [F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F21-OS3.1] Applies to floors and elements that support floors.
9.13.2.1. Required DampproofingN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.13.2.2. Dampproofing MaterialsN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
9.13.2.3. Preparation of SurfaceN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(3)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(4)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(5)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(6)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
9.13.2.4. Application of Dampproofing MaterialN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(3)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
9.13.2.5. Moisture Protection for Interior FinishesN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2]
(3)[F61-OS2.3] [F61-OH1.1, OH1.2]
9.13.2.6. Dampproofing of Floors-on-GroundN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
9.13.2.7. Dampproofing of Preserved Wood Foundation WallsN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
9.13.3.1. Required WaterproofingN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
9.13.3.2. Waterproofing MaterialsN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
9.13.3.3. Preparation of SurfacesN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(2)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(3)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(4)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
(5)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
9.13.3.4. Application of Waterproofing MembranesN/A
(1)[F61-OH1.1, OH1.2, OH1.3]
9.13.3.5. Floor Waterproofing SystemN/A
(1)[F61-OS2.3] [F61-OH1.1, OH1.2, OH1.3]
9.13.4.1. Application and ScopeN/A
(3)[F40-OH1.1]
9.13.4.2. Protection from Soil Gas IngressN/A
(1)[F40-OH1.1]
(1.2)[F40-OH1.1]
(2)[F40-OH1.1]
(3)[F40-OH1.1]
9.13.4.3. Providing for the Rough-In for a Subfloor Depressurization SystemN/A
(1)[F40-OH1.1]
(2)[F40-OH1.1]
(3)[F40-OH1.1]
9.14.2.1. Foundation Wall DrainageN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
(1.1)[F60-OH1.1, OH1.2, OH1.3]
(2)(a) [F60-OH1.1, OH1.2, OH1.3] Applies where foundations serve as or support an environmental separator. (a) [F60-OS2.1] (a) [F60-OS2.3] Applies where foundations serve as or support an environmental separator. (b) [F21-OH1.1, OH1.2, OH1.3] Applies where foundations serve as or support an environmental separator. (b) [F21-OH4.1] Applies where foundations support floors or elements supporting floors. (b) [F21-OP2.1] (b) [F21-OP2.3] Applies where foundations serve as or support an environmental separator. (b) [F21-OP2.4] Applies where foundations support walls or floors. (b) [F21-OS2.1] (b) [F21-OS2.3] Applies where foundations serve as or support an environmental separator. (b) [F21-OS3.1] Applies where foundations support floors or elements supporting floors. (b) [F21-OS3.7] Applies where foundations support walls that contain windows or doors required for emergency egress.
(3)[F60-OH1.1, OH1.2, OH1.3]
9.14.3.1. Material StandardsN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.3] [F60-OS2.1, OS2.3]
9.14.3.2. Minimum SizeN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
9.14.3.3. InstallationN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
(2)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
(3)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
(4)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
9.14.4.1. Type of Granular MaterialN/A
(1)(a) [F60-OH1.1, OH1.2, OH1.3] (a) [F60-OP2.3] [F21-OP2.6] (a) [F21-OS2.2] [F60-OS2.3] (b) [F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. (b) [F21-OH4] Applies to floors and elements that support floors. (b) [F21-OP2.1, OP2.4] (b) [F21-OP2.3] Applies to elements that support or are part of an environmental separator. (b) [F21-OS2.1] (b) [F21-OS2.3] Applies to elements that support or are part of an environmental separator (b) [F21-OS3.1] Applies to floors and elements that support floors.
9.14.4.2. InstallationN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
9.14.4.3. GradingN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
9.14.4.4. Wet Site ConditionsN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
9.14.5.1. Drainage DisposalN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
9.14.5.2. Sump PitsN/A
(1)(a),(b) [F60,F61-OH1.1,OH1.3] (c) [F40-OH1.1] [F52-OH1.2] (a),(b) [F60,F61-OS2.1,OS2.3] (c) [F52-OS2.3] (a),(b) [F60,F61-OP2.3,OP2.4] (c) [F52-OP2.3] (c) [F30-OS3.1]
(2)[F30-OS3.1] [F40-OH1.1]
(3)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
9.14.5.3. Dry WellsN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
(2)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
9.14.6.1. Surface DrainageN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.2, OP2.3] [F60-OS2.1, OS2.2, OS2.3]
9.14.6.2. Drainage away from Wells or Leaching BedsN/A
(1)[F46-OH2.2] Applies to directing drainage away from the location of a water supply. [F44-OH2.1] Applies to directing drainage away from a septic tank disposal system.
9.14.6.3. Window WellsN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OP2.1, OP2.3] [F60-OS2.1, OS2.3]
9.14.6.4. Catch BasinN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F61-OP2.3] [F61-OS2.3] [F61-OS3.1]
9.15.1.3. Foundations for Deformation Resistant BuildingsN/A
(1)[F20-OP2.2] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20-OS2.2] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.15.2.2. Unit Masonry ConstructionN/A
(1)[F20-OP2.1] [F21, F61-OP2.4] [F20, F21, F61-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F61-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F21, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F61-OS3.1] Applies to floors and elements that support floors.
(3)(a) [F20-OP2.1] (a) [F80-OP2.4] (a) [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator. (a) [F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. (a) [F20, F80-OH4] Applies to floors and elements that support floors. (a) [F20-OS2.1] (a) [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator. (a) [F20, F80-OS3.1] Applies to floors and elements that support floors. (b) [F20-OP2.1] (b) [F20-OP2.4] (b) [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator. (b) [F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. (b) [F20, F80-OH4] Applies to floors and elements that support floors. (b) [F20-OS2.1] (b) [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator. (b) [F20, F80-OS3.1] Applies to floors and elements that support floors. (c) [F20-OP2.1] (c) [F61-OP2.4] (c) [F20, F61-OP2.3] Applies to elements that support or are part of an environmental separator. (c) [F20, F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. (c) [F20, F61-OH4] Applies to floors and elements that support floors. (c) [F20-OS2.1] (c) [F20, F61-OS2.3] Applies to elements that support or are part of an environmental separator. (c) [F20, F61-OS3.1] Applies to floors and elements that support floors.
9.15.2.2. Pier Type FoundationsN/A
(1)[F20-OP2.1, OP2.2] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.2] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.1, OP2.2] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.2] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(4)[F20-OP2.1, OP2.4] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.4] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.15.2.4. Wood Frame FoundationsN/A
(1)(a) [F20-OP2.1, OP2.2] (a) [F20, F80-OP2.3] Applies to elements support or are part of an environmental separator. (a) [F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. (a) [F20, F80-OH4] Applies to floors and elements that support floors. (a) [F20-OS2.1, OS2.2] (a) [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator. (a) [F20, F80-OS3.1] Applies to floors and elements that support floors.
9.15.3.1. Footings RequiredN/A
(1)[F20-OP2.2] [F20, F21-OP2.4] [F20, F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH4] Applies to floors and elements that support floors. [F20-OS2.2] [F20, F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS3.1] Applies to floors and elements that support floors.
9.15.3.2. Support of FootingsN/A
(1)[F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F21-OH4] Applies to floors and elements that support floors. [F21-OP2.4] [F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F21-OS2.4] [F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F21-OS3.1] Applies to floors and elements that support floors.
(2)[F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F21-OH4] Applies to floors and elements that support floors. [F21-OP2.1, OP2.4] [F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F21-OS2.1] [F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F21-OS3.1] Applies to floors and elements that support floors.
9.15.3.4. Basic Footing Widths and AreasN/A
(1)[F20-OP2.1] [F21-OP2.4] [F20, F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH4] Applies to floors and elements that support floors. [F20-OS2.2] [F20, F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.2] [F21-OP2.4] [F20, F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH4] Applies to floors and elements that support floors. [F20-OS2.2] [F20, F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OP2.2] [F21-OP2.4] [F20, F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH4] Applies to floors and elements that support floors. [F20-OS2.2] [F20, F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS3.1] Applies to floors and elements that support floors.
9.15.3.5. Adjustments to Footing Widths for Exterior WallsN/A
(1)[F20-OP2.2, OP2.3] [F21-OP2.3, OP2.4] [F20-OS2.2, OS2.3] [F21-OS2.3] [F20, F21-OH1.1, OH1.2, OH1.3] [F20, F21-OH4] Applies to floors and elements that support floors. [F20, F21-OS3.1] Applies to floors and elements that support floors.
9.15.3.6. Adjustments to Footing Widths for Interior WallsN/A
(1)[F20-OP2.2] [F21-OP2.4] [F20, F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH4] Applies to floors and elements that support floors. [F20-OS2.2] [F20, F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.2] [F10-OS2.2]
9.15.3.7. Adjustments to Footing Area for ColumnsN/A
(1)[F20-OP2.2] [F21-OP2.4] [F20, F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH4] Applies to floors and elements that support floors. [F20-OS2.2] [F20, F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS3.1] Applies to floors and elements that support floors.
9.15.3.8. Footing ThicknessN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.15.3.9. Step FootingsN/A
(1)[F20, F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] Applies where the foundation supports or is part of an environmental separator. [F20, F22-OH4] Applies to foundations that support floors. [F20, F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to foundations that support floors.
9.15.4.1. Flat Wall Insulating Concrete Form UnitsN/A
(1)[F22, F55, F63-OH1.1, OH1.2, OH1.3]
9.15.4.2. Foundation Wall Thickness and Required LateralN/A
N/ASupport
(1)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2.1)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(4)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS3.2, OS2.4] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(5)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(6)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(7)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to floor and elements that support floors.
9.15.4.5. Reinforcement for Flat Insulating Concrete Form Foundation WallsN/A
(1)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to floors and elements that support floors.
(4)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.15.4.6. Extension above Ground LevelN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OP2.3] [F61-OS2.3]
9.15.4.7. Reduction in ThicknessN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.15.4.9. Crack Control JointsN/A
(1)[F21-OP2.3] [F21-OS2.3] [F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
(2)[F20-OP2.1] [F20, F61-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
9.15.5.1. Support of Floor JoistsN/A
(1)[F20-OP2.1, OP2.4] [F20-OP2.3] [F40, F61-OP2.3, OP2.4] Applies to elements that support or are part of an environmental separator. [F20, F40, F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F40, F61-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F40, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F40, F61-OS3.1] Applies to floors and elements that support floors.
9.15.5.2. Support of BeamsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F80-OH4] Applies to floors and elements that support floors. [F80-OP2.3, OP2.4] Applies to elements that support or are part of an environmental separator. [F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F80-OS3.1] Applies to floors and elements that support floors.
9.15.5.3. PilastersN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.15.6.2. Foundation Walls Above GroundN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OP2.3] [F61-OS2.3]
9.15.6.3. Form TiesN/A
(1)[F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F61-OP2.3] Applies to elements that support or are part of an environmental separator. [F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F30-OS3.1]
9.16.1.3. Required Floors-on-GroundN/A
(1)(a), (b) [F30-OS3.1] (a), (b) [F40-OH2.4]
9.16.2.1. Required Installation of Granular FillN/A
(1)[F40, F61-OH1.1] [F61, F60-OH1.2, OH1.3] [F60-OS2.3]
9.16.2.2. Support of FloorsN/A
(1)[F21-OH1.1, OH1.2, OH1.3] [F21-OP2.1, OP2.3, OP2.4] [F21-OS2.1, OS2.3] [F21-OS3.1]
(2)[F21-OH1.1, OH1.2, OH1.3] [F21-OP2.1, OP2.3, OP2.4] [F21-OS2.1, OS2.3] [F21-OS3.1]
(3)[F22-OS3.1]
9.16.3.1. Control of Water IngressN/A
(1)[F60-OH1.1, OH1.2, OH1.3] [F60-OS2.3] [F60-OS3.1]
9.16.3.2. Hydrostatic PressureN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OP2.1] [F61-OP2.6] [F20-OS2.1] [F61-OS2.3] [F20-OS3.1]
9.16.3.3. Floor DrainsN/A
(1)[F62-OH1.1, OH1.2, OH1.3] [F62-OS2.3] [F62-OS3.1]
9.16.4.1. Surface FinishN/A
(1)[F30, F80-OS3.1] [F40-OH2.4] [F62-OH1.1, OH1.2, OH1.3]
(2)[F20, F80-OS3.1] [F41-OH1.1]
9.16.4.2. Topping CourseN/A
(1)[F20, F80-OS3.1]
(2)[F20, F80-OS3.1]
9.16.4.3. ThicknessN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OH4] [F20-OP2.1, OP2.3] [F20-OS2.1, OS2.3] [F20-OS3.1]
9.16.4.4. Bond BreakN/A
(1)[F21-OS3.1]
9.16.5.1. Wood Frame FloorsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies where wood-frame floors-on-ground serve as an environmental separator. [F20-OH4] [F20-OP2.1] [F20-OP2.3] Applies where wood-frame floors-on-ground serve as an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies where wood-frame floors-on-ground serve as an environmental separator. [F20-OS3.1]
9.17.2.1. LocationN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.2, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.2] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.17.2.2. Lateral SupportN/A
(1)[F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F22-OP2.4, OP2.5] [F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F22-OS2.4, OS2.5] [F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F22-OP2.4, OP2.5] [F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F22-OS2.4, OS2.5] [F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.17.3.1. Size and ThicknessN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.17.3.2. End Bearing PlatesN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.17.3.3. PaintN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OP2.3, OP2.4] [F80-OH4] Applies to floors and elements that support floors. [F80-OS2.3] [F80-OS3.1] Applies to floors and elements that support floors.
9.17.3.4. Design of Adjustable Steel ColumnsN/A
(1)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.17.4.1. Column SizesN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.17.4.2. MaterialsN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.17.4.3. Columns in Contact with ConcreteN/A
(1)[F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F80-OH4] Applies to floors and elements that support floors. [F80-OP2.4] [F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F80-OS3.1] Applies to floors and elements that support floors.
9.17.4.4. Wood Column Termite ProtectionN/A
(1)[F80, F82-OP2.3, OP2.4] [F80, F82-OS2.3]
9.17.5.1. MaterialsN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F11-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.17.5.2. SizesN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.17.6.2. SizesN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.18.2.1. Access OpeningsN/A
(1)[F82-OH1.1, OH1.2]
(2)[F42-OH2.4, OH2.5] Applies where crawl spaces are heated or unheated and access is from the exterior. [F51, F63-OS2.3] Applies where crawl spaces are unheated and access is from the interior. [F42, F61-OS2.3] Applies where crawl spaces are heated or unheated and access is from the exterior. [F63-OS2.3] Applies where crawl spaces are unheated and access is from the interior. [F42, F61-OS2.3] Applies where crawl spaces are heated or unheated and access is from the exterior.
9.18.3.1. Ventilation of Unheated Crawl SpacesN/A
(1)[F62-OH1.1] [F62-OS2.3]
(2)[F62-OH1.1] [F62-OS2.3]
(3)(a) [F62-OH1.1, OH1.2] (a), (b) [F42, F61, F62-OS2.3] (b) [F42, F61-OH1.1, OH1.2] (b) [F42-OH2.3, OH2.5]
9.18.4.1. Access Way to ServicesN/A
(1)[F82-OH1.1, OH1.2] [F82-OH2.1]
9.18.5.1. DrainageN/A
(1)[F60-OH1.1, OH1.2] [F60-OS2.3]
9.18.6.1. Ground Cover in Unheated Crawl SpacesN/A
(1)[F61-OH1.1, OH1.2] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2] [F61-OS2.3]
9.18.6.2. Ground Cover in Heated Crawl SpacesN/A
(1)[F40, F61-OH1.1] [F61-OH1.2] [F61-OS2.3]
(2)[F40, F61-OH1.1] [F61-OH1.2] [F61-OS2.3]
(3)[F40-OH1.1]
(4)[F40,F61-OH1.1,OH1.2] [F61-OS2.3]
9.18.7.1. Crawl Spaces as Warm Air PlenumsN/A
(1)[F51-OH1.1, OH1.2] [F51-OS2.3]
(2)[F02-OS1.2]
(3)[F01-OS1.1]
(4)[F01-OS1.1]
9.19.1.1. Required VentingN/A
(1)[F51, F62-OS2.3] [F51, F62-OH1.1, OH1.2] [F51-OH1.3] Applies to sloped roof assemblies that may be subject to ice damming.
9.19.1.2. Vent RequirementsN/A
(1)[F51, F62-OS2.3] [F51, F62-OH1.1, OH1.2] [F51-OH1.3] Applies to sloped roof assemblies that may be subject to ice damming.
(2)[F51, F62-OS2.3] [F51, F62-OH1.1, OH1.2] [F51-OH1.3] Applies to sloped roof assemblies that may be subject to ice damming.
(3)[F51, F62-OS2.3] [F51, F62-OH1.1, OH1.2] [F51-OH1.3] Applies to sloped roof assemblies that may be subject to ice damming.
(4)[F51, F62-OS2.3] [F51, F61-OH1.1, OH1.2] [F51-OH1.3] Applies to sloped roof assemblies that may be subject to ice damming.
(5)[F42, F51, F61, F62-OS2.3] [F42-OH1.1] Applies to resistance to the entry of insects. [F51, F61, F62-OH1.1, OH1.2, OH1.3] [F42-OH2.5] Applies to resistance to the entry of insects.
9.19.1.3. ClearancesN/A
(1)[F51, F62-OH1.1, OH1.2, OH1.3] [F51, F62-OS2.3]
(2)[F51, F62-OH1.1, OH1.2, OH1.3] [F51, F62-OS2.3]
(3)[F51, F62-OH1.1, OH1.2, OH1.3] [F51, F62-OS2.3]
9.19.2.1. AccessN/A
(1)[F82-OH1.1, OH1.2, OH1.3] [F82-OS2.3]
(2)[F82-OH1.1, OH1.2] [F82-OS2.3]
(3)[F42-OH1.1] Applies where access is from an unheated enclosed space. [F51-OH1.2] Applies where access is from an interior heated space. [F42-OH1.1] [F61-OH1.1, OH1.2, OH1.3] Applies where access is from the exterior. [F42-OH2.5] Applies where access is from the exterior or an unheated enclosed space. [F42, F61-OS2.3] Applies where access is from the exterior or an unheated enclosed space.
9.20.2.1. Masonry Unit StandardsN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F80-OH4] Applies to floors and elements that support floors. [F01-OP1.2] Applies to masonry used in chimneys and fireplaces. [F20, F80-OP1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F01-OS1.1, OS1.2] Applies to masonry used in chimneys and fireplaces. [F20, F80-OS1.2] Applies to assemblies 9.20.2.4. Cellular Concrete required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.4] Applies to masonry used in chimneys and fireplaces.
9.20.2.2. Used BrickN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F80-OH4] Applies to floors and elements that support floors. [F01-OP1.2] Applies to masonry used in chimneys and fireplaces. [F20, F80-OP1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F01-OS1.1, OS1.2] Applies to masonry used in chimneys and fireplaces. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.4] Applies to masonry used in chimneys and fireplaces.
9.20.2.3. Glass BlocksN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20-OH4] Applies to floors and elements that support floors. [F01, F20-OP1.1] [F20-OP1.2] Applies to assemblies required to provide fire resistance. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F01, F20-OS1.1] [F20-OS1.2] Applies to assemblies required to provided fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS3.1] Applies to floors and elements that support floors. [F01, F20-OS3.4] Applies to masonry used in chimneys and fireplaces.
9.20.2.4. Cellular ConcreteN/A
(1)[F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F80-OH4] Applies to floors and elements that support floors. [F80-OP1.2] Applies to masonry used in chimneys and fireplaces. [F80-OS1.2] Applies to masonry used in chimneys and fireplaces. [F80-OP1.2, OP2.4] [F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F80-OS2.1] [F80-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F80-OS3.1] Applies to floors and elements that support floors. [F80-OS3.4] Applies to masonry used in chimneys and fireplaces.
9.20.2.5. StoneN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F80-OH4] Applies to floors and elements that support floors. [F01, F20, F80-OP1.2] Applies to masonry used in chimneys and fireplaces. [F20, F80-OP1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F01-OS1.1, OS1.2] Applies to masonry used in chimneys and fireplaces. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, 80-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture.
9.20.2.6. Concrete Units Exposed to the WeatherN/A
(1)[F61, F80-OH1.1, OH1.2, OH1.3] [F80-OH4] Applies to floors and elements that support floors. [F80-OP2.1, OP2.3] [F61-OP2.3] [F80-OP1.2] Applies to concrete blocks in chimneys and fireplaces. [F80-OS2.1, OS2.3] [F61-OS2.3] [F80-OS3.1] Applies to elements that support floors. [F80-OS3.4] Applies to masonry used in chimneys and fireplaces.
9.20.2.7. Compressive StrengthN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental and to masonry used in chimneys and fireplaces. [F20, F80-OH4] Applies to floors and elements that support floors. [F01, F20, F80-OP1.2] Applies to masonry used in chimneys and fireplaces. [F20, F80-OP1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F01-OS1.1, OS1.2] Applies to masonry used in chimneys and fireplaces. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.4] Applies to masonry used in chimneys and fireplaces.
9.20.3.1. Mortar MaterialsN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F80-OH4] Applies to floors and elements that support floors. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements support or are part of an environmental separator. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS3.1] Applies to floors and elements that support floors.
(3) 
(4)[F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F21-OH4] Applies to floors and elements that support floors. [F21-OP2.1, OP2.4] [F21-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F21-OS1.2] Applies to assemblies required to provide fire resistance. [F21-OS2.1] [F21-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F21-OS3.1] Applies to floors and elements that support (5) floors.
9.20.3.2. Mortar and Grout MixesN/A
(1)[F20, F21, F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F21, F61-OH4] Applies to floors and elements that support floors. [F20, F21, F61-OP2.1, OP2.4] [F20, F21, F61-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F21, F61-OS2.1] [F20, F21, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F61-OS3.1] Applies to floors and elements that support floors.
(2)(a) [F21, F55, F61-OH1.1, OH1.2, OH1.3] (a) [F21, F55, F61-OP2.1, OP2.3] (a) [F21, F55, F61-OS2.1, OS2.3] (b) [F2-OP2.1] (b) [F21, F44-OS1.2] Applies to assemblies required to provide fire resistance. (b) [F21-OS2.1]
(3)[F20, F21, F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F21, F61-OH4] Applies to floors and elements that support floors. [F20, F21, F61-OP2.1, OP2.4] [F20, F21, F61-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F21, F61-OS2.1] [F20, F21, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F61-OS3.1] Applies to floors and elements that support floors.
(4)[F20, F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F21-OH4] Applies to floors and elements that support floors. [F20, F21-OP2.1, OP2.4] [F20, F21-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F21-OS2.1] [F20, F21-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OS3.1] Applies to floors and elements that support floors. [F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(5)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(6)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(7)[F20, F21, F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20, F21, F61-OH4] Applies to floors and elements that support floors. [F20, F21, F61-OP2.1, OP2.4] [F20, F21, F61-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F61-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F21, F61-OS2.1] [F20, F21, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F61-OS3.1] Applies to floors and elements that support floors.
9.20.4.1. ThicknessN/A
(1)[F20, F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F61-OH4] Applies to floors and elements that support floors. [F20, F61-OP2.1, OP2.4] [F20, F61-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F61-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F61-OS2.1] [F20, F61-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F61-OS3.1] Applies to floors and elements that support floors.
(2)[F20, F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F61-OH4] Applies to floors and elements that support floors. [F20, F61-OP2.1, OP2.4] [F20, F61-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F61-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F61-OS2.1] [F20, F61-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F61-OS3.1] Applies to floors and elements that support floors.
9.20.4.2. Masonry UnitsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator and to masonry used in chimneys and fireplaces. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.5.1. Masonry SupportN/A
(1)[F20, F21-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F21-OH4] Applies to floors and elements that support floors. [F20, F21-OP2.1, OP2.4] [F20, F21-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F21-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F21-OS2.1] [F20, F21-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F21-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.2] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.5.2. Lintels or ArchesN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22–OP2.1, OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F22-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OP2.1, OP2.3, OP2.4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F22-OS2.1, OS2.3]
(3)[F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OP2.1, OP2.3, OP2.4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F22-OS2.1, OS2.3] (3.1) [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OP2.1, OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F22-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator.
(4)[F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F80-OH4] Applies to floors and elements that support floors. [F80-OP2.1, OP2.4] [F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F80-OS2.1] [F80-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F80-OS3.1] Applies to floors and elements that support floors. [F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(5)[F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OP2.1, OP2.3, OP2.4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F22-OS2.1, OS2.3]
(6)[F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OP2.1, OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F22-OS2.1] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator.
9.20.6.1. Thickness of Exterior WallsN/A
(1)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1.OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support are or part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are 9.20.6.4. Masonry Veneer part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.20.6.2. Cavity WallsN/A
(1)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assembles required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22, F61-OP2.3] Applies to elements that support or are part of an environmental separator. [F61-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22, F61-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors [F20, F22, F61-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors.
(3)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors.
9.20.6.3. Thickness of Interior WallsN/A
(2)(b) [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.5] (b) [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.5]
9.20.6.4. Masonry VeneerN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.5] [F20, F22-OP2.3] Applies to elements that are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that are part of an environmental separator.
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OP2.3] [F61-OS1.2] Applies to assemblies required to provide fire resistance. [F61-OS2.3] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
9.20.6.5. Parapet WallsN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.5] [F20-OS2.1, OP2.3, OP2.5] [F22-OS2.5] [F20, F22-OH1.1, OH1.2, OH1.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OP2.3] [F61-OS1.2] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OP2.3] [F61-OS1.2] [F61-OS2.3]
9.20.7.1. Maximum DimensionsN/A
(1)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.20.7.2. Minimum Wall ThicknessN/A
(1)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are a part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.20.7.3. Separation of Chases and RecessesN/A
(1)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.20.7.4. Non-Conforming Chases or RecessesN/A
(1)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.20.7.5. Chases or Recesses Cut into WallsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.8.1. Capping of Hollow Masonry WallsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.8.2. Cavity Walls Supporting Framing MembersN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F80-OP2.3] [F80-OS2.3]
(3)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.8.3. Bearing of Beams and JoistsN/A
(1)[F20-OP2.1] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator.
(2)[F20-OP2.1] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator.
(3)[F20-OP2.1] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator.
9.20.8.4. Support of Beams and ColumnsN/A
(1)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.2] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(4)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5]
[F22-OS2.5]
[F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator.
[F20, F22-OS3.1] Applies to floors and elements that support floors. 


 
(5)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.4, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.20.8.5. Projection of Masonry Veneer Beyond Supporting MembersN/A
(1)[F20-OP2.1, OP2.4, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator.
9.20.9.1. Joints to be Offset or ReinforcedN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.9.2. Bonding or Tying of Other than Masonry VeneerN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contains doors or windows required for emergency egress.
9.20.9.3. BondingN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.9.4. TyingN/A
(2)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OH4] Applies to floors and elements that support floors. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OH4] Applies to floors and elements that support floors. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows for emergency egress.
(4)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OH4] Applies to floors and elements that support floors. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors and windows required for emergency egress.
(5)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(6)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(7)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(8)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(9)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.9.5. Ties for Masonry VeneerN/A
(1)[F20, F22, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OP2.1] [F20, F22, F80-OP2.5] [F20, F22, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS2.1] [F20, F22, F80-OS2.5] [F20, F22, F80-OS2.3] Applies to elements that support or are part of an environmental separator.
(2)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OP2.1] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator.
(4)[F20, F22, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OP2.1] [F20, F22, F80-OP2.5] [F20, F22, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS2.1] [F20, F22, F80-OS2.5] [F20, F22, F80-OS2.3] Applies to elements that support or are part of an environmental separator.
9.20.9.6. Reinforcing for Glass BlockN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that are part of an environmental separator. [F20-OP2.1] [F20-OP2.3] Applies to elements that are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that are part of an environmental separator.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that are part of an environmental separator. [F20-OP2.1] [F20-OP2.3] Applies to elements that are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that are part of an environmental separator.
9.20.10.1. Lateral Support RequiredN/A
(1)[F20-OP2.1] [F20, F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OP2.1, OP2.4] [F20, F22-OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5]
(a)[F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
(a)[F20, F22-OH4] Applies to floors and elements that support floors.
(a)[F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator.
(a)[F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator.
(a)[F20, F22-OS3.1] Applies to floors and elements that support floors.
(4)[F20-OP2.1] [F20, F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.20.11.1. Anchorage to Floor or Roof Assemblies where Masonry Walls Require Lateral SupportN/A
(1)[F20-OP2.1] [F20, F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OH4] Applies to floors and elements that support floors. [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(4)[F20-OP2.1] [F20, F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.20.11.2. Bonding and Tying of Intersecting Masonry Walls where Walls Require Lateral SupportN/A
(1)[F20-OP2.1] [F20, F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(3)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support floors or are part of an environmental separator. [F20, F80-OH4] Applies to floors and elements that support floors. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.20.11.3. Anchoring Intersecting Wood Frame Walls to Masonry WallsN/A
(1)[F20, F22, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22, F80-OH4] Applies to floors and elements that support floors. [F20, F22, F80-OS1.2] Applies to assemblies to provide fire resistance. [F20, F80-OS2.1] [F20, F22, F80-OS2.5] [F20, F22, F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22, F80-OS3.1] Applies to floors and elements that support floors. [F20, F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F80-OP2.1] [F20, F22, F80-OP2.4, OP2.5] [F20, F22, F80-OP2.3] Applies to elements that support or are part of an environmental separator.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.11.4. Anchoring Wood Frame Roof Systems to Masonry WallsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3] [F20-OS2.1, OS2.3]
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3] [F20-OS2.1, OS2.3]
9.20.11.5. Anchoring Masonry Cornices, Sills and Trim to Masonry WallsN/A
(1)[F20, F80-OS2.1, OS2.3, OS2.5] [F22-OS2.5]
9.20.11.6. Anchoring to Masonry PiersN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.12.1. CorbellingN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator.
9.20.12.2. Corbelling for Cavity WallsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.12.3. Corbelling for Masonry VeneerN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator.
9.20.13.1. Materials for FlashingN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3] [F80-OS1.2] Applies to assemblies required to provide fire resistance. [F80-OS2.1, OS2.3]
(2)[F80-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3] [F80-OS1.2] Applies to assemblies required to provide fire resistance. [F80-OS2.1, OS2.3]
9.20.13.2. Fastening of FlashingN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3] [F80-OS1.2] Applies to assemblies required to provide fire resistance. [F80-OS2.1, OS2.3]
9.20.13.3. Location of FlashingN/A
(1)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OP2.1, OP2.3] [F61, F62-OS2.1, OS2.3]
(2)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OP2.1, OP2.3] [F61, F62-OS2.1, OS2.3]
9.20.13.4. Extension of FlashingN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OP2.1, OP2.3] [F61-OS1.2] Applies to assemblies required to provide fire resistance. [F61-OS2.1, OS2.3]
9.20.13.5. Flashing for Weep Holes in Masonry Veneer/Masonry WallsN/A
(1)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OP2.1, OP2.3] [F61-OS1.2] Applies to assemblies required to provide fire resistance. [F61, F62-OS2.1, OS2.3]
9.20.13.6. Flashing for Weep Holes in Masonry VeneerN/A
(2)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OP2.1, OP2.3] [F61-OS1.2] Applies to assemblies required to provide fire resistance. [F61, F62-OS2.1, OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OP2.1, OP2.3] [F61-OS1.2] Applies to assemblies required to provide fire resistance. [F61-OS2.1, OS2.3]
9.20.13.7. Flashing JointsN/A
(1)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OP2.1, OP2.3] [F61-OS1.2] Applies to assemblies required to provide fire resistance. [F61, F62-OS2.1, OS2.3]
9.20.13.8. Required Weep HolesN/A
(1)[F62-OH1.1, OH1.2, OH1.3] [F62-OP2.1, OP2.3] [F62-OS1.2] Applies to assemblies required to provide fire resistance. [F62-OS2.1, OS2.3]
(3)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OP2.1, OP2.3] [F61, F62-OS2.1, OS2.3]
9.20.13.9. Protection of Interior FinishN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OP2.1, OP2.3] [F61-OS2.1, OS2.3]
(2)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OP2.1, OP2.3] [F61, F62-OS2.1, OS2.3]
9.20.13.10. Mortar DroppingsN/A
(1)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OP2.1, OP2.3] [F61, F62-OS1.2] Applies to assemblies required to provide fire resistance. [F61, F62-OS2.1, OS2.3]
9.20.13.12. Drips Beneath Window SillsN/A
(1)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OP2.1, OP2.3] [F61, F62-OS1.2] Applies to assemblies required to provide fire resistance. [F61, F62-OS2.1, OS2.3]
9.20.14.1. Laying Temperature of Mortar and MasonryN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OH4] Applies to floors and elements that support floors. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS1.3] [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20, F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F80-OH4] Applies to floors and elements that support floors. [F20, F80-OP2.1, OP2.4] [F20, F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F80-OS1.3] [F20, F80-OS2.1] [F20, F80-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F20, F80-OS3.1] Applies to floors and elements that support floors. [F20, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.20.14.2. Protection from WeatherN/A
(1)[F80-OP2.1, OP2.3] [F80-OS2.1, OS2.3]
9.20.15.1. Amount of ReinforcementN/A
(1)[F20-OP2.1, OP2.3] [F20-OS2.1, OS2.3]
9.20.15.2. Installation StandardN/A
(1)[F20-OP2.1, OP2.3] [F20-OS2.1, OS2.3]
9.20.16.1. Corrosion Resistance of ConnectorsN/A
(1)[F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F80-OH4] Applies to floors and elements that support floors. [F80-OP2.1, OP2.4] [F80-OP2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F80-OS1.2] Applies to assemblies required to provide fire resistance. [F80-OS2.1] [F80-OS2.3] Applies to elements that support or are part of an environmental separator or are exposed to moisture. [F80-OS3.1] Applies to floors and elements that support floors. [F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.20.17.1. Thickness of Flat Insulating Concrete Form WallsN/A
(1)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.20.17.2. Reinforcement for Flat Insulating Concrete Form WallsN/A
(1)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.20.17.3. Openings in Flat Non-Loadbearing Insulating Concrete Form WallsN/A
(1)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(4)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(5)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(6)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.20.17.4. Openings in Loadbearing Flat Insulating Concrete Form WallsN/A
(1)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(4)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OH4] Applies to floors and elements that support floors. [F20-OP2.1] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
9.20.17.5. Framing Supported on Flat Insulating Concrete Form WallsN/A
(1)[F20, F22-OH4] [F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1]
(2)[F20, F22-OH4] [F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1]
(3)[F20, F22-OH4] [F20-OP2.1] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS3.1]
9.20.17.6. Anchoring of Roof Framing to Top of Flat Insulating Concrete Form WallsN/A
(1)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OH1.1, OH1.2, OH1.3]
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4]
9.21.1.2. Chimney or Flue Pipe WallsN/A
(1)[F01-OP1.1] Applies to the walls of any chimney or flue pipe, which are required to be constructed to be flametight. [F01-OS1.1] Applies to the walls of any chimney or flue pipe, which are required to be constructed to be flametight. [F44-OH1.1] Applies to the walls of any chimney or flue pipe, which are required to be constructed to be smoketight.
9.21.1.3. Factory Built ChimneysN/A
(1)[F01-OP1.1] Applies to the walls of any chimney or flue pipe, which are required to be constructed to be flametight. [F01-OS1.1] Applies to the walls of any chimney or flue pipe, which are required to be constructed to be flametight. [F44-OH1.1] Applies to the walls of any chimney or flue pipe, which are required to be constructed to be smoketight.
9.21.1.4. Flue PipesN/A
(1)[F01-OP1.1] Applies to the walls of any chimney or flue pipe, which are required to be constructed to be flametight. [F01-OS1.1] Applies to the walls of any chimney or flue pipe, which are required to be constructed to be flametight. [F44-OH1.1] Applies to the walls of any chimney or flue pipe, which are required to be constructed to be smoketight.
9.21.2.1. Chimney Flue LimitationsN/A
(1)[F44-OH1.1] [F44-OS3.4]
(2)[F44-OH1.1] [F44-OS3.4]
(3)[F44-OH1.1] [F44-OS3.4]
9.21.2.2. Connections of More Than One ApplianceN/A
(1)[F44-OH1.1] [F44-OS3.4]
(2)[F44-OS3.4]
(3)[F44-OH1.1] [F44-OS3.4]
9.21.2.3. Inclined Chimney FluesN/A
(1)[F44-OH1.1] [F44-OS3.4]
9.21.2.4. Size of Chimney FluesN/A
(2)[F44-OH1.1] [F44-OS3.4]
9.21.2.5. Fireplace ChimneysN/A
(1)[F44-OH1.1] [F44-OS3.4]
9.21.2.6. Oval Chimney FluesN/A
(1)[F44-OH1.1] [F44-OS3.4]
9.21.3.1. Lining MaterialsN/A
(1)[F20-OH1.1] [F01-OS1.1] [F20-OS2.3] [F44-OS3.4] [F01, F20, F44-OP1.1]
9.21.3.2. Joints in Chimney LinersN/A
(1)[F01-OP1.1] [F44-OH1.1] [F01-OS1.1] [F20, F44-OS2.3] [F01-OS3.4]
(2)[F01-OP1.1] [F44-OH1.1] [F01-OS1.1] [F01-OS3.4]
9.21.3.3. Clay LinersN/A
(1)[F01-OS1.1] [F20-OS2.2] [F20, F44-OS3.4] [F01, F20-OP1.1] [F20, F44-OH1.1]
(2)[F01, F20-OP1.1] [F44-OH1.1] [F01, F20-OS1.1] [F20-OS2.3] Applies to the liners referred to in Sentence (1), which are required to be not less than 15.9 mm thick. [F44-OS3.4]
9.21.3.4. Firebrick LinersN/A
(1)[F01-OP1.1] [F01-OS1.1] [F20, F44-OS3.4] [F44-OH1.1]
(2)[F01, F20-OP1.1] [F20-OH1.1] [F01, F20-OS1.1] [F20-OS2.2] [F20, F44-OS3.4]
9.21.3.5. Concrete LinersN/A
(1)[F01-OP1.1] [F01, F20-OS1.1] [F20-OS2.3] [F20, F44-OS3.4] [F44-OH1.1]
9.21.3.6. Metal LinersN/A
(1)[F01, F20-OP1.1] [F20, F44-OH1.1] [F01, F20-OS1.1] [F20-OS2.3] [F20, F44-OS3.4]
(2)[F20-OP1.1] [F01, F20-OS1.1] [F20-OS2.3] [F20, F44-OS3.4] [F44-OH1.1]
9.21.3.7. Installation of Chimney LinersN/A
(1)[F01-OP1.1] [F01-OS1.1] [F20-OS2.3] [F44-OS3.4] [F44-OH1.1]
9.21.3.8. Spaces Between Liners and Surrounding MasonryN/A
(1)[F01-OP1.1] [F01-OS1.1] [F20-OS2.3]
(2)[F01-OP1.1] [F44-OH1.1] [F20-OS1.1] [F20-OS2.3] [F44-OS3.4]
9.21.3.9. Mortar for Chimney LinersN/A
(1)[F20, F44-OH1.1] [F20, F44-OS3.4] (a), (b) [F01, F20-OP1.1] (a), (b) [F01, F20-OS1.1] (b) [F20-OS2.3]
(2)[F01, F20-OP1.1] [F20, F44-OH1.1] [F01, F20-OS1.1] [F20-OS2.3] [F44-OS3.4]
9.21.3.10. Extension of Chimney LinersN/A
(1)[F01-OP1.1] [F01-OS1.1] [F20-OS2.3] [F44-OS3.4] [F20, F44-OH1.1]
9.21.4.4. Height of Chimney FluesN/A
(1)(a), (b) [F44-OH1.1] (a), (b) [F44-OS3.4]
9.21.4.6. Chimney CapsN/A
(1)[F01-OP1.1] [F20, F44-OH1.1] [F01-OS1.1] [F20-OS2.3] [F44-OS3.4]
(2)[F20-OS2.3]
(3)[F01, F20-OP1.1] [F01, F20-OS1.1] [F20-OS2.3] [F20, F44-OS3.4]
(4)[F01, F20-OP1.1] [F20, F44-OH1.1] [F01, F20-OS1.1] [F20-OS2.3] [F20, F44-OS3.4]
9.21.4.7. CleanoutN/A
(1)[F01-OP1.1] [F01-OS1.1]
9.21.4.8. Wall ThicknessN/A
(1)[F01-OP1.1] [F22-OP2.1] [F01-OS1.1] [F20, F22-OS2.1]
9.21.4.9. Separation of Flue LinersN/A
(1)[F01-OS1.1] [F20, F22-OS2.3] [F44-OS3.4] [F01, F20-OP1.1] [F20, F44-OH1.1]
(2)[F01-OS1.1] [F20, F22-OS2.3] [F20, F44-OS3.4] [F20, F44-OH1.1]
9.21.4.10. FlashingN/A
(1)[F20, F61-OS2.3]
9.21.5.1. Clearance from Combustible MaterialsN/A
(1)(a), (b) [F01-OP1.1] (a), (b) [F01-OS1.1]
(2)[F01-OP1.1] [F01-OS1.1]
(3)[F01-OP1.1] [F01-OS1.1]
9.21.5.2. Sealing of SpacesN/A
(1)[F01-OP1.1] [F01-OS1.1]
9.21.5.3. Support of Joists or BeamsN/A
(1)[F01-OP1.1] [F01-OS1.1]
9.22.1.2. Masonry and ConcreteN/A
(2)[F22, F20-OS2.3]
9.22.1.4. Combustion AirN/A
(0.1)[F50, F81-OH1.1] [F44, F81-OS3.4]
(0.2)[F01, F80-OP1.1] [F03-OP1.2] [F01, F80-OS1.1] [F03-OS1.2]
(0.3)[F50, F81-OH1.1] [F44, F81-OS3.4]
(0.4)[F54-OH1.2]
(0.5)[F50, F81-OH1.1] [F44, F81-OS3.4]
(0.6)(a) [F50, F81-OH1.1] (a) [F44, F81-OS3.4] (b) [F03-OP1.2] (b) [F03-OS1.2]
(1)[F01-OP1.1] [F01-OS1.1]
9.22.2.1. Brick or Steel LinersN/A
(1)[F01, F20-OP1.1] [F01, F20-OS1.1]
9.22.2.2. Firebrick LinersN/A
(1)(a), (b) [F01-OP1.1] (a), (b) [F01-OS1.1]
(2)[F01-OP1.1] [F01-OS1.1]
(3)[F01-OP1.1] [F01-OS1.1]
9.22.2.3. Steel LinersN/A
(1)[F01-OP1.1] [F01-OS1.1] [F44-OS3.4] [F44-OH1.1]
9.22.3.1. Thickness of WallsN/A
(1)[F01-OP1.1] [F01-OS1.1]
(2)(a), (b) [F01-OP1.1] (a), (b) [F01-OS1.1]
9.22.4.1. Fire Chamber DimensionsN/A
(1)[F22-OH1.1] [F44-OS3.4]
9.22.5.1. Hearth ExtensionN/A
(1)[F01-OP1.1] [F01-OS1.1]
(2)(a), (b) [F01-OP1.1] (a), (b) [F01-OS1.1]
9.22.5.2. Support of HearthN/A
(1)[F01-OS1.1] [F20-OS2.3] [F01, F20-OP1.1]
(2)[F01-OP1.1] [F01-OS1.1]
9.22.6.1. Required Damper and SizeN/A
(1)[F01-OP1.1] [F01-OS1.1] [F54-OH1.2]
9.22.7.1. Slope of Smoke ChamberN/A
(1)[F44-OH1.1] [F44-OS3.4]
9.22.7.2. Wall ThicknessN/A
(1)[F01-OP1.1] [F01-OS1.1]
9.22.8.1. Conformance to StandardN/A
(1)[F01-OP1.1] [F01-OS1.1] [F44-OS3.4] [F44-OH1.1]
9.22.9.1. Clearance to the Fireplace OpeningN/A
(1)[F01-OP1.1] [F01-OS1.1]
9.22.9.2. Metal Exposed to the InteriorN/A
(1)[F01-OP1.1] [F01-OS1.1]
9.22.9.3. Clearance to Combustible FramingN/A
(1)[F01-OP1.1] [F01-OS1.1]
(2)[F01-OP1.1] [F01-OS1.1]
9.22.9.4. Heat Circulating Duct OutletsN/A
(1)(a), (b) [F01-OS1.1] (a), (b) [F01-OP1.1]
9.22.10.1. Appliance StandardN/A
(1)[F01-OP1.1] [F01-OS1.1] [F44-OS3.4] [F44-OH1.1]
9.22.10.2. InstallationN/A
(1)[F01-OP1.1] [F01-OS1.1] [F44-OS3.4] [F44-OH1.1]
(3)[F01-OP1.1] [F01-OS1.1] [F44-OS3.4] [F44-OH1.1]
9.23.2.1. Strength and RigidityN/A
(1)[F20-OP2.1] [F20, F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.2.2. Protection from DecayN/A
(1)[F80-OP2.3, OP2.4] [F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F80-OH4] Applies to floors and elements that support floors. [F80-OS1.2] Applies to assemblies required to provide fire resistance. [F80-OS2.3] [F80-OS3.1] Applies to floors and elements that support floors. [F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F81-OP2.3] [F81-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F81-OH4] Applies to floors and elements that support floors. [F81-OS1.2] Applies to assemblies required to provide fire resistance. [F81-OS2.3] [F81-OS3.1] Applies to floors and elements that support floors.
9.23.2.3. Protection from DampnessN/A
(1)[F80-OP2.1, OP2.3, OP2.4] [F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F80-OH4] Applies to floors and elements that support floors. [F80-OS1.2] Applies to assemblies required to provide fire resistance. [F80-OS2.1, OS2.3] [F80-OS3.1] Applies to floors and elements that support floors.
9.23.2.4. Connection to Preservative Treated WoodN/A
(1)[F20, F80-OS2.3] [F20, F80-OS2.3]
(2)[F20, F80-OS2.3] [F20, F80-OS2.3]
(3)[F20, F80-OS2.3] [F20, F80-OS2.3]
9.23.3.1. Standards for Nails and ScrewsN/A
(1)[F20-OP2.1] [F20, F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors.
(2)[F20-OP2.1] [F20, F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.3.2. Length of NailsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors.
9.23.3.3. Prevention of SplittingN/A
(1)[F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F80-OH4] Applies to floors and elements that support floors. [F80-OP2.1, OP2.4] [F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F80-OS1.2] Applies to assemblies required to provide fire resistance. [F80-OS2.1] [F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F80-OS3.1] Applies to floors and elements that support floors.
9.23.3.4. Nailing of FramingN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors.
9.23.3.5. Fastening for Sheathing or SubflooringN/A
(1)[F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
(2)[F22-OH4] Applies to floors and elements that support floors. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1] [F20, F22-OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
(3)[F22-OH4] Applies to floors and elements that support floors. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1] [F20, F22-OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
(5)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors.
(6)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors.
(7)[F20, F22-OS2.1] [F20-OP2.1] [F22-OP2.4] [F22-OH4] Applies to floors and elements that support floors. [F22-OS3.1] Applies to floors and elements that support floors. [F20-OS1.2] Applies to assemblies required to provide fire resistance.
(7.1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors.
(8)[F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
9.23.4.2. Spans for Joints, Rafters and BeamsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.3, OP2.5] [F20-OS2.1, OS2.3, OS2.5]
(4)[F20-OP2.1, OP2.3, OP2.5] [F20-OS2.1, OS2.3, OS2.5]
9.23.4.3. Steel BeamsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.4.4. Concrete ToppingN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.4.5. Heavy Roofing MaterialsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.5.1. Holes Drilled in Framing MembersN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.5.2. Notching of Framing MembersN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.5.3. Wall StudsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.5.4. Top PlatesN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.5.5. Roof TrussesN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator.
9.23.6.1. Anchorage of Building FramesN/A
(1)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(2)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(3)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(4)[F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OS3.1] Applies to floors and elements that support floors.
(5)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS3.1] Applies to floors and elements that support floors.
(6)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20-OS3.1] Applies to floors and elements that support floors.
9.23.6.2. Anchorage of Columns and PostsN/A
(1)[F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F22-OP2.4, OP2.5] [F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F22-OS2.4, OS2.5] [F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and the elements that support walls, that contain doors or windows required for emergency egress.
(2)[F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F22-OP2.4, OP2.5] [F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F22-OS2.4, OS2.5] [F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and the elements that support walls, that contain doors or windows required for emergency egress.
9.23.6.3. Anchorage of Smaller BuildingsN/A
(1)[F22-OS2.3, OS2.5]
9.23.7.1. Size of Sill PlatesN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.7.2. Levelling of Sill PlatesN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.5] [F22-OS2.4, OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. F20, F22-OS3.1] Applies to floors and elements that support floors.
9.23.8.1. Bearing for BeamsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.8.2. Priming of Steel BeamsN/A
(1)[F80-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F80-OH4] Applies to floors and elements that support floors. [F80-OP2.1, OP2.4] [F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F80-OS1.2] Applies to assemblies required to provide fire resistance. [F80-OS2.1] [F80-OS2.3] Applies to floors and elements that support floors. [F80-OS3.1] Applies to floors and elements that support floors.
9.23.8.3. Built-up Wood BeamsN/A
(1)[F20-OP2.1] [F20-OS2.1]
(2)[F20-OP2.1] [F20-OS2.1]
(3)[F20-OP2.1] [F20-OS2.1]
(4)[F20-OP2.1] [F20-OS2.1]
(5)[F20-OP2.1] [F20-OS2.1]
(6)[F20-OP2.1] [F20-OS2.1]
(7)[F20-OP2.1] [F20-OS2.1]
(8)[F20-OP2.1] [F20-OS2.1]
9.23.9.1. End Bearing for JoistsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1]
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1]
9.23.9.2. Joists Supported by BeamsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(4)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(5)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.9.3. Restraint of Joist BottomsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.9.4. Strapping, Bridging, Furring and Ceilings in Span Tables 9.23.4.2.-A and 9.23.4.2.-BN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(4)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(5)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(6)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.9.5. Header JoistsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.9.6. Trimmer JoistsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.9.7. Support of Tail and Header JoistsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.9.8. Support of WallsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(4)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(5)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(6)[F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
9.23.9.9. Cantilevered Floor JoistsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.10.1. Stud Size and SpacingN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.10.2. Bracing and Lateral SupportN/A
(0.1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress.
(0.2)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress.
(0.3)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress.
(0.4)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress.
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to walls that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to walls that support or are part of an environmental separator. [F22-OH4] Applies to walls that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to walls that support or are part of an environmental separator. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress.
9.23.10.3. Orientation of StudsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.10.4. Continuity of StudsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.10.5. Support for Cladding MaterialsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.10.6. Studs at Sides of OpeningsN/A
(1)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance.
(2)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance.
(3)(b)[F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F22-OS3.1] Applies to floors and elements that support floors. [F20, F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20-OP2.1] [F20-OP2.5] [F20-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F20, F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator.
9.23.10.7. Stud Posts Built into WallsN/A
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and roofs and elements that support floors and roofs. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and roofs and elements that support floors and roofs. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.11.1. Size of Wall PlatesN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.11.2. Bottom Wall PlatesN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.11.3. Top PlatesN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(4)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.11.4. Joints in Top PlatesN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(4)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(5)[F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.12.1. Openings in Non-Loadbearing WallsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20, F22-OS1.2]
9.23.12.2. Openings in Loadbearing WallsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)
9.23.12.3. Lintel Spans and SizesN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.5] [F22-OP2.4, OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.13.1. Requirements for Low to Moderate Wind and Seismic ForcesN/A
(2)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors.
9.23.13.4. Braced Wall BandsN/A
(1)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
(2)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors.
(3)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
9.23.13.5. Braced Wall Panels in Braced Wall BandsN/A
(1)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
(2)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
9.23.13.6. Materials in Braced Wall PanelsN/A
(1)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
(2)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F20, F22-OH4] Applies to walls that support floors.
(4)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
(5)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3]
(6)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
9.23.13.7. Additional System ConsiderationsN/A
(7)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
9.23.14.1. Continuity of Rafters and JoistsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance.
9.23.14.2. Framing around OpeningsN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance.
9.23.14.3. End Bearing LengthN/A
(1)[F20-OP2.1, OP2.5] [F22-OP2.5] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.5] [F22-OS2.5] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance.
9.23.14.4. Location and Attachment of RaftersN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
(2)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
(3)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
9.23.14.5. Shaping of RaftersN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
9.23.14.6. Hip and Valley RaftersN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F20, F22-OH1.1, OH1.2, OH1.3]
9.23.14.7. Intermediate Support for Rafters and JoistsN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
(2)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
(4)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
(5)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
(6)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F22-OH4] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
9.23.14.8. Ridge SupportN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(4)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(5)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(6)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(7)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(8)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(9)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.14.9. Restraint of Joist BottomsN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
9.23.14.10. Ceiling Joists Supporting Roof LoadN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
(2)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
9.23.14.11. Roof TrussesN/A
(1)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance.
(3)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.5]
9.23.15.1. Subflooring RequiredN/A
(1)[F20-OS2.1]
9.23.15.2. Material StandardsN/A
(1)[F22-OH4] [F22-OP2.4] [F20-OS2.1] [F22-OS3.1]
(2)[F80-OH4] [F80-OP2.4] [F80-OS2.1] [F80-OS3.1]
(3)[F22-OH4] [F22-OP2.4] [F20-OS2.1] [F22-OS3.1]
(4)[F80-OH4] [F80-OP2.4] [F80-OS2.1] [F80-OS3.1]
9.23.15.3. Edge SupportN/A
(1)[F22-OH4] [F22-OP2.4] [F22-OS3.1]
9.23.15.4. Direction of InstallationN/A
(1)[F22-OH4] [F22-OP2.4] [F22-OS3.1]
(2)[F22-OH4] [F22-OP2.4] [F22-OS3.1]
9.23.15.5. Subfloor Thickness or RatingN/A
(1)[F22-OH4] [F22-OP2.4] [F20-OS2.1] [F22-OS3.1]
(2)[F22-OH4] [F22-OP2.4] [F20-OS2.1] [F22-OS3.1]
(3)[F22-OH4] [F22-OP2.4] [F20-OS2.1] [F22-OS3.1]
9.23.15.6. Annular Grooved NailsN/A
(1)[F81-OH1.1] [F81-OP2.3] [F81-OS2.3]
9.23.15.7. Lumber SubflooringN/A
(1)[F22-OH4] [F22-OP2.4] [F22-OS3.1]
(2)[F22-OH4] [F22-OP2.4] [F22-OS3.1]
(3)[F22-OP2.4] [F22-OS3.1]
9.23.16.1. Required Roof SheathingN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20, F22-OH1.1, OH1.2, OH1.3]
9.23.16.2. Material StandardsN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5]
9.23.16.3. Direction of InstallationN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5]
(2)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5]
9.23.16.4. Joints in Panel-Type SheathingN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5]
(2)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5]
9.23.16.5. Lumber Roof SheathingN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5]
9.23.16.6. Edge SupportN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5]
(2)N/A
9.23.16.7. Thickness or RatingN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F22-OH4] [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.1]
(2)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance.
(3)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F20, F22-OH1.1, OH1.2, OH1.3]
(4)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F20, F22-OH1.1, OH1.2, OH1.3]
9.23.17.1. Required SheathingN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.1] Applies to floors and elements that support floors. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.17.2. Thickness, Rating and Material StandardsN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F20, F22-OS3.1] Applies to floors and elements that support floors.
9.23.17.3. Attachment of Cladding to SheathingN/A
(2)[F20, F22, F80-OH1.1, OH1.2, OH1.3] [F20, F22, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F22, F80-OS2.1] Applies to elements that support or are part of an environmental separator. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.17.4. Lumber SheathingN/A
(1)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5]
(2)[F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OH4] Applies to floors and elements that support floors. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.5] [F22-OS3.1] Applies to floors and elements that support walls. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.23.17.5. Joints in Panel-Type SheathingN/A
(1)[F80, F81-OH1.1, OH1.2, OH1.3] [F80, F81-OH4] Applies to floors and elements that support floors. [F80, F81-OP2.3, OP2.4] [F80, F81-OS2.3] [F80, F81-OS3.1] Applies to floors and elements that support floors.
9.24.1.2. Material StandardsN/A
(1)[F20, F22, F80-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22, F80-OP2.4] [F20, F22, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.4] [F22, F80-OS2.4] [F20, F22, F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.1.4. ScrewsN/A
(1)[F20, F22, F80-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22, F80-OP2.4] [F20, F22, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.4] [F22, F80-OS2.4] [F20, F22, F80-OS2.3] Applies to elements that support or are part of an environmental separator. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.1.5. Cladding, Sheathing and Interior Finish RequiredN/A
(1)[F20, F22, F80-OH1.1, OH1.2, OH1.3] [F20, F22, F80-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22, F80-OS1.2] Applies to assemblies required to provide fire resistance. [F20, F22, F80-OS2.1] Applies to elements that support or are part of an environmental separator. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.2.1. Size and Spacing of Studs in Interior WallsN/A
(1)[F20-OP2.1, OP2.4] [F22-OP2.4] [F20-OS2.1, OS2.4] [F22-OS2.4] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.2.2. Thickness of StudsN/A
(1)[F20-OP2.1, OP2.4] [F22-OP2.4] [F20-OS2.1, OS2.4] [F22-OS2.4] [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.2.3. RunnersN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.4] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance.
9.24.2.4. Openings in Fire SeparationsN/A
(1)[F20-OS1.2]
(2)[F20-OS1.2]
(3)[F20-OS1.2]
(4)[F20-OS1.2]
9.24.2.5. Size and Spacing of Studs in Exterior WallsN/A
(1)[F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4] [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4] [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.3.1. Installation of RunnersN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.4] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.4] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(3)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.4] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(4)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.4] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.3.2. Fire-Rated WallsN/A
(1)[F21-OS1.2]
(2)[F21-OS1.2]
(3)[F20-OS1.2]
(4)[F20-OS1.2]
9.24.3.3. Orientation of StudsN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.4] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.3.4. Support for Cladding MaterialsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.4] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.3.5. Framing around OpeningsN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F20-OS2.1, OS2.4] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.4] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
9.24.3.6. Attachment of Studs to RunnersN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.4] [F22-OP2.4] [F20, F22-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1, OS2.4] [F22-OS2.4] [F20, F22-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22, F80-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
(2)[F21-OS1.2]
9.24.3.7. Openings for Fire DampersN/A
(1)[F20-OS1.2]
(2)[F20-OS1.2]
(3)[F03-OS1.2]
9.25.1.1. Scope and ApplicationN/A
(2)[F51, F63-OH1.1, OH1.2] [F55, F63-OS2.3]
9.25.2.1. Required InsulationN/A
(1)[F51, F63-OH1.1, OH1.2] [F63-OS2.3]
9.25.2.2. Insulation MaterialsN/A
(1)[F51, F63, F80-OH1.1, OH1.2] [F63, F80-OS2.3]
(3)[F51, F63-OH1.1, OH1.2] [F63-OS2.3]
(4)[F51, F63, F80-OH1.1, OH1.2] [F63, F80-OS2.3]
9.25.2.3. Installation of Thermal InsulationN/A
(1)[F51, F63-OH1.1, OH1.2] [F63-OS2.3]
(2)[F51, F63-OH1.1, OH1.2] [F63-OS2.3]
(3)[F55-OH1.1, OH1.2] [F55-OS2.3]
(4)[F51, F63, F80-OH1.1, OH1.2] [F63, F80-OS2.3]
(5)[F21-OH1.1, OH1.2, OH1.3] [F21-OS2.2, OS2.3]
(6)[F80-OH1.1, OH1.2] [F80-OS2.3]
(7)[F80-OH1.1, OH1.2] [F80-OS2.3]
(8)[F21-OH1.1, OH1.2] [F21-OS2.3]
9.25.2.4. Installation of Loose-Fill InsulationN/A
(1)[F51, F63-OH1.1, OH1.2] [F63-OS2.3]
(2)[F51-OH1.1, OH1.2, OH1.3] [F51-OS2.3]
(4)(a) [F21, F51-OH1.1, OH1.2] (a) [F21, F51-OS2.3] (c) [F81-OH1.1, OH1.2] (c) [F81-OH1.1, OH1.2, OH1.3] Applies where the interior finish provide the required bracing. (c) [F81-OH4] Applies where the interior finish provides the required bracing of walls that support floors. (c) [F81-OP2.1, OP2.3, OP2.4, OP2.5] Applies where the interior finish provides the required bracing. (c) [F81-OP3.1] Applies where the interior finish contributes to the required fire resistance of the wall. (c) [F81-OS2.1, OS2.3] (c) [F81-OS2.1, OS2.3, OS2.4, OS2.5] Applies where the interior finish provides the required bracing. (c) [F81-OS3.7] Applies where the interior finish provides the required bracing. (c) [F81-OS3.1] Applies where the interior finish provides the required bracing of walls that support floors. (d) [F80-OH1.1, OH1.2, OH1.3] (d) [F80-OS2.3]
(5)[F51, F63-OH1.1, OH1.2] [F63-OS2.3]
(6)(a) [F51, F62-OH1.1, OH1.2, OH1.3] (a) [F62, F51-OS2.3] (b) [F51, F63-OH1.1, OH1.2] (b) [F51, F63-OS2.3]
9.25.2.5. Installation of Spray-Applied PolyurethaneN/A
(1)[F41, F51, F63-OH1.1] [F51, F63-OH1.2] [F63-OS2.3]
9.25.3.1. Required Barrier to Air LeakageN/A
(1)[F55-OH1.1, OH1.2, OH1.3] [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(2)[F55-OH1.1, OH1.2, OH1.3] [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
9.25.3.2. Air Barrier System PropertiesN/A
(1)[F20, F55-OH1.1, OH1.2, OH1.3] [F20, F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F20, F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(2)[F20, F55-OH1.1, OH1.2, OH1.3] [F20, F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F20, F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
9.25.3.3. Continuity of the Air Barrier SystemN/A
(1)[F55-OH1.1, OH1.2, OH1.3] [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(2)[F55-OH1.1, OH1.2, OH1.3] [F40-OH1.1] [F55-OS2.3] (a) [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. (a) [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(2.1)[F55-OH1.1, OH1.2, OH1.3] [F40-OH1.1] [F55-OS2.3] (a) [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. (a) [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(5)[F55-OH1.1, OH1.2, OH1.3] [F40-OH1.1] [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(5.1)[F55-OH1.1, OH1.2, OH1.3] [F40-OH1.1] [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(6)[F55-OH1.1, OH1.2, OH1.3] [F40-OH1.1] [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(6.1)[F55-OH1.1, OH1.2, OH1.3] [F40-OH1.1] [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(6.2)[F55-OH1.1, OH1.2, OH1.3] [F40-OH1.1] [F44-OS1.1] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space. [F55-OS2.3] [F44-OS3.4] Applies where the air barrier system separates a garage, or suite containing a garage, from residential space.
(7)[F55-OH1.1, OH1.2, OH1.3] [F55-OS2.3]
(8)[F01-OS1.1]
(9)[F55-OH1.1, OH1.2, OH1.3]
(10)[F55-OH1.1, OH1.2, OH1.3] [F40-OH1.1] [F55-OS2.3]
9.25.4.1. Required Barrier to Vapour DiffusionN/A
(1)[F63-OH1.1, OH1.2] [F63-OS2.3]
9.25.4.2. Vapour Barrier MaterialsN/A
(1)[F63-OH1.1, OH1.2] [F63-OS2.3]
(2)[F63-OH1.1, OH1.2, OH1.3] [F63-OS2.3]
(3)[F62, F63-OH1.1, OH1.2, OH1.3] [F62, F63-OS2.3]
(4)[F63, F80-OH1.1, OH1.2] [F63, F80-OS2.3]
(5)[F63, F80-OH1.1, OH1.2] [F63, F80-OS2.3]
(6)[F63, F80-OH1.1, OH1.2] [F63, F80-OS2.3]
(7)[F63-OH1.1, OH1.2] [F63-OS2.3]
(8)[F63-OH1.1, OH1.2] [F63-OS2.3]
9.25.4.3. Installation of Vapour BarriersN/A
(1)[F63-OH1.1, OH1.2] [F63-OS2.3]
(2)[F63-OH1.1, OH1.2] [F63-OS2.3]
(3)[F63-OS2.3] [F63-OH1.1, OH1.2]
9.25.5.1. GeneralN/A
(2)[F62, F63-OS2.3] [F62, F63-OH1.1, OH1.2]
9.25.5.2. Position of Low Permeance MaterialsN/A
(1)[F62, F63-OS2.3] [F62, F63-OH1.1, OH1.2]
9.26.1.2. Required ProtectionN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.1.3. Alternate Installation MethodsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.2.1. Material StandardsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.2.2. Installation of MaterialsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.2.3. NailsN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OS2.3]
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(4)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OS2.3]
9.26.2.4. StaplesN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OS2.3]
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(3)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OS2.3]
9.26.3.1. SlopeN/A
(1)[F20, F61, F80-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3] [F61, F80-OS2.3]
(2)[F20, F61, F80-OH1.1, OH1.2, OH1.3] [F20, F61, F80-OS2.3]
(3)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
(4)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
(5)[F21-OH1.1, OH1.2, OH1.3] [F21-OS2.3]
9.26.4.1. Required Flashing at IntersectionsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.4.2. MaterialsN/A
(1)[F61, F62, F80-OH1.1, OH1.2, OH1.3] [F61, F62, F80-OS2.3]
9.26.4.3. Valley FlashingN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3.1)[F20, F61, F80-OH1.1, OH1.2, OH1.3] [F20, F61, F80-OS2.3]
(4)[F20, F61, F80-OH1.1, OH1.2, OH1.3] [F20, F61, F80-OS2.3]
(5)[F20, F61, F80-OH1.1, OH1.2, OH1.3] [F20, F61, F80-OS2.3]
(6)[F20, F61, F80-OH1.1, OH1.2, OH1.3] [F20, F61, F80-OS2.3]
9.26.4.4. Intersection of Shingle Roofs and MasonryN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OP1.1] Applies where a shingle roof intersects with a masonry chimney. [F61-OS1.1] Applies where a shingle roof intersects with a masonry chimney. [F61-OS2.3] [F61-OS3.4] Applies where a shingle roof intersects with a masonry chimney.
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OP1.1] Applies where counter flashing is installed between a shingle roof and a masonry chimney. [F61-OS1.1] Applies where counter flashing is installed between a shingle roof and a masonry chimney. [F61-OS2.3] [F61-OS3.4] Applies where counter flashing is installed between a shingle roof and a masonry chimney.
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OP1.1] Applies where flashing is installed between a shingle roof and a masonry chimney. [F61-OS1.1] Applies where flashing is installed between a shingle roof and a masonry chimney. [F61-OS2.3] [F61-OS3.4] Applies where flashing is installed between a shingle roof and a masonry chimney.
(4)[F61-OH1.1, OH1.2, OH1.3] [F61-OP1.1] Applies where a shingle roof slopes upward from a masonry chimney. [F61-OS1.1] Applies where a shingle roof slopes upward from a masonry chimney. [F61-OS2.3] [F61-OS3.4] Applies where a shingle roof slopes upward from a masonry chimney.
9.26.4.5. Intersection of Shingle Roofs and Walls Other Than MasonryN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.4.6. Intersection of Built-Up Roofs and MasonryN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OP1.1] Applies where a built-up roof intersects with a masonry chimney. [F61-OS1.1] Applies where a built-up roof intersects with a masonry chimney. [F61-OS2.3] [F61-OS3.4] Applies where a built-up roof intersects with a masonry chimney.
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OP1.1] Applies where counter flashing is installed between a built-up roof and a masonry chimney. [F61-OS1.1] Applies where counter flashing is installed between a built-up roof and a masonry chimney. [F61-OS2.3] [F61-OS3.4] Applies where counter flashing is installed between a built-up roof and a masonry chimney.
9.26.4.7. Intersection of Built-Up Roofs and Walls Other Than MasonryN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.4.8. Chimney SaddlesN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OP1.1] [F61-OS1.1] [F61-OS2.3] [F61-OS3.4]
(2)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] [F20, F80-OS1.1] [F20, F80-OS2.3] [F20, F80-OS3.4]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(5)[F61-OH1.1, OH1.2, OH1.3] [F61-OP1.1] [F61-OS1.1] [F61-OS2.3] [F61-OS3.4]
9.26.5.1. Required Eave ProtectionN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.5.2. MaterialsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.6.1. MaterialsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F62-OH1.1, OH1.2, OH1.3] [F62-OS2.3]
9.26.6.2. InstallationN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.7.1. CoverageN/A
(1)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.1]
9.26.7.2. Starter StripN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.7.3. Head LapN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.7.4. FastenersN/A
(1)[F20, F61-OH1.1, OH1.2, OH1.3] [F20, F61-OS2.3]
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(4)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(5)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
9.26.7.5. Securing of TabsN/A
(1)[F20, F61-OH1.1, OH1.2, OH1.3] [F20, F61-OS2.3]
9.26.7.6. Hips and RidgesN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
9.26.8.1. CoverageN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.8.2. Starter StripN/A
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.8.3. Securing of TabsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.8.4. Securing of Shingle CoursesN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.8.5. Hips and RidgesN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
9.26.9.2. GradeN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.9.3. SizeN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.9.4. Spacing and JointsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.9.5. FasteningN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OS2.3]
9.26.9.6. ExposureN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.10.1. Size and ThicknessN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.10.2. UnderlayN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.10.3. Spacing and JointsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.10.4. FasteningN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OS2.3]
9.26.10.5. ExposureN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.10.8. GradeN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.11.1. Quantity of MaterialsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.11.2. Coal-Tar and Asphalt ProductsN/A
(1)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
9.26.11.3. Roof FeltsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
9.26.11.4. Aggregate SurfacingN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.11.6. Number of LayersN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OS2.3]
9.26.11.7. Installation of LayersN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(2)[F61, F81-OH1.1, OH1.2, OH1.3] [F61, F81-OS2.3]
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
9.26.11.8. Roofing over Wood-Based SheathingN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.11.9. Attachment to DeckingN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.11.10. Cant StripsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3] [F61-OS3.1]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(4)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3] [F61-OS3.1]
(5)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(6)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.12.1. CoverageN/A
(1)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
9.26.12.2. JointsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.13.1. ThicknessN/A
(1)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
9.26.13.2. SupportN/A
(1)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4] [F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OH1.1, OH1.2, OH1.3]
9.26.14.1. SupportN/A
(1)[F20-OS2.1, OS2.3] [F22-OS2.3, OS2.4] [F20, F22-OH1.1, OH1.2, OH1.3]
9.26.15.1. InstallationN/A
(1)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
9.26.16.1. InstallationN/A
(1)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
9.26.17.1. InstallationN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.26.18.2. DownspoutsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.2.1. Minimizing and Preventing Ingress and DamageN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F80, F81-OH1.1, OH1.2, OH1.3] [F80, F81-OS2.3]
9.27.2.2. Minimum Protection from Precipitation IngressN/A
(4)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.2.3. First and Second Planes of ProtectionN/A
(1)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OS2.3]
9.27.2.4. Protection of Cladding from MoistureN/A
(1)[F61, F80-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61, F80-OS2.3]
9.27.3.1. Elements of the Second Plane of ProtectionN/A
(1)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OS2.3]
(3)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OS2.3]
9.27.3.2. Sheathing Membrane Material StandardN/A
(1)[F20, F55, F61, F62-OH1.1, OH1.2, OH1.3] [F20, F55, F61, F62-OS2.3]
9.27.3.3. Required Sheathing Membrane and InstallationN/A
(1)[F55, F61-OH1.1, OH1.2, OH1.3] [F55, F61-OS2.3]
(2)[F55, F61-OH1.1, OH1.2, OH1.3] [F55, F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.3.4. Insulating Sheathing in Lieu of Sheathing MembraneN/A
(2)[F55, F61-OH1.1, OH1.2, OH1.3] [F55, F61-OS2.3]
9.27.3.5. Sheathing Membranes in Lieu of SheathingN/A
(1)[F55, F61-OH1.1, OH1.2, OH1.3] [F55, F61-OS2.3]
(2)[F55, F61-OH1.1, OH1.2, OH1.3] [F55, F61-OS2.3]
9.27.3.6. Face Sealed CladdingN/A
(2)[F20, F55, F61-OH1.1, OH1.2, OH1.3] [F20, F55, F61-OS2.3]
(3)[F55, F61-OH1.1, OH1.2, OH1.3] [F55, F61-OS2.3]
9.27.3.7. Flashing MaterialsN/A
(1)[F61, F62, F80-OH1.1, OH1.2, OH1.3] [F61, F62, F80-OS2.3]
9.27.3.8. Flashing InstallationN/A
(1)(a), (b), (c)(i) [F61-OH1.1, OH1.2, OH1.3] (a), (b), (c)(i) [F61-OS2.3] (c)(ii) [F61, F62-OH1.1, OH1.2, OH1.3] (c)(ii) [F61, F62-OS2.3]
(2)(a), (b)(ii), (c)(i) [F61-OH1.1, OH1.2, OH1.3] Applies to detailing of horizontal joints. (a), (b)(ii), (c)(i) [F61-OS2.3] Applies to detailing of horizontal joints. (b)(i), (c)(ii) [F61, F62-OH1.1, OH1.2, OH1.3] Applies to cladding installed outboard of a drained and vented air space. (b)(i), (c)(ii) [F61, F62-OS2.3] Applies to cladding installed outboard of a drained and vented air space.
(3)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OS2.3]
(4)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OS2.3]
(5)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62-OS2.3]
9.27.4.1. Required SealantsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.4.2. MaterialsN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OS2.3]
(2)[F80-OH1.1, OH1.2, OH1.3] [F80-OS2.3]
(3)[F80-OH1.1, OH1.2, OH1.3] [F80-OS2.3]
9.27.5.1. AttachmentN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20, F22-OH1.1, OH1.2, OH1.3] Applies where panel-type cladding is installed to provide the required bracing. [F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20, F22-OH4] Applies where panel-type cladding is installed to provide the required bracing of walls that support floors. [F20, F22-OS3.1] Applies where panel-type cladding is installed to provide the required bracing of walls that support floors. [F20, F22-OS3.7] Applies where panel-type cladding is installed to provide bracing of walls that contain doors or windows required for emergency egress.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3]
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(4)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3]
9.27.5.2. BlockingN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20, F22-OH1.1, OH1.2, OH1.3] Applies where panel-type cladding is installed to provide the required bracing. [F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
9.27.5.3. FurringN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where furring is used for the attachment if panel-type cladding installed to provide the required bracing.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20, F22-OH1.1, OH1.2, OH1.3] Applies where furring is used for the attachment of panel-type cladding installed to provide the required bracing. [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where furring is used for the attachment of panel-type cladding installed to provide the required bracing.
(3)[F20-OH1.1, OH1.2, OH1.3] [F20, F22-OH1.1, OH1.2, OH1.3] Applies where furring is used for the attachment of panel-type cladding installed to provide the required bracing. [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where furring is used for the attachment of panel-type cladding installed to provide the required bracing.
9.27.5.4. Size and Spacing of FastenersN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20, F22-OH1.1, OH1.2, OH1.3] Applies to the attachment of panel-type cladding installed to provide the required bracing. [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3]
9.27.5.5. Fastener MaterialsN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OP2.1, OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F80-OS2.3] [F80-OS2.3, OS2.4] Applies where panel-type cladding is installed to provide required bracing.
9.27.5.6. Expansion and ContractionN/A
(1)[F21-OH1.1, OH1.2, OH1.3] [F21-OS2.3]
9.27.5.7. Penetration of FastenersN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3]
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3]
(3)[F20-OH1.1, OH1.2, OH1.3] [F20, F22-OH1.1, OH1.2, OH1.3] Applies where panel-type cladding is installed to provide the required bracing. [F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
9.27.6.1. MaterialsN/A
(1)[F20, F61-OH1.1, OH1.2, OH1.3] [F20, F62-OS2.3]
9.27.6.2. Thickness and WidthN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
9.27.6.3. JointsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F21, F61-OH1.1, OH1.2, OH1.3] [F21, F61-OS2.3]
9.27.7.1. MaterialsN/A
(1)[F61-OH1.1, OH1.1, OH1.3] [F61-OS2.3]
(2)[F20, F61-OH1.1, OH1.2, OH1.3] [F20, F61-OS2.3]
(3)[F20, F61-OH1.1, OH1.2, OH1.3] [F20, F61-OS2.3]
9.27.7.2. WidthN/A
(1)[F20, F61-OH1.1, OH1.2, OH1.3] [F20, F61-OS2.3]
9.27.7.3. FastenersN/A
(1)[F20, F61-OH1.1, OH1.2, OH1.3] [F20, F61-OS2.3]
9.27.7.4. Offsetting of JointsN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.7.5. Fastening to LathN/A
(1)[F81-OH1.1, OH1.2, OH1.3] [F81-OS2.3]
(2)[F62-OH1.1, OH1.2, OH1.3] [F62-OS2.3]
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(4)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(5)[F62-OH1.1, OH1.2, OH1.3] [F62-OS2.3]
9.27.7.6. Exposure and ThicknessN/A
(1)[F20, F62-OH1.1, OH1.2, OH1.3] [F20, F62-OS2.3]
9.27.8.1. Material StandardsN/A
(1)[F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide required bracing. [F20, F22-OH1.1, OH1.2, OH1.3]
9.27.8.2. ThicknessN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide required bracing.
(2)[F20-OP2.1, OP2.3] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20, F22-OH1.1, OH1.2, OH1.3]
9.27.8.3. Edge TreatmentN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F61-OS2.3] [F61-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
9.27.8.4. Panel CladdingN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20, F22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(2)[F21-OH1.1, OH1.2, OH1.3] [F21-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(4)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.8.5. Lapped Strip SidingN/A
(1)[F21, F61-OH1.1, OH1.2, OH1.3] [F21, F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.9.1. Material StandardsN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
9.27.9.2. ThicknessN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20, F22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(2)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20, F22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(3)[F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
9.27.9.3. Panel CladdingN/A
(1)[F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20, F21, F22-OH1.1, OH1.2, OH1.3] [F20, F21, F22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F33-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.9.4. Lapped Strip SidingN/A
(1)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(2)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.9.5. ClearanceN/A
(1)[F21-OH1.1, OH1.2, OH1.3] [F21-OP2.1, OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F21-OS2.1, OS2.3] [F21-OS2.1, OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
9.27.10.1. Material StandardN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] Applies where panel-type cladding is installed to provide required bracing.
9.27.10.2. ThicknessN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20, 22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(2)[F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(3)[F20, F22-OH1.1, OH1.2, OH1.3] [F20, 22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(4)[F20-OP2.1, OP2.3, OP2.4] [F22-OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS2.1, OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
9.27.10.3. Panel CladdingN/A
(1)[F20, F22, F80-OH1.1, OH1.2, OH1.3] [F20, F22, F80-OS2.1, OS2.3] [F20, F80-OS2.1, OS2.3, OS2.4] [F22, F80-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(2)[F21-OH1.1, OH1.2, OH1.3] [F21-OS2.3]
(3)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
(4)[F61-OH1.1, OH1.2, OH1.3] [F61-OS2.3]
9.27.10.4. ClearanceN/A
(1)[F21-OH1.1, OH1.2, OH1.3] [F21-OP2.1, OP2.3, OP2.4, OP2.5] Applies where panel-type cladding is installed to provide the required bracing. [F21-OS2.1, OS2.3] [F21-OS2.1, OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
9.27.11.1. Material StandardsN/A
(1)[F20, F22, F61-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3] [F22, F61-OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
(2)[F20, F22, F61-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3] [F22, F61-OS2.3]
(3)[F20, F22, F61-OH1.1, OH1.2, OH1.3] [F20-OS2.1, OS2.3] [F22, F61-OS2.3] [F20-OS2.1, OS2.3, OS2.4] [F22-OS2.3, OS2.4, OS2.5] Applies where panel-type cladding is installed to provide the required bracing.
9.27.12.1. Material StandardN/A
(1)[F62, F61, F20-OH1.1, OH1.2, OH1.3] [F62, F61, F20-OS2.3]
(2)[F62, F61, F20-OH1.1, OH1.2, OH1.3] [F62, F61, F20-OS2.3]
(3)[F62, F61, F20, F42-OH1.1, OH1.2, OH1.3] [F62, F61, F20, F42-OS2.3]
(4)[F02-OS1.2] [F02-OP1.2]
9.27.13.1. Material StandardN/A
(1)[F62, F61, F20-OH1.1, OH1.2, OH1.3] [F62, F61, F20-OS2.3]
(2)[F02-OS1.2] [F02-OS1.2]
9.27.14.2. MaterialsN/A
(1)[F20, F61, F62-OH1.1, OH1.2, OH1.3] [F20, F61, F62-OH2.3]
(2)[F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS2.3]
9.27.14.3. Design and InstallationN/A
(1)[F20, F61, F62-OH1.1, OH1.2, OH1.3] [F20, F61, F62-OS2.3]
9.28.1.1. Sheathing Beneath StuccoN/A
(1)[F20, F22-OH1.1, OH1.2, OH1.3] [F20, F22-OS2.3]
9.28.1.2. Lath and ReinforcingN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(3)[F20, F21-OH1.1] [F20, F21-OP1.1] [F20, F21-OS1.1] [F20, F21-OS2.3] [F20, F21-OS3.4]
9.28.1.3. Concrete Masonry UnitsN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F80-OS2.3] [F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.1.4. Clearance over Ground LevelN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OS2.3]
9.28.1.5. Flashing and CaulkingN/A
(1)[F80-OH1.1, OH1.2, OH1.3] Applies to the separation of aluminum flashing from stucco. [F80-OS2.3] Applies to the separation of aluminum flashing from stucco.
9.28.2.1. Portland CementN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.2.2. AggregateN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F80-OS2.3] [F80-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS2.3] [F20, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.2.3. WaterN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F80-OS2.3] [F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.3.1. MaterialsN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F80-OS2.3] [F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.3.2. Nails and StaplesN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
(4)[F20-OS2.1]
9.28.4.1. MaterialsN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F80-OS2.3] [F80-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F80-OH1.1, OH1.2, OH1.3] [F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F80-OS2.3] [F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.4.2. No Sheathing RequiredN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
9.28.4.3. Stucco Lath SpecificationsN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.4.4. Self-Furring DevicesN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS2.3] [F20, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.4.5. Application of Stucco LathN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OS2.3]
(4)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.4.6. FasteningN/A
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
(3)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
(4)[F20-OS2.1]
9.28.5.1. MixesN/A
(1)[F20, F61, F80-OH1.1, OH1.2, OH1.3] [F20, F61, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F61, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F61, F80-OS2.3] [F20, F61, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.5.2. PigmentsN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS2.3] [F20, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OS2.3]
9.28.5.3. MixingN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS2.3] [F20, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS2.3] [F20, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.6.1. Low Temperature ConditionsN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS2.3] [F20, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS2.3] [F20, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.6.2. Number of Coats and Total ThicknessN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS2.3] [F20, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.6.3. First CoatN/A
(1)[F20, F80-OH1.1, OH1.2, OH1.3] [F20, F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F20, F80-OS2.3] [F20, F80-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.6.4. Second CoatN/A
(1)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
9.28.6.5. Finish CoatN/A
(1)[F80-OH1.1, OH1.2, OH1.3] [F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F80-OS2.3] [F80-OS3.4] Applies where stucco is applied to masonry chimneys.
(2)[F20-OH1.1, OH1.2, OH1.3] [F20-OP1.1] Applies where stucco is applied to masonry chimneys. [F20-OS1.1] Applies where stucco is applied to masonry chimneys. [F20-OS2.3] [F20-OS3.4] Applies where stucco is applied to masonry chimneys.
(3)[F80-OH1.1, OH1.2, OH1.3] [F80-OP1.1] Applies where stucco is applied to masonry chimneys. [F80-OS1.1] Applies where stucco is applied to masonry chimneys. [F80-OS2.3] [F80-OS3.4] Applies where stucco is applied to masonry chimneys.
9.29.2.1. Where RequiredN/A
(1)[F80, F81-OP2.3, OP2.4] [F80, F81-OS2.3] [F80, F81-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F80, F81-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies.
9.29.2.2. MaterialsN/A
(1)[F80-OP2.3, OP2.4] [F80-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F80-OS2.3] [F80, F81-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
9.29.3.1. Size and Spacing of FurringN/A
(1)[F20, F22-OP2.1, OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20, F22-OS2.1]
9.29.3.2. FasteningN/A
(1)[F20-OP2.1, OP2.4] [F20-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.4.1. ApplicationN/A
(1)[F20, F80-OS2.1, OS2.3] [F20, F80-OP2.1, OP2.3] [F22, F80-OP2.4] [F20, F22, F81, F90-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F80-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies.
9.29.5.1. ApplicationN/A
(1)[F20, F80-OP2.1, OP2.3] [F22, F80-OP2.4] [F20, F22, F80-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20, F80-OS2.1, OS2.3] [F20, F22, F80, F81-OH1.1, OH1.2] Applies where interior finishes support or serves as required environmental separation elements.
(3)[F20, F80-OP2.1, OP2.3] [F22, F80-OP2.4] [F20, F22, F80-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20, F80-OS2.1, OS2.3] [F20, F22, F80, F81-OH1.1, OH1.2] Applies where interior finishes support or serves as required environmental separation elements.
9.29.5.2. MaterialsN/A
(1)[F20, F80-OP2.1, OP2.3] [F22, F80-OP2.4] [F20, F22, F80-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20, F80-OS2.1, OS2.3] [F20, F22, F80, F81-OH1.1, OH1.2] Applies where interior finishes support or serves as required environmental separation elements.
9.29.5.3. Maximum Spacing of SupportsN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.5.4. Support of InsulationN/A
(1)[F20-OS2.1] [F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies.
9.29.5.5. Length of FastenersN/A
(1)[F20-OP2.1, OP2.4] [F20-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.5.6. NailsN/A
(1)[F20-OP2.1, OP2.4] [F20-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.5.7. ScrewsN/A
(1)[F20-OP2.1, OP2.4] [F20-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.5.8. Spacing of NailsN/A
(1)[F20-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OP2.1] [F20-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.3] Applies where interior finishes support or serve as required environmental separation elements.
(3)[F20-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP2.1] [F20-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS2.1] [F20-OS2.3] Applies where interior finishes support or serve as required environmental separation elements.
(4)[F20-OP1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP3.1] Applies where interior finishes are installed to contribute to the required fire resistance of exterior walls. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OS2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS3.1, OS3.7] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support studs or where interior support or serve as required environmental separation elements. [F20, F22-OH1.1, OH1.2, OH1.3] Applies where interior finishes contribute to the required bracing or lateral support for studs or where finishes support or serve as required environmental separation elements. [F20, F22-OH4] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support studs or where interior support or serve as required environmental separation elements.
(5)[F20-OP1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP3.1] Applies where interior finishes are installed to contribute to the required fire resistance of exterior walls. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OS2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS3.1, OS3.7] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20, F22-OH1.1, OH1.2, OH1.3] Applies where interior finishes contribute to the required bracing or lateral support for studs or where finishes support or serve as required environmental separation elements. [F20, F22-OH4] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support studs or where interior support or serve as required environmental separation elements.
(6)[F20-OP1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OS2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS3.1, OS3.7] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20, F22-OH1.1, OH1.2, OH1.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OH4] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior support or serve as required environmental separation elements.
(7)[F20-OP1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP3.1] Applies where interior finishes are installed to contribute to the required fire resistance of exterior walls. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OS2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS3.1, OS3.7] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20, F22-OH1.1, OH1.2, OH1.3] Applies where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20-OH4] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements.
9.29.5.9. Spacing of ScrewsN/A
(1)[F20-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OP2.1] [F20-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.3] Applies where interior finishes support or serve as required environmental separation elements.
(3)[F20-OH1.1, OH1.2, OH1.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP1.2] Applies where gypsum board is required to provide the fire resistance and the rating of the assembly is determined according to Table 1 in SB-3. [F20-OP2.1] [F20-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP3.1] Applies where interior finishes are installed to contribute to the required fire resistance of exterior walls. [F20-OS1.2] Applies where gypsum board is required to provide the fire resistance and the rating of the assembly is determined according to Table 1 in SB-3. [F20-OS2.1] [F20-OS2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS2.1] [F20-OS2.3] Applies where interior finishes support or serve as required environmental separation elements.
(4)[F20-OP1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP3.1] Applies where interior finishes are installed to contribute to the required fire resistance of exterior walls. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OS2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS3.1, OS3.7] Applies where the walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20, F22-OH1.1, OH1.2, OH1.3] Applies where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20, F22-OH4] Applies where the walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements.
(6)[F20-OP1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where interior finishes contribute the required bracing or lateral support for studs. [F20, F22-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP3.1] Applies where interior finishes are installed to contribute to the required fire resistance of exterior walls. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where interior finishes contribute the required bracing or lateral support for studs. [F20, F22-OS2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS3.1, OS3.7] Applies where the walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20, F22-OH1.1, OH1.2, OH1.3] Applies where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20-OH4] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements.
(7)[F20-OP1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where interior finishes contribute the required bracing or lateral support for studs. [F20, F22-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OP3.1] Applies where interior finishes are installed to contribute to the required fire resistance of exterior walls. [F20-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS3.1, OS3.7] Applies where the walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20, F22-OH1.1, OH1.2, OH1.3] Applies where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements. [F20-OH4] Applies where walls support floors and where interior finishes contribute to the required bracing or lateral support for studs or where interior finishes support or serve as required environmental separation elements.
9.29.5.10. Low Temperature ConditionsN/A
(1)[F81-OS1.2] Applies where the finishing of joints is required to maintain required fire-resistance ratings.
9.29.6.1. ThicknessN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.6.2. Grooved PlywoodN/A
(1)[F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
9.29.6.3. Nails and StaplesN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
(2)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
9.29.6.4. Edge SupportN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.7.1. Material StandardN/A
(1)[F20, F80-OP2.1, OP2.3] [F20, F22-OP2.4] [F20, F22, F80-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20, F80-OS2.1, OS2.3] [F20, F22, F80-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
9.29.7.2. ThicknessN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20-OS2.1] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies.
9.29.7.3. NailsN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.7.4. Edge SupportN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.8.1. Material StandardN/A
(1)[F20F80-OP2.1, OP2.3] [F20, F22-OP2.4] [F20, F22, F80-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20, F80-OS2.1, OS2.3] [F20, F22, F80, F81-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
9.29.8.2. ThicknessN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
(2)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
9.29.8.3. NailsN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
(2)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
9.29.8.4. Edge SupportN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
9.29.9.1. Material StandardN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
(2)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
9.29.9.2. Minimum ThicknessN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
(4)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements.
(5)[F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OP2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where interior finishes contribute to the required bracing or lateral support for studs. [F20, F22-OS2.3] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OH1.1, OH1.2, OH1.3] Applies where interior finishes support or serve as required environmental separation elements, or where interior finishes contribute to the required bracing of exterior walls.
9.29.9.3. NailsN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
(2)[F20-OS2.1, OS2.3, OS2.5] [F22-OS2.3, OS2.4, OS2.5] [F20-OP2.1, OP2.3, OP2.5] [F22-OP2.3, OP2.4, OP2.5] [F20, F22-OS1.2] Applies to assemblies required to provide fire resistance. [F22-OS3.1] Applies to walls that support floors. [F22-OS3.7] Applies to walls that contain doors or windows required for emergency egress. [F20, F22-OH4] Applies to walls that support floors. [F20, F22-OH1.1, OH1.2, OH1.3] Applies to elements that support or are part of an environmental separator.
9.29.9.4. Edge SupportN/A
(1)[F20-OP2.1] [F20, F22-OP2.4] [F20, F22-OH1.1, OH1.2] Applies where interior finishes support or serve as required environmental separation elements. [F20, F22-OS1.2] Applies where interior finishes are required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1]
9.29.10.1. Tile ApplicationN/A
(1)[F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where the substrate for the tile contribute to the required bracing or lateral support for studs. [F20-OP2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20-OS1.2] Applies where the substrate is required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where the substrate for the tile contributes to the required bracing or lateral support for studs. [F20-OS2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20, F81-OH1.1, OH1.2] Applies where the substrate serves as a required environmental separation element.
(2)[F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where the substrate for the tile contribute to the required bracing or lateral support for studs. [F20-OP2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20-OS1.2] Applies where the substrate is required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where the substrate for the tile contributes to the required bracing or lateral support for studs. [F20-OS2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20, F81-OH1.1, OH1.2] Applies where the substrate serves as a required environmental separation element.
9.29.10.2. Mortar BaseN/A
(1)[F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where the substrate for the tile contribute to the required bracing or lateral support for studs. [F20-OP2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20-OS1.2] Applies where the substrate is required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where the substrate for the tile contributes to the required bracing or lateral support for studs. [F20-OS2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20, F81-OH1.1, OH1.2] Applies where the substrate serves as a required environmental separation element.
(2)[F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where the substrate for the tile contribute to the required bracing or lateral support for studs. [F20-OP2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20-OS1.2] Applies where the substrate is required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where the substrate for the tile contributes to the required bracing or lateral support for studs. [F20-OS2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20, F81-OH1.1, OH1.2] Applies where the substrate serves as a required environmental separation element.
(3)[F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where the substrate for the tile contribute to the required bracing or lateral support for studs. [F20-OP2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20-OS1.2] Applies where the substrate is required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where the substrate for the tile contributes to the required bracing or lateral support for studs. [F20-OS2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20, F81-OH1.1, OH1.2] Applies where the substrate serves as a required environmental separation element.
(4)[F20-OP2.1] [F20-OP2.5] [F22-OP2.4, OP2.5] Applies where the substrate for the tile contribute to the required bracing or lateral support for studs. [F20-OP2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20-OS1.2] Applies where the substrate is required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.1] [F20-OS2.5] [F22-OS2.4, OS2.5] Applies where the substrate for the tile contributes to the required bracing or lateral support for studs. [F20-OS2.3] Applies where the substrate for the tile serves as a required environmental separation element or where the tile is installed to provide the required waterproof wall finish. [F20-OH1.1, OH1.2] Applies where the substrate serves as a required environmental separation element.
9.29.10.3. AdhesivesN/A
(1)[F20-OP2.3, OP2.4] [F20-OH1.1, OH1.2] Applies where the substrate serves as a required environmental separation element. [F20-OS1.2] Applies where the substrate is required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.3]
9.29.10.4. Moisture Resistant BackingN/A
(1)[F81-OP2.3, OP2.4] [F20-OS1.2] Applies where the substrate is required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F20-OS2.3] [F81-OH1.1, OH1.2] Applies where the substrate serves as a required environmental separation element.
9.29.10.5. Joints between Tiles and BathtubN/A
(1)[F81-OP2.3, OP2.4] [F81-OH1.1, OH1.2] Applies where the substrate serves as a required environmental separation element. [F81-OS1.2] Applies where the substrate is required to act as fire protection for foamed plastics or to contribute to the required fire resistance of assemblies. [F81-OS2.3]
9.30.1.1. Required Finish FlooringN/A
(1)[F30-OS3.1] [F40, F41-OH2.4]
9.30.1.2. Water ResistanceN/A
(1)[F41, F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F80-OS2.3] Applies where finished flooring is required to provide water resistance.
9.30.1.3. SleepersN/A
(1)[F20, F80-OS3.1] [F80-OH1.1] Applies to portion of Code text: "Wood sleepers support finished flooring over a concrete base supported on the ground ... shall be treated with a wood preservative."
9.30.2.1. Required UnderlayN/A
(1)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
(2)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
(3)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
(4)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
9.30.2.2. Materials and ThicknessN/A
(1)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
9.30.2.3. FasteningN/A
(1)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
(2)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
(3)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
9.30.2.4. Joints OffsetN/A
(1)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS3.1] [F81-OS2.3] Applies where finished flooring is required to provide water resistance.
9.30.2.5. Surface DefectsN/A
(1)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
9.30.3.1. ThicknessN/A
(1)[F20-OS2.1] [F30-OS3.1]
9.30.3.2. Strip Direction and End JointsN/A
(1)[F30-OS3.1]
(2)[F20-OS2.1]
(3)[F20-OS2.1]
9.30.3.3. NailingN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
9.30.3.4. StaplesN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
9.30.4.1. AdhesiveN/A
(1)[F81-OS3.1]
9.30.5.1. MaterialsN/A
(1)[F41, F80-OH1.1] [F80-OS3.1]
(2)[F41-OH1.1] [F81, F80-OS3.1]
9.30.6.1. SubstrateN/A
(1)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
(2)[F81-OH1.1] Applies where finished flooring is required to provide water resistance. [F81-OS2.3] Applies where finished flooring is required to provide water resistance. [F81-OS3.1]
9.31.2.2. Corrosion ProtectionN/A
(1)[F80-OH2.1] [F80-OS2.3]
9.31.2.3. Grab BarsN/A
(1)[F20-OS3.1]
9.31.3.1. Required Water SupplyN/A
(1)[F70, F71-OH2.2, OH2.3]
9.31.3.2. Required ConnectionsN/A
(1)[F70, F71-OH2.3]
(2)[F70, F71-OH2.3]
9.31.4.1. Required FixturesN/A
(1)[F70, F71, F72-OH2.1, OH2.3]
9.31.4.2. Hot Water SupplyN/A
(1)[F40-OH2.1, OH2.4] [F71-OH2.3] applies to "a hot water supply shall be provided"
9.31.4.3. Floor DrainsN/A
(1)[F40, F41, F62-OH1.2, OH1.3] [F62-OH1.1]
9.31.6.1. Hot Water SupplyN/A
(1)(a) [F40-OH2.1, OH2.4] [F71-OH2.3]
9.31.6.1A. Hot Water TemperatureN/A
(1)[F31-OS2.3] Applies to hot water supply equipment. [F41-OH2.2] Applies to hot water supply equipment.
(2)[F41-OH2.2]
9.31.6.2. Equipment and InstallationN/A
(3)[F23-OS3.4] [F01-OS1.1]
9.31.6.3. Corrosion-Resistant CoatingN/A
(1)[F80, F81-OH2.3]
9.31.6.4. Fuel-Burning HeatersN/A
(1)[F01-OS1.1] [F41-OH1.1]
9.31.6.5. Heating CoilsN/A
(1)[F31-OS2.3] [F71-OH2.3]
9.32.1.2. Required VentilationN/A
(1)[F40, F50, F52-OH1.1] [F51, F52-OH1.2]
(2)[F40, F50, F52-OH1.1] [F51, F52-OH1.2]
9.32.1.3. Venting of Laundry-Drying EquipmentN/A
(1)[F40, F44, F50, F52-OH1.1] [F01-OS1.1] [F01-OP1.1]
(2)[F40, F80-OH1.1] [F81-OS1.1] [F63, F80-OS2.3] [F81-OP1.1]
(3)[F40, F44, F50, F52-OH1.2] [F01-OS1.1] [F01-OP1.1]
9.32.2.1. Required VentilationN/A
(1)[F40, F50, F52-OH1.1] [F51, F52-OH1.2]
9.32.2.2. Non-Heating Season VentilationN/A
(1)[F51, F52-OH1.2] [F40, F52, F50-OH1.1]
(3)[F42-OH2.5] [F61, F42-OH1.1] [F61, F42-OS2.3]
(4)[F80-OH2.5] [F80, F42-OH1.1, OH1.2]
9.32.2.3. Non Heating Season Mechanical VentilationN/A
(1)[F40, F50, F52-OH1.1]
(3)[F40, F50, F52-OH1.1] [F51, F52-OH1.2]
(4)[F40, F50, F52-OH1.1] [F51, F52-OH1.2]
9.32.3.1. Required VentilationN/A
(1)[F40, F50, F53-OS3.4] [F40, F50, F52-OH1.1] [F51, F52-OH1.2]
(2)(a),(b) [F40, F50, F52-OH1.1] (a),(b) [F51, F52-OH1.2] (c) [F53-OH1.1] (c) [F53-OS3.4]
9.32.3.2. Design and InstallationN/A
(1)[F52-OS2.3] [F40, F52, F50-OH1.1] [F52, F51-OH1.2]
(2)[F81-OH1.1]
(3)[F81-OH1.1] [F81-OS3.4]
(4)[F40, F43, F50, F53-OH1.1] [F43, F53, F82-OS3.4]
(5)[F82-OH1.1]
(6)[F63, F81-OH1.1]
9.32.3.3. Principal Ventilation SystemN/A
(1)[F40, F50, F52-OH1.1] [F51, F52-OH1.2]
(2)[F40, F50, F52-OH1.1] [F51, F52-OH1.2]
(4)[F80, F81-OH1.1]
(5)[F81-OH1.1]
(6)[F81-OH1.1]
(7)[F81-OH1.1]
(8)[F81-OH1.1]
(9)[F40, F50, F52-OH1.1]
(10)[F40-OH1.1]
9.32.3.4. Ventilation Systems Used in Conjunction with Forced Air Heating SystemsN/A
(2)[F50, F51, F81-OH1.1] [F51, F81-OH1.2] [F43, F50, F81-OS3.4]
(5)[F40, F43, F50, F52-OH1.1] (a) [F43, F50, F53-OS3.4] (b) [F43, F50, F81-OS3.4]
(7)[F40, F50, F52, F53-OH1.1] [F43, F50, F53-OS3.4]
(8)(a),(b) [F81-OH1.1] (c) [F53-OH1.1] (c) [F53, F63-OS2.3] (a),(b) [F43, F53-OH1.1]
(9)(c) [F53, F63-OH1.1] (a),(b) [F43, F50, F53-OS3.4] (c) [F53, F63-OS2.3]
(10)[F53-OH1.1] [F43, F50, F53-OS3.4] [F53, F63-OS2.3]
(11)[F53-OH1.1]
(12)[F81-OH1.2]
9.32.3.5. Ventilation Systems Not Used in Conjunction with Forced Air Heating SystemsN/A
(2)[F53-OH1.1] [F43, F50, F53-OS3.4]
(3)(a) [F43, F53-OH1.1] (b) [F53, F63-OH1.1] (a) [F43, F50, F53, F81-OS3.4] (b) [F53, F63-OS2.3]
(4)[F40, F43, F50, F52-OH1.1] [F43, F50, F53-OS3.4]
(5)[F53-OH1.1] [F53, F63-OS2.3] [F43, F50, F53-OS3.4]
(6)[F53-OH1.1] [F53, F63-OS2.3] [F43, F50, F53-OS3.4]
(7)[F53-OH1.1]
(8)[F51, F54-OH1.2]
(9)[F54-OH1.2]
(10)[F40, F50, F52-OH1.1]
(12)[F40, F50, F52-OH1.1]
(13)[F51, F54-OH1.2]
(14)[F40, F50, F52-OH1.1]
9.32.3.6. Exhaust Only Ventilation SystemsN/A
(1)[F40, F50, F52-OH1.1] [F43-OS3.4]
(2)[F40, F50, F52-OH1.1]
(3)[F40, F50, F52-OH1.1]
9.32.3.7. Supplemental ExhaustN/A
(1)[F40, F52-OH1.1]
(3)[F40, F52-OH1.1]
(4)[F40, F52-OH1.1]
(5)[F40, F52-OH1.1]
(6)[F81-OH1.1]
(7)[F81-OH1.1]
(8)[F81-OH1.1]
9.32.3.8. Protection Against DepressurizationN/A
(2)[F53-OH1.1] (a) [F43, F50, F53-OS3.4] (b) [F53, F63-OS2.3]
(3)[F53, F81-OH1.1] [F43, F50, F53, F81-OS3.4]
(4)[F81-OS3.4] [F81-OH1.1, OH1.2]
(5)[F53-OH1.1] [F81-OS1.1] [F80, F81-OS3.4]
(7)[F43, F50, F53-OS3.4] [F53-OH1.1]
9.32.3.9A. Location of Carbon Monoxide AlarmsN/A
(1)[F44-OS3.4]
(2)[F44-OS3.4]
(3)[F44-OS3.4]
(4)[F44-OS3.4]
(5)[F44-OS3.4]
(6)[F44-OS3.4]
9.32.3.9B. Location of Carbon Monoxide Alarms in All BuildingsN/A
(1)[F44-OS3.4]
9.32.3.9C. Installation and Conformance StandardsN/A
(1)[F44-OS3.4] (a), (e) [F81-OS3.4]
(3)[F11, F81-OS1.5] [F74-OA2]
(4)[F11, F81-OS1.5] [F74-OA2]
(6)[F44-OS3.4]
9.32.3.10. FansN/A
(1)[F40, F50, F52, F53-OH1.1] [F51, F52-OH1.2] [F53, F63-OS2.3]
(2)[F81-OH1.1, OH1.2]
(3)[F53-OH1.1, OH1.2] [F53-OS3.4]
(4)[F40, F50, F52, F53-OH1.1] [F51, F52-OH1.2]
(5)[F81-OH1.1, OH1.2]
(6)[F81-OS3.4] [F81-OH1.1, OH1.2]
(7)[F40, F50, F52, F53-OH1.1] [F51, F52-OH1.2] [F81-OS3.4]
9.32.3.11. DuctsN/A
(1)[F81-OH1.1]
(2)[F40, F52, F63-OH1.1] [F52, F63-OS2.3]
(3)[F63-OH1.1] [F63, F80-OS2.3]
(4)[F63-OH1.1]
(5)[F41, F82-OH1.1] [F01, F82-OS1.1]
(6)(a),(b),(c) [F02, F03-OS1.1] (a) [F80-OS1.1] (c) [F82-OS1.1]
(7)[F41, F53, F80-OH1.1]
(8)[F40, F41-OH1.1] [F40, F63-OS2.3]
(9)[F40, F50, F52, F53-OH1.1] [F53-OS3.4]
(12)[F40, F50, F52, F53-OH1.1] [F53-OS3.4]
9.32.3.12. Heat Recovery VentilatorsN/A
(2)[F40, F50, F52-OH1.1]
(3)[F40, F50, F52-OH1.1]
(4)[F53-OH1.1, OH1.2] [F53, F63-OS2.3] [F43, F53-OS3.4]
(5)[F62-OH1.1]
(6)[F81-OH1.1]
9.32.3.13. Outdoor Intake and Exhaust OpeningsN/A
(1)[F40, F50, F52-OH1.1] [F40, F44, F50-OS3.4]
(2)[F40, F50, F52, F53-OH1.1] [F43, F53-OS3.4]
(3)[F40, F50, F52-OH1.1] [F40, F50, F44-OS3.4]
(4)[F62, F63-OS2.3] [F62, F63-OP2.3]
(5)[F62, F63-OS2.3] [F62, F63-OP2.3]
(6)[F62, F63-OS2.3] [F62, F63-OP2.3]
(7)[F40, F50, F52-OH1.1] [F40, F44, F50, F53-OS3.4]
(8)[F40, F53-OH1.1]
(9)[F61-OH1.1] [F61-OS2.3]
(10)[F42-OH1.1] [F01, F42-OS1.1] [F42-OH2.5]
(11)[F42, F63-OH1.1] [F01, F42-OS1.1]
(12)[F42-OH1.1] [F01, F42-OS1.1]
(13)[F53, F82-OH1.1] [F43, F53, F82-OS3.4]
(14)[F53, F82-OH1.1] [F43, F53-OS3.4]
(15)[F42, F80-OH2.5] [F01, F42, F80-OS1.1]
9.33.1.1. ApplicationN/A
(3)[F40-OH1.1] [F40-OS3.4]
9.33.2.1. Residential Heating SystemsN/A
(1)[F51, F52-OH1.2] [F63-OH1.1] [F63-OS2.3]
9.33.3.1. Indoor Design TemperaturesN/A
(1)[F51-OH1.2]
9.33.4.1. Design of Heating and Air-Conditioning SystemsN/A
(1)[F41, F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] Applies only to heating systems. [F44-OS3.4] Applies only to heating systems.
9.33.4.2. Installation of Hydronic Heating SystemsN/A
(1)[F01-OS1.1] [F01-OP1.1] [F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F44-OS3.4] Applies to heating equipment.
9.33.4.3. Heating System ControlN/A
(1)[F51, F52-OH1.2] [F63-OH1.1]
9.33.4.4. AccessN/A
(1)[F82-OH1.1, OH1.2] [F82-OS2.3] Applies only to heating systems. [F82-OS1.1] [F82-OP1.1]
9.33.4.5. Protection from FreezingN/A
(1)[F81-OH1.1, OH1.2] [F81-OS2.3] Applies only to heating systems.
9.33.4.6. Expansion, Contraction and System PressureN/A
(1)[F20-OH1.1, OH1.2] [F20-OS3.2] [F20-OS2.3] Applies only to heating systems.
9.33.4.7. Structural MovementN/A
(1)[F23-OS3.4] [F23-OH1.1, OH1.2] [F23-OS1.1] [F23-OP1.1]
(2)[F20-OS3.3, OS3.4] [F20-OS1.1]
9.33.4.8. AsbestosN/A
(1)[F43-OH1.1]
9.33.4.9. Contaminant TransferN/A
(1)[F44-OH1.1] [F44-OS3.4]
9.33.5.1. Capacity of Heating AppliancesN/A
(1)[F131, F132, F133, F150-OR1.2]
(2)[F131, F132, F133, F150-OR1.2]
(3)[F131, F132, F133, F150-OR1.2]
9.33.5.2. Installation StandardsN/A
(1)[F41, F50, F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F44-OS3.4]
(2)[F41, F50, F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F44-OS3.4]
9.33.5.3. Design, Construction and Installation Standard for Solid-Fuel-Burning AppliancesN/A
(1)[F41, F43-OH1.1] [F51-OH1.2] [F51-OS2.3] [F43-OS3.4] [F01-OS1.1] [F01-OP1.1]
(2)[F10-OE]
9.33.6.2. Materials in Air Duct SystemsN/A
(1)[F01-OS1.1] [F01-OP1.1]
(2)(a),(b),(c),(d) [F01-OS1.1] (a),(b),(c),(d) [F01-OP1.1]
(3)[F01-OS1.1] [F01-OP1.1]
(4)(a),(b),(c),(d) [F01-OS1.1] (a),(b),(c),(d) [F01-OP1.1]
(6.1)[F81-OH1.1] [F44, F81-OS3.4]
(6.2)[F20, F80-OH1.1, OH1.2]
(7)(a),(b) [F41, F63-OH1.1] [F50, F51, F52-OH1.2] (a),(b) [F63-OS2.3]
9.33.6.3. TapeN/A
(1)[F01-OS1.1] [F01-OP1.1]
9.33.6.4. Covering, Linings, Adhesives and InsulationN/A
(5)[F01-OS1.1] [F01-OP1.1]
(6)[F01-OS1.1] (c) [F01, F02, F05-OS1.5] [F01-OP1.1]
(7)[F01-OP1.1] [F01-OP1.1]
(9)[F63-OH1.1] Applies to ventilation ducts and their fittings. [F51, F52-OH1.2] Applies to air duct distribution systems serving heating systems. [F03-OS1.1] Applies to air duct distribution systems. [F03-OP1.1] Applies to air duct distribution systems. [F63-OS2.3] Applies to air duct distribution systems.
9.33.6.5. Galvanized Steel or Aluminum Supply DuctsN/A
(1)[F20-OH1.1, OH1.2] [F01-OS1.1] [F01-OP1.1]
(2)[F20, F63-OH1.1] [F20, F51, F52-OH1.2] [F20, F63-OS2.3]
9.33.6.6. Construction of Ducts and PlenumsN/A
(1)[F03-OS1.1] [F03-OP1.1]
(2)[F01-OS1.1] [F20-OS3.1] [F63-OH1.1] [F51, F52-OH1.2] [F20, F63-OS2.3]
(3)[F43, F63-OH1.1] [F51, F52-OH1.2] [F01-OS1.1] [F63-OS2.3] [F01-OP1.1]
(4)[F43, F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F01-OS1.1] [F01-OP1.1]
(4.1)[F20-OH4] [F20-OP2.4] [F20-OS2.3]
(5)[F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F01-OS1.1] [F01-OP1.1]
9.33.6.7. Installation of Ducts and PlenumsN/A
(1)[F40-OH1.1] [F40-OS3.4]
(2)[F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F01-OS1.1] [F01-OP1.1]
(3)[F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] [F20-OS3.1]
(4)[F51, F52-OH1.2] [F63, F50-OH1.1] [F63, F80-OS2.3]
(5)[F01-OS1.1] [F01-OP1.1]
(6)[F80-OH1.1, OH1.2] [F80-OS2.3]
(7)(a) [F44, F81-OH1.2, OH1.3] (b),(c) [F44, F81-OH1.1]
(8)[F44, F81-OH1.1] [F81-OH1.2]
(9)[F44, F81-OH1.1] [F81-OH1.2]
(10)[F131-OR2]
(11)[F81-OH1.1, OH1.2, OH1.3]
9.33.6.8. Clearances of Ducts and PlenumsN/A
(2)(a),(b) [F01-OS1.1] (a),(b) [F01-OP1.1]
(3)(a),(b) [F01-OS1.1] (a),(b) [F01-OP1.1]
(4)(a),(b),(c) [F01-OS1.1] (a),(b),(c) [F01-OP1.1]
(5)[F01-OS1.1] [F01-OP1.1]
9.33.6.9. Adjustable Dampers and Balance StopsN/A
(1)[F40, F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3] Applies to branch supply ducts that are not fitted with diffusers with adjustable balance stops.
9.33.6.10. Warm-Air Supply Outlets and Return Inlets – GeneralN/A
(2)(a),(b) [F01, F02-OS1.1] (a),(b) [F01, F02-OP1.1]
9.33.6.10A. Supply, Return, Intake and Exhaust OpeningsN/A
(1)[F30-OS3.1] [F81-OH1.2]
(2)[F81-OH1.1] [F81, F44-OS3.4] [F41, F44-OH1.1]
(3)[F81-OH1.1] [F82, F81-OH1.1]
(4)[F82-OS3.4]
9.33.6.11. Warm Air Supply OutletsN/A
(1)[F40, F63-OH1.1] [F51, F52-OH1.2] [F63-OS2.3]
(2)[F63-OH1.1] [F51-OH1.2] [F63-OS2.3]
(3)[F40, F63-OH1.1] [F51-OH1.2]
(4)[F40, F63-OH1.1] [F51-OH1.2] [F63-OS2.3]
(5)[F40, F63-OH1.1] [F51-OH1.2] [F63-OS2.3]
(6)[F40, F63-OH1.1] [F51-OH1.2] [F63-OS2.3]
(8)[F31-OS3.2]
(9)[F40, F63-OH1.1] [F51-OH1.2] [F63-OS2.3] Applies to warm-air supply outlets located in finished areas.
(10)[F40-OH1.1] [F40-OS3.4]
9.33.6.12. Return-Air InletsN/A
(1)[F44, F40-OH1.1] [F44, F40-OS3.4]
(2)[F63-OH1.1] [F51-OH1.2]
(3)[F63-OH1.1] [F51-OH1.2] [F63-OS2.3]
9.33.6.13. Return-Air SystemN/A
(1)[F63-OH1.1] [F51-OH1.2] [F63-OS2.3]
(1.1)[F01, F02-OP1.1] [F01, F02-OS1.1]
(2)[F01-OS1.1] [F01-OP1.1]
(3)[F01-OS1.1] [F01-OP1.1]
(4)(a),(b),(c) [F01-OS1.1] (a),(b),(c) [F01-OP1.1]
(5)[F51, F52-OH1.1, OH1.2] [F51, F52-OS2.3]
(6)[F63-OH1.1] [F51-OH1.2] [F63-OS2.3]
(7)(a),(b) [F44-OH1.1] (a),(b) [F44-OS3.4]
9.33.6.14. Filters and Odour Removal EquipmentN/A
(1)[F01-OS1.1] [F01-OP1.1]
(2)[F32-OS3.3] [F41-OH1.1]
(3)(a),(b) [F81-OH1.1]
9.33.7.1. Recessed Radiators and ConvectorsN/A
(1)[F01-OS1.1] [F01-OP1.1]
9.33.7.2. Surface TemperatureN/A
(1)[F31-OS3.2]
9.33.8.1. Piping Materials and InstallationN/A
(1)[F20-OS3.2] [F20-OH1.1, OH1.2]
(2)[F21, F40-OH1.1] [F21, F51-OH1.2]
(3)[F20-OS2.2]
9.33.8.2. Insulation and CoveringsN/A
(1)[F80-OH1.2] [F80-OS3.2]
(2)(a),(b) [F01-OS1.1] (a),(b) [F01-OP1.1]
(3)(a),(b) [F01, F02-OS1.1, OS1.2] (a),(b) [F01, F02-OP1.1, OP1.2]
(4)[F01, F02-OS1.1, OS1.2] [F01, F02-OP1.1]
(5)[F31-OS3.2]
9.33.8.3. ClearancesN/A
(1)[F01-OS1.1] [F01-OP1.1]
9.33.8.4. ProtectionN/A
(1)[F01-OS1.1] [F01-OP1.1]
(2)[F01-OS1.1] [F01-OP1.1]
9.33.9.1. Cooling UnitsN/A
(1)(a),(b),(c) [F43-OH1.1] [F51-OH1.2]
9.33.10.2. Factory-Built ChimneysN/A
(1)[F01-OS1.1] [F44-OS3.4] [F44, F41-OH1.1] [F01-OP1.1]
9.34.1.3. Location of Equipment in Public AreasN/A
(1)[F10-OS3.1] [F32, F81-OS3.3]
9.34.1.4. Recessed Lighting FixturesN/A
(1)[F01-OS1.1]
9.34.1.5. Wiring and CablesN/A
(1)[F02-OS1.2] [F02-OP1.2]
9.34.2.1. Lighting of EntrancesN/A
(1)[F30-OS3.1] [F34-OS4.2]
9.34.2.2. Outlets in Houses and Dwelling UnitsN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
9.34.2.3. StairwaysN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
9.34.2.4. BasementsN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
9.34.2.5. Storage RoomsN/A
(1)[F30-OS3.1]
9.34.2.6. Garages and CarportsN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
(3)[F30-OS3.1]
9.34.2.7. Public and Service AreasN/A
(1)[F30-OS3.1]
(2)[F30-OS3.1]
(3)[F30-OS3.1]
9.35.2.2. Garage FloorN/A
(1)[F40-OS1.1]
9.35.3.2. Protection from Damage due to Soil MovementN/A
(1)[F21-OH1.1, OH1.2, OH1.3] [F21-OH4] Applies to floors and elements that support floors. [F21-OP2.3, OP2.4] [F21-OS2.3] [F21-OS3.1] Applies to floors and elements that support floors.
(2)[F21-OH1.1, OH1.2, OH1.3] [F21-OH4] Applies to floors and elements that support floors. [F21-OP2.3, OP2.4] [F21-OS2.3] [F21-OS3.1] Applies to floors and elements that support floors.
9.35.3.4. Column PiersN/A
(1)[F80-OP2.3] [F80-OS2.3]
(2)[F20-OP2.1, OP2.2] [F20-OS2.1, OS2.2]
9.35.4.2. ColumnsN/A
(1)[F20-OP2.1] [F20-OS2.1]
9.35.4.3. AnchorageN/A
(1)[F22-OP2.4, OP2.5] [F22-OS2.4, OS2.5]
9.37.2.1. ExclusionsN/A
(2)[F42-OH2.5] [F20-OP2.1] [F20-OS2.1] [F30-OS3.1]
9.37.2.2. FoundationsN/A
(2)[F20-OP2.1] [F20-OS2.1]
9.38.1.1. Material RequirementsN/A
(1)[F20-OP2.1] [F20-OS2.1]
9.38.1.2. Requirement for Wood PreservativeN/A
(1)[F80-OH4] [F80-OP2.1, OP2.3] [F80-OS2.3, OS3.1]
9.38.1.3. Exterior JointsN/A
(1)[F61-OH1.3] [F42-OH2.5] [F61-OP2.3]
9.38.2.2. Attachment of LogsN/A
(1)[F61-OH1.3] [F42-OH2.5] [F61-OP2.3]
9.38.2.3. Joining LogsN/A
(1)[F22-OP2.5] [F22-OS2.5]
9.38.2.4. Vertical LogsN/A
(1)[F22-OP2.5] [F22-OS2.5]
9.38.2.5. PlatesN/A
(1)[F20-OP2.1] [F20-OS2.1]
9.38.3.1. Support Over OpeningsN/A
(1)[F22-OP2.5] [F22-OS2.5]
9.38.3.2. ClearanceN/A
(1)[F21-OP2.4] [F21-OS2.4]
9.39.3.3. Foundations and AnchorageN/A
(1)[F20, F22-OS2.1, OS2.2, OS2.5] [F20, F22-OP2.1, OP2.2, OP2.4, OP2.5]
9.40.1.3. Reinforcing SteelN/A
(1)[F20, F21-OH4] [F20-OP2.1, OP2.4] [F21-OP2.4] [F20-OS2.1]
9.40.1.4. Slab ConstructionN/A
(1)[F20, F21, F55, F61, F80-OH1.1, OH1.2] [F20, F21, F61, F80-OH1.3] Applies where concrete supports or is used in an environmental separator. [F20, F21, F80-OH4] [F20-OP2.1, OP2.4] [F21-OP2.3, OP2.4] [F80-OP2.3] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F21, F80-OS2.3] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F80-OS3.1]
(2)[F20, F21, F55, F61, F80-OH1.1, OH1.2] [F20, F21, F61, F80-OH1.3] Applies where concrete supports or is used in an environmental separator. [F20, F21, F80-OH4] [F20-OP2.1, OP2.4] [F21-OP2.3, OP2.4] [F80-OP2.3] [F20-OP2.3] Applies to elements that support or are part of an environmental separator. [F20-OS2.1] [F21, F80-OS2.3] [F20-OS2.3] Applies to elements that support or are part of an environmental separator. [F20, F21, F80-OS3.1]
(3)[F20, F21-OH4] [F20-OP2.1, OP2.4] [F21-OP2.4] [F20-OS2.1]
(4)[F22-OP2.5] [F22-OS2.5]
(5)[F61, F62-OH1.1, OH1.2, OH1.3] [F61, F62, F80-OP2.3] [F61, F62, F80-OS2.3] [F30-OS3.1]
9.41.2.1. Change of Use and Compensating ConstructionN/A
(1)9.5 Applies to the design of areas and spaces in buildings. [F74-OA2] [F70, F71-OH2.3] [F101-OH6] [F30-OS3.1] [F10-OS3.7] 9.7 Applies to windows and skylights in Part 9 buildings. [F55, F61, F62, F63, F80, F81, F82-OH1.1] [F51, F53, F54, F55, F61, F62, F63, F80, F82-OH1.2] [F61, F62, F63-OH1.3] [F102-OH7] [F42-OP2.3] [F03, F20-OS1.2] [F10-OS1.5] [F20-OS2.1] [F20, F21, F42, F61, F63-OS2.3] [F30-OS3.1] [F10, F30-OS3.7] [F34-OS4.1] [F131-OR2] 9.10.17. Applies to flame-spread limits in Part 9 buildings. [F01, F02-OS1.2] [F01, F02, F05-OS1.5] 9.31. Applies to plumbing facilities serving Part 9 dwelling units. [F44, F62-OH1.1] [F40, F41, F62-OH1.2, OH1.3] [F70, F71, F72, F80-OH2.1] [F41-OH2.2] [F70, F71, F72, F80, F81-OH2.3] [F01-OS1.1] [F31, F80-OS2.3] [F20-OS3.1] [F23-OS3.4] 9.32. Applies to ventilation in Part 9 residential occupancies. [F40, F42, F50, F52, F53, F61, F80, F81, F82-OH1.1] [F42, F51, F52, F80, F81-OH1.2] [F42, F80-OH2.5] [F82-OP1.1] [F131-OR2] [F02, F03, F80, F82-OS1.1] [F42, F53, F61, F63-OS2.3] [F40, F43, F44, F50, F53, F81-OS3.4] 9.34.1. [F01-OS1.1] [F10-OS3.1] [F32, F81-OS3.3] Applies to electrical facilities in Part 9 buildings. 9.34.2. [F30-OS3.1] Applies to lighting outlets for Part 9 buildings. [F34-OS4.2] Applies to lighting outlets for Part 9 buildings. 9.34.3. [F30-OS3.1] [F10-OS3.7] Applies to emergency lighting for Part 9 buildings.
9.41.2.2. Performance Level Evaluation and Compensating ConstructionN/A
(1)[F140-OC]

Table 10 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 10 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 10 of Division B
Acceptable SolutionsObjectives and Functional Statements
10.3.1.1. GeneralN/A
(1)3.2.6. Applies to additional requirements for high buildings. [F03, F06, F12, F13, F82-OP1.2] [F03-OP3.1] [F02, F03, F06, F12, F13, F82-OS1.2] [F02, F03, F05, F06, F10, F11, F12, F82-OS1.5] [F30-OS3.1] [F11, F12-OS3.7] 3.7. Applies to health requirements for buildings. [F74-OA2] [F50-OH1.1] [F40, F72-OH2.1] [F70-OH2.2] [F71-OH2.3] [F40, F41- OH2.4] [F101-OH6] [F102-OH7] [F01-OP1.1] [F01-OS1.1] [F20, F30-OS3.1] [F32-OS3.3] [F43, F44-OS3.4] 3.11. Applies to public pools. [F74-OA2] [F50-OH1.1] [F72-OH2.1] [F46, F70-OH2.2] [F40, F41, F45, F71, F122- OH2.3] [F40, F41-OH2.4] [F101-OH6] [F01-OS1.1] [F04-OS1.3] [F03-OS2.1] [F12, F30, F34, F36, F120, F121, F123, F124-OS3.1] [F31-OS3.2] [F32, F34-OS3.3] [F34, F43, F44, F81, F122-OS3.4] [F10, F11, F12, F34, F123-OS3.7] 3.12. Applies to public spas. [F74-OA2] [F46-OH2.2] [F40, F41, F70, F71, F72, F81, F122-OH2.3] [F40, F41-OH2.4] [F11, F12, F13, F30, F34, F36, F81, F120, F121, F123, F124-OS3.1] [F43, F81, F122-OS3.4] [F10, F34, F123-OS3.7] 9.5. Applies to the design of areas and spaces in buildings. [F74-OA2] [F70, F71-OH2.3] [F101-OH6] [F30-OS3.1] [F10-OS3.7] 9.7. Applies to windows and skylights in Part 9 buildings. [F55, F61, F62, F63, F80, F81, F82-OH1.1] [F51, F53, F54, F55, F61, F62, F63, F80, F82-OH1.2] [F61, F62, F63-OH1.3] [F102-OH7] [F42-OP2.3] [F03, F20-OS1.2] [F10-OS1.5] [F20-OS2.1] [F20, F21, F42, F61, F63-OS2.3] [F30-OS3.1] [F10, F30-OS3.7] Solution [F34-OS4.1] [F131-OR2] 9.10.17. Applies to flame spread limits in Part 9 buildings. [F01, F02-OS1.2] [F01, F02, F05-OS1.5] 9.31. Applies to plumbing facilities serving Part 9 dwelling units. [F44, F62-OH1.1] [F40, F41, F62-OH1.2, OH1.3] [F70, F71, F72, F80-OH2.1] [F41-OH2.2] [F70, F71, F72, F80, F81-OH2.3] [F01-OS1.1] [F31, F80-OS2.3] [F20-OS3.1] [F23-OS3.4] 9.32. Applies to ventilation in Part 9 residential occupancies. [F40, F42, F50, F52, F53, F61, F80, F81, F82-OH1.1] [F42, F51, F52, F80, F81-OH1.2] [F42, F80-OH2.5] [F82-OP1.1] [F131-OR2] [F02, F03, F80, F82-OS1.1] [F42, F53, F61, F63-OS2.3] [F40, F43, F44, F50, F53, F81-OS3.4] 9.34.1. [F01-OS1.1] [F10-OS3.1] [F32, F81-OS3.3] Applies to electrical facilities in Part 9 buildings. 9.34.2. [F30-OS3.1] Applies to lighting outlets for Part 9 buildings. [F34-OS4.2] Applies to lighting outlets for Part 9 buildings. 9.34.3. [F30-OS3.1] [F10-OS3.7] Applies to emergency lighting for Part 9 buildings.
10.3.2.1. GeneralN/A
(1)[F140-OC]

Table 11 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 11 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 11 of Division B
Acceptable SolutionsObjectives and Functional Statements
11.2.1.3. Prohibition of Occupancy CombinationsN/A
(1)[F41-OH2.1] [F02, F03-OS1.2] [F10-OS1.5]
11.3.1.1. Material Alteration or Repair of a Building SystemN/A
(1)[F140-OC]
11.3.3.2. Extensive RenovationN/A
(4)[F02, F04-OP1.2, OP1.3]
(5)[F02, F04-OS1.2, OS1.3]
11.3.5.2. Vertical Separations and Existing Sewage SystemsN/A
(1)[F110-OE] [F113-OH2.1, OH5]
11.4.1.1. Performance LevelN/A
(1)[F140-OC]
11.4.3.2. StructuralN/A
(1)[F110-OE] Applies to manure storage tanks. [F21, F22, F61, F80, F81-OH4] [F04-OP1.2] [F20-OP2.1, OP2.2, OP2.3, OP2.4, OP2.6] [F21-OP2.1, OP2.2, OP2.4, OP2.5, OP2.6] [F22-OP2.1, OP2.3, OP2.4, OP2.5] [F81-OP2.1, OP2.4] [F82-OP2.3] [F61-OP2.3, OP2.4] [F80-OP2.3, OP2.4, OP2.6] [F04-OP3.1] [F21-OP4.1, OP4.4] [F20-OP4.3] [F04-OS1.2] [F20-OS2.1, OS2.2, OS2.3, OS2.4] [F21-OS2.1, OS2.2, OS2.3, OS2.5, OS2.6] [F61-OS2.3] [F80-OS2.3] [F81-OS2.3] [F82-OS2.3] [F30-OS3.1] [F43-OS3.4] Applies to manure storage tanks.
11.4.3.3. Increase in Occupant LoadN/A
(1)As applied to fire alarm systems in Subsection 3.2.4.: [F12, F13, F81, F82-OP1.2] [F02, F03, F11, F12, F13, F81, F82-OS1.2] [F11, F13-OS1.4] [F10, F11, F12, F13, F81, F82-OS1.5] [F11, F12-OS3.7] Applies to voice communication systems. As applied to smoke control measures, and at least one elevator to permit transport of firefighters to all floors in hotels whose floor level is more than 18 m high measured between grade and floor level of the top storey in Subsection 3.2.6.: [F02, F03, F06, F12, F13, F82-OP1.2] [F03-OP3.1] [F02, F03, F06, F12, F13, F82-OS1.2] [F02, F03, F05, F06, F10, F12-OS1.5] [F30-OS3.1] As applied to lighting of exits, lighting of access to exits and emergency lighting in Subsection 3.2.7.: [F40-OH2.4] [F12-OH5] Applies to the requirement for a suitably identified shut-off valve outside the building. [F01-OP1.1] [F01, F02, F03, F06, F12, F81-OP1.2] [F02-OP3.1] [F12-OS1.1] Applies to the requirement for a suitably identified shut-off valve outside the building. [F02, F03, F06, F10, F11, F12, F81-OS1.2] [F02, F03, F06, F10, F11, F12, F81-OS1.5] [F02, F06, F30, F81-OS3.1] [F36-OS3.6] [F10, F11, F12, F81-OS3.7] As applied to access to exit widths based on occupant load in Article 3.3.1.16.: [F10-OS3.7] As applied to door release hardware in Article 3.3.1.12.: [F73-OA1] [F30-OS3.1] [F10, F12-OS3.7] As applied to travel distance in Article 3.4.2.4.: [F10-OS3.7] As applied to number of exits in Articles 3.4.2.3. and 3.4.2.5.: [F05, F10-OS1.5] [F10-OS3.7] As applied to exit widths based on occupant load in Article 3.4.3.2.: [F12-OP1.2] [F12-OS1.2] [F30-OS3.1] [F10, F12-OS3.7] As applied to exit signs in Articles 3.4.5.1. and 3.4.5.2.: [F10, F81-OS3.7] As applied to door release hardware in Article 3.4.6.15.: [F73-OA1] [F02-OS1.2] [F10, F81-OS1.5] [F10, F81-OS3.7] As applied to access to exit widths based on occupant load in Subsection 9.9.3.: [F30-OS3.1] [F10-OS3.7] As applied to exit widths based on occupant load in Subsection 9.9.3.: [F30-OS3.1] [F10-OS3.7] As applied to travel distance in Article 9.9.9.1.: [F10-OS3.7] As applied to number of exits in Articles 9.9.8.2. and 9.9.9.2.: [F10-OS3.7] As applied to exit signs in Subsection 9.9.10.: [F73-OA1] [F10-OS1.5] [F10-OS3.7] As applied to lighting of exits, lighting of access to exits and emergency lighting in Article 9.9.11.: [F30-OS3.1] [F10-OS3.7] As applied to fire alarm systems in Subsection 9.10.18.: [F02-OS1.2] Applies to a sprinklered building. [F03, F11-OS1.2] [F11-OS1.5] As applied to smoke alarms in Subsection 9.10.19.: [F11, F81-OS1.4] [F11, F81, F82-OS1.5]
(3)As applied to required ventilation for buildings in Sentence 6.2.2.1.(2): [F50-OH1.1] As applied to plumbing facilities for buildings in Subsection 3.7.4.: [F74-OA2] [F50-OH1.1] [F72-OH2.1] [F70-OH2.2] [F71-OH2.3] [F40-OH2.4] [F101-OH6] [F20, F30-OS3.1] As applied to plumbing facilities serving Part 9 dwelling units in Article 9.31.1.1.: [F44, F62-OH1.1] [F40, F41, F62-OH1.2, OH1.3] [F70, F71, F72, F80-OH2.1] [F41-OH2.2] [F70, F71, F72, F80, F81-OH2.3] [F01-OS1.1] [F31, F80-OS2.3] [F20-OS3.1] [F23-OS3.4]
11.4.3.4. Change in Major OccupancyN/A
(1)[F02, F03, F04-OP1.2, OP1.3] Applies to increase in construction index. [F02, F04-OP1.2, OP1.3] Applies where the building is required to be sprinklered. [F02, F03, F04-OS1.2, OS1.3] Applies to increase in construction index. [F02, F04-OS1.2, OS1.3] Applies where the building is required to be sprinklered. Applies where an Early Warning system is provided for a Part 3 building, in accordance with Subsection 3.2.4.: [F12, F13, F81, F82-OP1.2] [F02, F03, F11, F12, F13, F81, F82-OS1.2] [F11, F13-OS1.4] [F10, F11, F12, F13, F81, F82-OS1.5] [F11, F12-OS3.7] Applies to voice communication systems. Applies where an Early Warning system is provided for a Part 9 building, in accordance with Subsection 9.10.18.: [F02-OS1.2] Applies to a sprinklered building. [F03, F11-OS1.2] [F11-OS1.5] Applies where an Early Warning system is provided for a Part 9 building, in accordance with Subsection 9.10.19.: [F11, F81-OS1.4] [F11, F81, F82-OS1.5]
(2)As applied to additional requirements for high buildings in Subsection 3.2.6.: [F03, F06, F12, F13, F82-OP1.2] [F03-OP3.1] [F02, F03, F06, F12, F13, F82-OS1.2] [F02, F03, F05, F06, F10, F11, F12, F82-OS1.5] [F30-OS3.1] [F11, F12-OS3.7] As applied to health requirements for buildings in Section 3.7.: [F74-OA2] [F50-OH1.1] [F40, F72-OH2.1] [F70-OH2.2] [F71-OH2.3] [F40, F41-OH2.4] [F101-OH6] [F102-OH7] [F01-OP1.1] [F01-OS1.1] [F20, F30-OS3.1] [F32-OS3.3] [F43, F44-OS3.4] As applied to public pools in Section 3.11.: [F74-OA2] [F50-OH1.1] [F72-OH2.1] [F46, F70-OH2.2] [F40, F41, F45, F71, F122-OH2.3] [F40, F41-OH2.4] [F101-OH6] [F01-OS1.1] [F04-OS1.3] [F03-OS2.1] [F12, F30, F34, F36, F120, F121, F123, F124-OS3.1] [F31-OS3.2] [F32, F34-OS3.3] [F34, F43, F44, F81, F122-OS3.4] [F10, F11, F12, F34, F123-OS3.7] As applied to public spas in Section 3.12.: [F74-OA2] [F46-OH2.2] [F40, F41, F70, F71, F72, F81, F122-OH2.3] [F40, F41-OH2.4] [F11, F12, F13, F30, F34, F36, F81, F120, F121, F123, F124-OS3.1] [F43, F81, F122-OS3.4] [F10, F34, F123-OS3.7] As applied to required ventilation for buildings in Sentence 6.2.2.1.(2): [F50-OH1.1] As applied to Sentence 6.2.3.9.(1): [F40-OH1.1] [F44-OS1.1] As applied to Sentence 6.2.4.7.(10): [F40-OH1.1] [F44-OS1.1] As applied to Subsection 9.5.1.: [F10-OS3.7] As applied to Articles 9.5.3.1. to 9.5.10.1.: [F70, F71-OH2.3] [F101-OH6] [F30-OS3.1] [F10-OS3.7] As applied to windows and skylights in Part 9 buildings in Section 9.7.: [F55, F61, F62, F63, F80, F81, F82-OH1.1] [F51, F53, F54, F55, F61, F62, F63, F80, F82-OH1.2] [F61, F62, F63-OH1.3] [F102-OH7] [F42-OP2.3] [F03, F20-OS1.2] [F10-OS1.5] [F20-OS2.1] [F20, F21, F42, F61, F63-OS2.3] [F30-OS3.1] [F10, F30-OS3.7] [F34-OS4.1] [F131-OR2] As applied to flame spread limits in Part 9 buildings Subsection 9.10.17.: [F01, F02-OS1.2] [F01, F02, F05-OS1.5] As applied to plumbing facilities serving Part 9 dwelling units in Section 9.31.: [F44, F62-OH1.1] [F40, F41, F62-OH1.2, OH1.3] [F70, F71, F72, F80-OH2.1] [F41-OH2.2] [F70, F71, F72, F80, F81-OH2.3] [F01-OS1.1] [F31, F80-OS2.3] [F20-OS3.1] As applied to ventilation in Part 9 residential occupancies in Section 9.32.: [F40, F42, F50, F52, F53, F61, F80, F81, F82-OH1.1] [F42, F51, F52, F80, F81-OH1.2] [F42, F80-OH2.5] [F82-OP1.1] [F131-OR2] [F02, F03, F80, F82-OS1.1] [F42, F53, F61, F63-OS2.3] [F40, F43, F44, F50, F53, F81-OS3.4] As applied to Subsection 9.34.1.: [F01-OS1.1] [F10-OS3.1] [F32, F81-OS3.3] Applies to electrical facilities in Part 9 buildings. As applied to Subsection 9.34.2.: [F30-OS3.1] Applies to lighting outlets for Part 9 buildings. [F34-OS4.2] Applies to lighting outlets for Part 9 buildings. As applied to Subsection 9.34.3.: [F30-OS3.1] [F10-OS3.7] Applies to emergency lighting for Part 9 buildings.
(3)As applied to fire alarm systems in Subsection 3.2.4.: [F12, F13, F81, F82-OP1.2] [F02, F03, F11, F12, F13, F81, F82-OS1.2] [F11, F13-OS1.4] [F10, F11, F12, F13, F81, F82-OS1.5] [F11, F12-OS3.7] Applies to voice communication systems. As applied to smoke control measures, and at least one elevator to permit transport of fire fighters to all floors in hotels whose floor level is more than 18 m high, measured between grade and the floor level of the top storey in Subsection 3.2.6.: [F02, F03, F06, F12, F13, F82-OP1.2] [F03-OP3.1] [F02, F03, F06, F12, F13, F82-OS1.2] [F02, F03, F05, F06, F10, F12-OS1.5] [F30-OS3.1] As applied to lighting of exits lighting of access to exits and emergency lighting in Subsection 3.2.7.: [F40-OH2.4] Applies to the requirement for a suitably identified shut-off valve outside the building. [F01-OP1.1] [F01, F02, F03, F06, F12, F81-OP1.2] [F02-OP3.1] [F12-OS1.1] Applies to the requirement for a suitably identified shut-off valve outside the building. [F02, F03, F06, F10, F11, F12, F81-OS1.2] [F02, F03, F06, F10, F11, F12, F81-OS1.5] [F02, F06, F30, F81-OS3.1] [F36-OS3.6] [F10, F11, F12, F81-OS3.7] As applied to access to exit widths based on occupant load in Article 3.3.1.16.: [F10-OS3.7] As applied to door release hardware in Article 3.3.1.12.: [F73-OA1] [F30-OS3.1] [F10, F12-OS3.7] As applied to travel distance in Article 3.4.2.4.: [F10-OS3.7] As applied to number of exits in Articles 3.4.2.3. and 3.4.2.5.: [F05, F10-OS1.5] [F10-OS3.7] As applied to exit widths based on occupant load in Article 3.4.3.2.: [F12-OP1.2] [F12-OS1.2] [F30-OS3.1] [F10, F12-OS3.7] As applied to exit signs in Articles 3.4.5.1. and 3.4.5.2.: [F10, F81-OS3.7] As applied to door release hardware in Article 3.4.6.15.: [F73-OA1] [F02-OS1.2] [F10, F81-OS1.5] [F10, F81-OS3.7] As applied to access to exit widths based on occupant load in Subsection 9.9.3.: [F30-OS3.1] [F10-OS3.7] As applied to exit widths based on occupant load in Subsection 9.9.3.: [F30-OS3.1] [F10-OS3.7] As applied to travel distance in Article 9.9.9.1.: [F10-OS3.7] As applied to number of exits in Articles 9.9.8.2. and 9.9.9.2.: [F10-OS3.7] As applied to exit signs in subsection 9.9.10.: [F10-OS1.5] [F10-OS3.7] [F73-OA1] As applied to lighting of exits, lighting of access to exits and emergency lighting in Article 9.9.11.: [F30-OS3.1] [F10-OS3.7] As applied to fire alarm systems in Subsection 9.10.18.: [F02-OS1.2] Applies to a sprinklered building. [F03, F11-OS1.2] [F11-OS1.5] As applied to smoke alarms in Subsection 9.10.19.: [F11, F81-OS1.4] [F11, F81, F82-OS1.5]
(4)As applied to fire separations in Article 3.1.3.1.: [F03-OP1.2] [F03-OS1.2] As applied to Table 11.4.3.4.B.: [F140-OC]
(6)[F02, F04-OP1.2, OP1.3] [F02, F04-OS1.2, OS1.3]
11.4.3.5. PlumbingN/A
(1)[F140-OC] [F20-OE] [F20-OE] Applies to drainage piping. [F20-OE] Applies to underground drainage piping. [F20, F81, F113-OE] [F40-OE] [F44-OE] [F44-OE] Applies to oil interceptors. [F44, F81, F112-OE] [F81-OE] Applies to underground drainage piping. [F81, F112-OE] [F111-OE] Applies to drainage systems served by a sewage system. [F20-OH1.1] [F20-OH1.1] Applies to vent piping. [F20, F43, F81-OH1.1] [F20, F43, F81-OH1.1] Applies to venting system. [F20, F43, F81-OH1.1] Applies to bell and spigot joints in venting systems. [F20, F81-OH1.1] [F21-OH1.1] [F40-OH1.1] [F40, F41, F50-OH1.1] Applies to the requirement for ventilation. [F40, F81-OH1.1] [F41-OH1.1] [F41, F81-OH1.1] Applies to vent pipes. [F43-OH1.1] [F43, F80, F81-OH1.1] Applies to venting system. [F43, F81-OH1.1] Applies to venting system. [F44, F81-OH1.1] [F80-OH1.1] [F81-OH1.1] [F81-OH1.1] Applies to venting system. [F31-OH1.2] [F20-OH1.3] [F20, F80, F81-OH1.3] [F61-OH1.3] [F61, F80-OH1.3] [F62-OH1.3] [F62, F81-OH1.3] [F80, F81-OH1.3] [F81-OH1.3] Applies to water pipes. [F20-OH2.1] [F20-OH2.1] Applies to drainage piping. [F20, F80, F81, F113-OH2.1] [F20, F80, F81, F113-OH2.1] Applies to building sewer. [F20, F80, F81, F113-OH2.1] Applies to drainage system. [F20, F80, F81, F113-OH2.1] Applies to Waste Fittings. [F20, F81-OH2.1] Applies to drainage piping. [F20, F81-OH2.1] Applies to bell and spigot joints in drainage systems. [F21-OH2.1] [F40-OH2.1] [F41, F81-OH2.1] [F43-OH2.1] [F45-OH2.1] [F62-OH2.1] [F62, F70-OH2.1] [F70-OH2.1] [F72-OH2.1] [F80-OH2.1] [F80, F81-OH2.1] Applies to drainage system. [F80, F81, F113-OH2.1] [F80, F81, F113-OH2.1] Applies to drainage system. [F81-OH2.1] [F81-OH2.1] Applies to drainage system. [F81, F113-OH2.1] [F20-OH2.2] [F20-OH2.2] Applies to water piping. [F20, F46, F80, F81-OH2.2] [F20, F46, F80, F81-OH2.2] Applies to water piping. [F20, F46, F80, F81-OH2.2] Applies to Supply Fittings. [F20, F46, F81-OH2.2] Applies to water piping. [F20, F80, F81-OH2.2] [F20, F81-OH2.2] [F21-OH2.2] [F41, F46-OH2.2] [F46-OH2.2] [F46-OH2.2] Applies to Water Systems. [F46, F70-OH2.2] [F46, F70, F81-OH2.2] [F46, F80, F81-OH2.2] [F46, F80, F81-OH2.2] Applies to water piping. [F46, F81-OH2.2] [F46, F81-OH2.2] Applies to water piping. [F70-OH2.2] [F70, F80-OH2.2] [F70, F81-OH2.2] [F80-OH2.2] [F81-OH2.2] Applies to the size of air break. [F81-OH2.2] Applies to water service pipe. [F81-OH2.2] Applies to private water supply. [F81-OH2.2] Applies to water system. [F82-OH2.2] [F71-OH2.3] [F71, F72-OH2.3] Applies to equipment. [F72-OH2.3] [F40-OH2.4] [F40, F46-OH2.4] [F41-OH2.4] [F41-OH2.4] Applies to floor drains in garbage rooms. [F41, F81-OH2.4] [F63-OH2.4] [F81-OH2.4] [F42-OH2.5] [F81-OH2.6] Applies to drainage pipe. [F81-OH2.6] Applies to private sewers. [F20-OH2.1, OH2.2] [F20, F46, F80, F81, F113-OH2.1, OH2.2] [F80-OH2.1, OH2.2] [F80-OH2.1, OH2.2, OH2.3, OH2.4] [F82-OH2.1, OH2.2, OH2.3, OH2.4] Applies to the need for maintenance. [F81-OH2.1, OH2.2, OH2.4] [F20, F81-OH2.1, OH2.3] [F20, F81, F113-OH2.1, OH2.3] [F80-OH2.1, OH2.3] Applies to Drainage Systems. [F81-OH2.1, OH2.3, OH2.4] [F81, F82-OH2.1, OH2.3, OH2.4] [F40-OH2.1, OH2.4] [F40, F41-OH2.1, OH2.4] [F41, F43-OH2.1, OH2.4] [F41, F81-OH2.1, OH2.4] [F43-OH2.1, OH2.4] [F80-OH2.1, OH2.4] [F80, F81-OH2.1, OH2.4] [F81-OH2.1, OH2.4] [F82-OH2.1, OH2.4] [F20, F80, F81-OH2.1, OH2.6] [F20, F80, F81, F113-OH2.1, OH2.6] [F20, F81-OH2.1, OH2.6] [F81-OH2.2, OH2.4] [F41, F81-OH2.4, OH2.5] [F20-OH4] [F43-OH5] [F44-OH5] [F44-OH5] Applies to oil interceptors. [F81-OH5] [F20-OS2.2, OS2.3] [F01-OP1.1] [F01-OP1.1] Applies to oil interceptors. [F01, F40, F81-OP1.1] [F20, F81-OP1.1] [F02, F12, F81-OP1.2] [F12-OP1.4] [F61-OP2.3] [F61, F80-OP2.3] [F61, F81-OP2.3] [F62-OP2.3] [F63-OP2.3] [F80-OP2.3] [F81-OP2.3] [F20-OP5] [F20, F31, F46, F80, F81-OP5] [F20, F46, F80, F81-OP5] [F20, F46, F80, F81-OP5] Applies to Supply Fittings. [F20, F46, F80, F81-OP5] Applies to water piping. [F20, F46, F80, F81, F113-OP5] [F20, F46, F81-OP5] [F20, F46, F81-OP5] Applies to water piping. [F20, F80, F81-OP5] [F20, F80, F81-OP5] Applies to drainage system. [F20, F80, F81, F113-OP5] [F20, F80, F81, F113-OP5] Applies to drainage system. [F20, F80, F81, F113-OP5] Applies to Waste Fittings. [F20, F81-OP5] [F20, F81-OP5] Applies to drainage system. [F20, F81-OP5] Applies to bell and spigot joints in drainage systems. [F20, F81, F113-OP5] [F21-OP5] [F21, F61, F81-OP5] [F40-OP5] [F46-OP5] [F46, F80, F81-OP5] [F46, F80, F81-OP5] Applies to water piping. [F62-OP5] [F62, F72-OP5] [F72-OP5] [F80-OP5] [F80, F81-OP5] [F80, F81-OP5] Applies to drainage system. [F80, F81, F113-OP5] [F80, F81, F113-OP5] Applies to drainage system. [F81-OP5] [F81-OP5] Applies to water pipes. [F81-OP5] Applies to Drainage Systems. [F81, F113-OP5] [F81, F113-OP5] Applies to drainage pipes. [F82-OP5] [F01-OS1.1] [F01-OS1.1] Applies to oil interceptors. [F01, F40, F81-OS1.1] [F01, F81-OS1.1] [F20, F81-OS1.1] [F81-OS1.1] [F02, F12, F81-OS1.2] [F12-OS1.4] [F20, F81-OS2.1] [F20, F81-OS2.3] [F20-OS3.1] [F20, F30, F80-OS3.1] [F30-OS3.1] [F30-OS3.1] Applies to the requirement for lighting. [F80-OS3.1] [F81-OS3.1] [F20, F81-OS3.2] [F31-OS3.2] [F31, F81-OS3.2] [F31, F81-OS3.2] Applies to pipes containing hot water. [F31, F81-OS3.2] Applies to pressure vessels containing hot water. [F81-OS3.2] [F32-OS3.3] [F40, F80-OS3.4] [F43-OS3.4] Applies to equipment. [F44-OS3.4] [F81-OS3.4] [F36-OS3.6] [F40-OR1] [F130-OR1]
11.4.3.6. Sewage SystemsN/A
(1)[F81, F110, F111-OE] [F81, F111-OE] [F82-OE] [F82, F110-OE] [F82, F111-OE] [F104, F110, F111-OE] [F110-OE] [F110, F111-OE] [F110, F111, F112-OE] [F110, F112-OE] [F111-OE] [F111, F112-OE] [F111, F113-OE] [F112-OE] [F50-OH1.1] [F82-OH2.1] [F82, F111-OH2.1] [F104, F110, F111-OH2.1] [F110-OH2.1] [F110, F111-OH2.1] [F110, F111, F112-OH2.1] [F110, F112-OH2.1] [F111-OH2.1] [F111, F112-OH2.1] [F40-OH2.4] [F42-OH2.5] [F113-OH2.6] [F81, F110, F111-OH5] [F81, F111-OH5] [F82-OH5] [F82, F110-OH5] [F82, F111-OH5] [F104, F110, F111-OH5] [F110-OH5] [F110, F111-OH5] [F110, F111, F112-OH5] [F110, F112-OH5] [F111-OH5] [F111, F112-OH5] [F111, F113-OH5] [F112-OH5] [F101-OH6] [F20-OP2.3] [F81-OP2.6] [F104, F110, F111-OR2] [F20-OS2.1] [F20-OS2.2] [F30-OS3.1]

Table 12 — Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 12 of Division B

Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 12 of Division B
Acceptable SolutionsObjectives and Functional Statements
12.2.1.1. Energy Efficiency DesignN/A
(1)[F131-OR2] [F131-OR1, OR1.2]
(2)[F131-OR2] [F131-OR1, OR1.2]
(3)[F131-OR2] [F131-UR1, OR1.2]
12.2.2.1. Carbon Dioxide EquivalentsN/A
(1)[F131-OR1, OR1.2]
(2)[F131-OR1, OR1.2]
12.2.3.1. Peak Electric DemandN/A
(1)[F131-OR1, OR1.2] [F133-OR2.1]
12.2.4.1. Motion SensorsN/A
(2)[F30-OS3.1] [F10-OS3.7]
(3)[F30-OS3.1] [F10-OS3.7]
12.3.1.2. Windows and Sliding Glass DoorsN/A
(1)[F131-OR1.2]
12.3.1.3. Temperature Control in Houses and Dwelling UnitsN/A
(1)[F131-OR1.2]
(2)(a) [F131-OR1.2] [F133-OR2.1]
(b)[F131-OR1.2] [F133-OR2.1]
(c)[F131-OR1.2] [F133-OR2.1]
(3)[F131-OR1.2] [F132-OR2.1]
12.3.1.4. Hot Water Piping InsulationN/A
(1)[F131-OR1.2] [F132-OR2.1]
(2)[F131-OR1.2] [F132-OR2.1]
(3)[F131-OR1.2] [F132-OR2.1]
12.3.1.5. Residential FurnacesN/A
(1)[F131-OR1.2] [F132-OR2.1] [F150-OE1.1]
12.3.1.6. Energy Supply for Kitchen and Laundry FacilitiesN/A
(1)[F131-OR1.2]