Section 1 General

1.1. Scope

1.1.1. Application

  1. This Section applies to farm buildings of low human occupancy.

1.1.2. Construction Requirements

  1. The construction of farm buildings of low human occupancy shall, subject to Article 2.1.3.5. in Division B of the Building Code, conform to the requirements of Part 9 of Division B of the Building Code except as provided in this Section.

1.2. Lumber

1.2.1. Lumber Requirements

  1. Except as permitted by Article 1.2.2. , lumber shall conform to appropriate requirements in Subsection 9.3.2. of Division B of the Building Code.

1.2.2. Ungraded Lumber

  1. Ungraded lumber may be used for wood posts, joists, rafters, lintels, beams and wall studs in a farm building of low human occupancy of not more than one storey in building height.
  1. Ungraded lumber means lumber that has not been grade-stamped to indicate its grade, as determined by the NLGA "Standard Grading Rules for Canadian Lumber (Interpretation Included)", but that meets the following visual attributes:
  1. it is rough sawn to full nominal size,
  1. it has no evidence of decay,
  1. it has no tight knots that exceed 25 percent of the cross section and that are spaced closer than 150 mm on centres,
  1. it has no loose knots or holes that exceed 25 percent of the cross section and that are spaced closer than 600 mm on centres,
  1. it has the slope of grain not exceeding 1 (vertical) in 4 (horizontal), and
  1. it is free of excessive warp.

1.3. Structural Requirements

1.3.1. Structural Design

  1. Except as provided in Articles 1.3.2. to 1.3.4. , wood posts, joists, rafters, lintels, beams and wall studs shall be designed in conformance with Section 9.4. of Division B of the Building Code.

1.3.2. Posts

  1. In a farm building of low human occupancy, the size of wood posts shall conform to Tables 1.3.2.A. to 1.3.2.J. for the loads shown in the Tables.

1.3.3. Spans

  1. In a farm building of low human occupancy, the spans of wood joists, rafters, lintels and beams shall conform to the spans shown in Tables 1.3.3.K. to 1.3.3.T. for the loads shown in the Tables.

1.3.4. Stud Size and Spacing

  1. In a farm building of low human occupancy, the size and spacing of wood studs shall conform to Tables 1.3.4.U. to 1.3.4.W. for the loads shown in the Tables.

Table 1.3.2.A. Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.2.(1)

Table 1.3.2.A. Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy for Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades), For Wind Loading q10 ≤ 0.30 kPa
Building Width, mWall Height, mPost Spacing, 2.4 m Roof Load, 1.4 kPaPost Spacing, 2.4 m Roof Load, 1.9 kPaPost Spacing, 2.4 m Roof Load, 2.4 kPaPost Spacing, 2.4 m Roof Load, 2.8 kPaPost Spacing, 2.4 m Roof Load, 3.3 kPaPost Spacing, 3.6 m Roof Load, 1.4 kPaPost Spacing, 3.6 m Roof Load, 1.9 kPaPost Spacing, 3.6 m Roof Load, 2.4 kPaPost Spacing, 3.6 m Roof Load, 2.8 kPaPost Spacing, 3.6 m Roof Load, 3.3 kPaPost Spacing, 4.8 m Roof Load, 1.4 kPaPost Spacing, 4.8 m Roof Load, 1.9 kPaPost Spacing, 4.8 m Roof Load, 2.4 kPaPost Spacing, 4.8 m Roof Load, 2.8 kPaPost Spacing, 4.8 m Roof Load, 3.3 kPa
9.14≤3.0AAAAAAAAAAAABBB
9.143.6AAAAAAABBBBBBCC
9.144.2BBBBBBBBCCBCCCC
9.144.8BBBBBBCCCCCCCCC
9.146.0CCCCCCCCDDCDDN/AN/A
12.1≤3.0AAAAAAAABBABBBC
12.13.6AAAABABBBCBBCCC
12.14.2BBBBBBBCCCCCCCC
12.14.8BBBCCCCCCCCCDDD
12.16.0CCCCCCCDDN/ADDN/AN/AN/A
15.2≤3.0AAAAAAABBBBBBCC
15.23.6AAABBBBBCCBCCCC
15.24.2BBBBCBCCCCCCCDD
15.24.8BBCCCCCCCDCCDDN/A
15.26.0CCCCDCDDN/AN/ADN/AN/AN/AN/A
18.2≤3.0AAABBABBBCBBCCC
18.23.6AABBBBBCCCCCCCD
18.24.2BBBCCCCCCCCCDDD
18.24.8BCCCCCCCDDCDDN/AN/A
18.26.0CCCDDDDN/AN/AN/AN/AN/AN/AN/AN/A
Column 1234567891011121314151617

Legend - Post Sizes: A = 89 mm x 140 mm · B = 140 mm x 140 mm · C = 140 mm x 184 mm · D = 184 mm x 184 mm

Notes to Table 1.3.2.A.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. Posts shall be oriented with the long dimension parallel to the building width.
  3. Bracing systems shall be specified by a competent designer.
  4. Posts shall be situated on footings and shall be anchored to prevent wind uplift.
  5. Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor help to meet this condition.
  6. Post designs are based on partial fixity condition due to embedment in soil.
  7. Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.

Table 1.3.2.B. Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.2.(1)

Table 1.3.2.B. Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy for Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades), For Wind Loading q10 ≤ 0.45 kPa
Building Width, mWall Height, mPost Spacing, 2.4 m Roof Load, 1.4 kPaPost Spacing, 2.4 m Roof Load, 1.9 kPaPost Spacing, 2.4 m Roof Load, 2.4 kPaPost Spacing, 2.4 m Roof Load, 2.8 kPaPost Spacing, 2.4 m Roof Load, 3.3 kPaPost Spacing, 3.6 m Roof Load, 1.4 kPaPost Spacing, 3.6 m Roof Load, 1.9 kPaPost Spacing, 3.6 m Roof Load, 2.4 kPaPost Spacing, 3.6 m Roof Load, 2.8 kPaPost Spacing, 3.6 m Roof Load, 3.3 kPaPost Spacing, 4.8 m Roof Load, 1.4 kPaPost Spacing, 4.8 m Roof Load, 1.9 kPaPost Spacing, 4.8 m Roof Load, 2.4 kPaPost Spacing, 4.8 m Roof Load, 2.8 kPaPost Spacing, 4.8 m Roof Load, 3.3 kPa
9.14≤3.0AAAAAAAAABABBBB
9.143.6AAAAAABBBBBBCCC
9.144.2BBBBBBBCCCCCCCC
9.144.8BBBCCCCCCCCCCDD
9.146.0CCCCCCDDDDDN/AN/AN/AN/A
12.1≤3.0AAAAAAABBBBBBCC
12.13.6AAABBBBBCCCCCCC
12.14.2BBBBCCCCCCCCCCD
12.14.8BCCCCCCCCCCDDDN/A
12.16.0CCCCDDDDN/AN/AN/AN/AN/AN/AN/A
15.2≤3.0AAAABABBBCBBCCC
15.23.6AABBBBBCCCCCCCD
15.24.2BBBCCCCCCCCCDDD
15.24.8BCCCCCCCDDCDDN/AN/A
15.26.0CCCDDDDN/AN/AN/AN/AN/AN/AN/AN/A
18.2≤3.0AAABBBBBCCBCCCC
18.23.6ABBBCBCCCCCCCDD
18.24.2BBCCCCCCCDCDDDN/A
18.24.8CCCCCCCDDN/ADDN/AN/AN/A
18.26.0CCDDN/ADN/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 1234567891011121314151617

Legend - Post Sizes: A = 89 mm x 140 mm · B = 140 mm x 140 mm · C = 140 mm x 184 mm · D = 184 mm x 184 mm

Notes to Table 1.3.2.B.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. Posts shall be oriented with the long dimension parallel to the building width.
  3. Bracing systems shall be specified by a competent designer.
  4. Posts shall be situated on footings and shall be anchored to prevent wind uplift.
  5. Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor help to meet this condition.
  6. Post designs are based on partial fixity condition due to embedment in soil.
  7. Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.

Table 1.3.2.C. Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.2.(1)

Table 1.3.2.C. Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy for Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades), For Wind Loading q10 ≤ 0.30 kPa
Building Width, mWall Height, mPost Spacing, 2.4 m Roof Load, 1.4 kPaPost Spacing, 2.4 m Roof Load, 1.9 kPaPost Spacing, 2.4 m Roof Load, 2.4 kPaPost Spacing, 2.4 m Roof Load, 2.8 kPaPost Spacing, 2.4 m Roof Load, 3.3 kPaPost Spacing, 3.6 m Roof Load, 1.4 kPaPost Spacing, 3.6 m Roof Load, 1.9 kPaPost Spacing, 3.6 m Roof Load, 2.4 kPaPost Spacing, 3.6 m Roof Load, 2.8 kPaPost Spacing, 3.6 m Roof Load, 3.3 kPaPost Spacing, 4.8 m Roof Load, 1.4 kPaPost Spacing, 4.8 m Roof Load, 1.9 kPaPost Spacing, 4.8 m Roof Load, 2.4 kPaPost Spacing, 4.8 m Roof Load, 2.8 kPaPost Spacing, 4.8 m Roof Load, 3.3 kPa
9.14≤3.0AAAAAAAABBABBBC
9.143.6AAAABABBBCBCCCC
9.144.2BBBBBBCCCCCCCCC
9.144.8CCCCCCCCCCCCCDD
9.146.0CCCCCCDDDN/ADN/AN/AN/AN/A
12.1≤3.0AAAAAABBBBBBCCC
12.13.6AABBBBBCCCCCCCC
12.14.2BBBCCCCCCCCCCDD
12.14.8CCCCCCCCDDCDDN/AN/A
12.16.0CCCDDDDN/AN/AN/AN/AN/AN/AN/AN/A
15.2≤3.0AAABBABBCCBCCCC
15.23.6ABBBCBCCCCCCCCD
15.24.2BBCCCCCCDCCDDN/AN/A
15.24.8CCCCCCCDDN/ADDN/AN/AN/A
15.26.0CCDDN/ADN/AN/AN/AN/AN/AN/AN/AN/AN/A
18.2≤3.0AABBBBCCCCBCCCD
18.23.6BBBCCCCCCCCCCDD
18.24.2BCCCCCCDDCDDN/AN/AN/A
18.24.8CCCDCDDN/AN/ADN/AN/AN/AN/AN/A
18.26.0CDDN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 1234567891011121314151617

Legend - Post Sizes: A = 89 mm x 140 mm · B = 140 mm x 140 mm · C = 140 mm x 184 mm · D = 184 mm x 184 mm

Notes to Table 1.3.2.C.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. Posts shall be oriented with the long dimension parallel to the building width.
  3. Bracing systems shall be specified by a competent designer.
  4. Posts shall be situated on footings and shall be anchored to prevent wind uplift.
  5. Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor help to meet this condition.
  6. Post designs are based on partial fixity condition due to embedment in soil.
  7. Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.

Table 1.3.2.D. Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.2.(1)

Table 1.3.2.D. Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy for Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades), For Wind Loading q10 ≤ 0.45 kPa
Building Width, mWall Height, mPost Spacing, 2.4 m Roof Load, 1.4 kPaPost Spacing, 2.4 m Roof Load, 1.9 kPaPost Spacing, 2.4 m Roof Load, 2.4 kPaPost Spacing, 2.4 m Roof Load, 2.8 kPaPost Spacing, 2.4 m Roof Load, 3.3 kPaPost Spacing, 3.6 m Roof Load, 1.4 kPaPost Spacing, 3.6 m Roof Load, 1.9 kPaPost Spacing, 3.6 m Roof Load, 2.4 kPaPost Spacing, 3.6 m Roof Load, 2.8 kPaPost Spacing, 3.6 m Roof Load, 3.3 kPaPost Spacing, 4.8 m Roof Load, 1.4 kPaPost Spacing, 4.8 m Roof Load, 1.9 kPaPost Spacing, 4.8 m Roof Load, 2.4 kPaPost Spacing, 4.8 m Roof Load, 2.8 kPaPost Spacing, 4.8 m Roof Load, 3.3 kPa
9.14≤3.0AAAAAABBBBBBCCC
9.143.6AAABBBBCCCCCCCC
9.144.2BBBBCCCCCCCCCCD
9.144.8CCCCCCCCDCDDDN/AN/A
9.146.0CCCCDDDN/AN/AN/AN/AN/AN/AN/AN/A
12.1≤3.0AAAABABBBCBBCCC
12.13.6BBBBBBCCCCCCCCC
12.14.2BBCCCCCCCCCCDDD
12.14.8CCCCCCCDDDDDN/AN/AN/A
12.16.0CCDDDDN/AN/AN/AN/AN/AN/AN/AN/AN/A
15.2≤3.0AABBBBBCCBCCCCC
15.23.6ABBCCCCCCCCCCDD
15.24.2BCCCCCCDDCDDN/AN/AN/A
15.24.8CCCCCCDDDN/ADN/AN/AN/AN/A
15.26.0CDDN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
18.2≤3.0AABBBBCCCCCCCCD
18.23.6BBCCCCCCDCCDDN/AN/A
18.24.2CCCCCCDDDDDN/AN/AN/AN/A
18.24.8CCCDDCDN/AN/AN/ADN/AN/AN/AN/A
18.26.0DDN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 1234567891011121314151617

Legend - Post Sizes: A = 89 mm x 140 mm · B = 140 mm x 140 mm · C = 140 mm x 184 mm · D = 184 mm x 184 mm

Notes to Table 1.3.2.D.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. Posts shall be oriented with the long dimension parallel to the building width.
  3. Bracing systems shall be specified by a competent designer.
  4. Posts shall be situated on footings and shall be anchored to prevent wind uplift.
  5. Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor help to meet this condition.
  6. Post designs are based on partial fixity condition due to embedment in soil.
  7. Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.

Table 1.3.2.E. Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.2.(1)

Table 1.3.2.E. Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy for Ungraded Lumber, Full-Dimensioned, For Wind Loading q10 ≤ 0.30 kPa
Building Width, mWall Height, mPost Spacing, 2.4 m Roof Load, 1.4 kPaPost Spacing, 2.4 m Roof Load, 1.9 kPaPost Spacing, 2.4 m Roof Load, 2.4 kPaPost Spacing, 2.4 m Roof Load, 2.8 kPaPost Spacing, 2.4 m Roof Load, 3.3 kPaPost Spacing, 3.6 m Roof Load, 1.4 kPaPost Spacing, 3.6 m Roof Load, 1.9 kPaPost Spacing, 3.6 m Roof Load, 2.4 kPaPost Spacing, 3.6 m Roof Load, 2.8 kPaPost Spacing, 3.6 m Roof Load, 3.3 kPaPost Spacing, 4.8 m Roof Load, 1.4 kPaPost Spacing, 4.8 m Roof Load, 1.9 kPaPost Spacing, 4.8 m Roof Load, 2.4 kPaPost Spacing, 4.8 m Roof Load, 2.8 kPaPost Spacing, 4.8 m Roof Load, 3.3 kPa
9.14≤3.0AAAAAAAABBABBCC
9.143.6AAAABABBBCBCCCC
9.144.2BBBBBBBCCCCCCCD
9.144.8BBBBCCCCCCCCCDD
9.146.0CCCCCCCDDDDDN/AN/AN/A
12.1≤3.0AAAABABBBCBBCCC
12.13.6AABBBBBCCCCCCCD
12.14.2BBBBCBCCCCCCDDD
12.14.8BBCCCCCCDCDDDN/AN/A
12.16.0CCCCDCDDN/AN/ADN/AN/AN/AN/A
15.2≤3.0AAABBBBCCCBCCDD
15.23.6ABBBCBCCCCCCDDD
15.24.2BBCCCCCCDDCDDN/AN/A
15.24.8BCCCCCCDDDDDN/AN/AN/A
15.26.0CCCDDDDN/AN/AN/AN/AN/AN/AN/AN/A
18.2≤3.0AABBCBBCCDCCDDN/A
18.23.6ABBCCCCCDDCDDN/AN/A
18.24.2BCCCCCCDDDCDN/AN/AN/A
18.24.8CCCCDCDDN/AN/ADN/AN/AN/AN/A
18.26.0CCDDN/ADN/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 1234567891011121314151617

Legend - Post Sizes: A = 101.6 mm x 152.4 mm · B = 152.4 mm x 152.4 mm · C = 152.4 mm x 203.2 mm · D = 203.2 mm x 203.2 mm

Notes to Table 1.3.2.E.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. Posts shall be oriented with the long dimension parallel to the building width.
  3. Bracing systems shall be specified by a competent designer.
  4. Posts shall be situated on footings and shall be anchored to prevent wind uplift.
  5. Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor help to meet this condition.
  6. Post designs are based on partial fixity condition due to embedment in soil.
  7. Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.

Table 1.3.2.F. Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.2.(1)

Table 1.3.2.F. Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy for Ungraded Lumber, Full-Dimensioned, For Wind Loading q10 ≤ 0.45 kPa
Building Width, mWall Height, mPost Spacing, 2.4 m Roof Load, 1.4 kPaPost Spacing, 2.4 m Roof Load, 1.9 kPaPost Spacing, 2.4 m Roof Load, 2.4 kPaPost Spacing, 2.4 m Roof Load, 2.8 kPaPost Spacing, 2.4 m Roof Load, 3.3 kPaPost Spacing, 3.6 m Roof Load, 1.4 kPaPost Spacing, 3.6 m Roof Load, 1.9 kPaPost Spacing, 3.6 m Roof Load, 2.4 kPaPost Spacing, 3.6 m Roof Load, 2.8 kPaPost Spacing, 3.6 m Roof Load, 3.3 kPaPost Spacing, 4.8 m Roof Load, 1.4 kPaPost Spacing, 4.8 m Roof Load, 1.9 kPaPost Spacing, 4.8 m Roof Load, 2.4 kPaPost Spacing, 4.8 m Roof Load, 2.8 kPaPost Spacing, 4.8 m Roof Load, 3.3 kPa
9.14≤3.0AAAABABBBCBCCCC
9.143.6AABBBBBCCCCCCDD
9.144.2BBBCCCCCCDCCDDD
9.144.8BBCCCCCDDDDDDN/AN/A
9.146.0CCCDDDDN/AN/AN/AN/AN/AN/AN/AN/A
12.1≤3.0AAABBABBCCBCCCD
12.13.6ABBBCBCCCCCCCDD
12.14.2BBCCCCCDDCDDDN/AN/A
12.14.8BCCCCCDDDDDDN/AN/AN/A
12.16.0CCDDDDN/AN/AN/AN/AN/AN/AN/AN/AN/A
15.2≤3.0AABBCBCCCDCCDDD
15.23.6ABBCCCCDDDCDDDN/A
15.24.2BCCCCCDDDDDDN/AN/AN/A
15.24.8CCCCDCDDDN/ADN/AN/AN/AN/A
15.26.0CCDDN/ADN/AN/AN/AN/AN/AN/AN/AN/AN/A
18.2≤3.0ABBCCBCCDDCDDN/AN/A
18.23.6BBCCCCCDDDDDN/AN/AN/A
18.24.2CCCCDCDDDDDN/AN/AN/AN/A
18.24.8CCCDDDDN/AN/AN/ADN/AN/AN/AN/A
18.26.0CDDN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 1234567891011121314151617

Legend - Post Sizes: A = 101.6 mm x 152.4 mm · B = 152.4 mm x 152.4 mm · C = 152.4 mm x 203.2 mm · D = 203.2 mm x 203.2 mm

Notes to Table 1.3.2.F.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. Posts shall be oriented with the long dimension parallel to the building width.
  3. Bracing systems shall be specified by a competent designer.
  4. Posts shall be situated on footings and shall be anchored to prevent wind uplift.
  5. Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor help to meet this condition.
  6. Post designs are based on partial fixity condition due to embedment in soil.
  7. Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.

Table 1.3.2.G. Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.2.(1)

Table 1.3.2.G. Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy for Ungraded Lumber, Full-Dimensioned, For Wind Loading q10 ≤ 0.30 kPa
Building Width, mWall Height, mPost Spacing, 2.4 m Roof Load, 1.4 kPaPost Spacing, 2.4 m Roof Load, 1.9 kPaPost Spacing, 2.4 m Roof Load, 2.4 kPaPost Spacing, 2.4 m Roof Load, 2.8 kPaPost Spacing, 2.4 m Roof Load, 3.3 kPaPost Spacing, 3.6 m Roof Load, 1.4 kPaPost Spacing, 3.6 m Roof Load, 1.9 kPaPost Spacing, 3.6 m Roof Load, 2.4 kPaPost Spacing, 3.6 m Roof Load, 2.8 kPaPost Spacing, 3.6 m Roof Load, 3.3 kPaPost Spacing, 4.8 m Roof Load, 1.4 kPaPost Spacing, 4.8 m Roof Load, 1.9 kPaPost Spacing, 4.8 m Roof Load, 2.4 kPaPost Spacing, 4.8 m Roof Load, 2.8 kPaPost Spacing, 4.8 m Roof Load, 3.3 kPa
9.14≤3.0AAABBABBBCBCCCD
9.143.6ABBBCBCCCCCCDDD
9.144.2BBCCCCCDDCDDDN/AN/A
9.144.8CCCCCCDDDDDDN/AN/AN/A
9.146.0CCDDDDN/AN/AN/AN/AN/AN/AN/AN/AN/A
12.1≤3.0AABBCBCCCDCCDDD
12.13.6ABBCCCCDDDCDDDN/A
12.14.2BCCCCCDDDDDDN/AN/AN/A
12.14.8CCCCDCDDDN/ADN/AN/AN/AN/A
12.16.0CCDDN/ADN/AN/AN/AN/AN/AN/AN/AN/AN/A
15.2≤3.0ABBCCBCCDDCDDN/AN/A
15.23.6BBCCCCCDDDDDN/AN/AN/A
15.24.2BCCCDCDDDDDN/AN/AN/AN/A
15.24.8CCCDDDDN/AN/AN/ADN/AN/AN/AN/A
15.26.0CDDN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
18.2≤3.0ABBCCCCDDDCDDN/AN/A
18.23.6BCCCCCDDDDDDN/AN/AN/A
18.24.2CCCDDCDDDDDN/AN/AN/AN/A
18.24.8CCDDDDDN/AN/AN/ADN/AN/AN/AN/A
18.26.0CDDN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 1234567891011121314151617

Legend - Post Sizes: A = 101.6 mm x 152.4 mm · B = 152.4 mm x 152.4 mm · C = 152.4 mm x 203.2 mm · D = 203.2 mm x 203.2 mm

Notes to Table 1.3.2.G.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. Posts shall be oriented with the long dimension parallel to the building width.
  3. Bracing systems shall be specified by a competent designer.
  4. Posts shall be situated on footings and shall be anchored to prevent wind uplift.
  5. Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor help to meet this condition.
  6. Post designs are based on partial fixity condition due to embedment in soil.
  7. Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.

Table 1.3.2.H. Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.2.(1)

Table 1.3.2.H. Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy for Ungraded Lumber, Full-Dimensioned, For Wind Loading q10 ≤ 0.45 kPa
Building Width, mWall Height, mPost Spacing, 2.4 m Roof Load, 1.4 kPaPost Spacing, 2.4 m Roof Load, 1.9 kPaPost Spacing, 2.4 m Roof Load, 2.4 kPaPost Spacing, 2.4 m Roof Load, 2.8 kPaPost Spacing, 2.4 m Roof Load, 3.3 kPaPost Spacing, 3.6 m Roof Load, 1.4 kPaPost Spacing, 3.6 m Roof Load, 1.9 kPaPost Spacing, 3.6 m Roof Load, 2.4 kPaPost Spacing, 3.6 m Roof Load, 2.8 kPaPost Spacing, 3.6 m Roof Load, 3.3 kPaPost Spacing, 4.8 m Roof Load, 1.4 kPaPost Spacing, 4.8 m Roof Load, 1.9 kPaPost Spacing, 4.8 m Roof Load, 2.4 kPaPost Spacing, 4.8 m Roof Load, 2.8 kPaPost Spacing, 4.8 m Roof Load, 3.3 kPa
9.14≤3.0AAAABABBBCBCCCC
9.143.6AABBBBCCCCCCCCD
9.144.2BBBCCCCCCCCCDDD
9.144.8CCCCCCCDDDDDDN/AN/A
9.146.0CCCDDDDN/AN/AN/AN/AN/AN/AN/AN/A
12.1≤3.0AABBBBBCCCCCCCD
12.13.6ABBCCCCCCCCCDDD
12.14.2BCCCCCCDDCDDN/AN/AN/A
12.14.8CCCCCCDDDN/ADN/AN/AN/AN/A
12.16.0CDDDN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
15.2≤3.0ABBBCBCCCCCCDDD
15.23.6BBCCCCCDDCDDN/AN/AN/A
15.24.2CCCCCCDDN/ADDN/AN/AN/AN/A
15.24.8CCCDDDDN/AN/AN/AN/AN/AN/AN/AN/A
15.26.0DDDN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
18.2≤3.0ABBCCCCCDDCDDN/AN/A
18.23.6BCCCCCDDN/ADDN/AN/AN/AN/A
18.24.2CCCCCCDDN/ADDN/AN/AN/AN/A
18.24.8CCCCDCDDN/AN/ADN/AN/AN/AN/A
18.26.0CCDDDDN/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 1234567891011121314151617

Legend - Post Sizes: A = 101.6 mm x 152.4 mm · B = 152.4 mm x 152.4 mm · C = 152.4 mm x 203.2 mm · D = 203.2 mm x 203.2 mm

Notes to Table 1.3.2.H.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. Posts shall be oriented with the long dimension parallel to the building width.
  3. Bracing systems shall be specified by a competent designer.
  4. Posts shall be situated on footings and shall be anchored to prevent wind uplift.
  5. Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor help to meet this condition.
  6. Post designs are based on partial fixity condition due to embedment in soil.
  7. Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.

Table 1.3.2.I. Post Sizes for Farm Buildings of Low Human Occupancy (With Second Storey Loading)

Forming Part of Sentence 1.3.2.(1)

Table 1.3.2.I. Post Sizes for Farm Buildings of Low Human Occupancy (With Second Storey Loading) for Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades), For Wind Loading q10 ≤ 0.30 kPa and q10 ≤ 0.45 kPa
Sidewall Height, mTotal Roof Load, kPa2.4 m o.c. Building Width, 9.14 m2.4 m o.c. Building Width, 12.2 m2.4 m o.c. Building Width, 15.2 m2.4 m o.c. Building Width, 18.3 m3.6 m o.c. Building Width, 9.14 m3.6 m o.c. Building Width, 12.2 m3.6 m o.c. Building Width, 15.2 m3.6 m o.c. Building Width, 18.3 m2.4 m o.c. Building Width, 9.14 m2.4 m o.c. Building Width, 12.2 m2.4 m o.c. Building Width, 15.2 m2.4 m o.c. Building Width, 18.3 m3.6 m o.c. Building Width, 9.14 m3.6 m o.c. Building Width, 12.2 m3.6 m o.c. Building Width, 15.2 m3.6 m o.c. Building Width, 18.3 mSecond Storey Plate, kN/m
3.01.9AAAAAAABAAAAAABB14.6
3.02.4AAAAABBBAAAABBBB14.6
3.02.8AAABBBBBAABBBBBC14.6
3.03.3AABBBBCCABBBBBCC14.6
3.61.9AAAAABBBAAABBBBC14.6
3.62.4AABBBBBCABBBBCCC14.6
3.62.8ABBBBCCCBBBBCCCC14.6
3.63.3BBBCCCCCBBBCCCCC14.6
3.01.9AAAAAAABAAAAAABB7.3
3.02.4AAAAAABBAAAAABBB7.3
3.02.8AAABBBBBAAABBBBC7.3
3.03.3AABBBBBCAABBBBCC7.3
3.61.9AAAAABBBAAABBBBC7.3
3.62.4AAABBBBCABBBBBCC7.3
3.62.8ABBBBCCCBBBBCCCC7.3
3.63.3BBBBBCCCBBBCCCCC7.3
3.01.9AAAAAAAAAAAAAABB3.6
3.02.4AAAAAABBAAAAABBB3.6
3.02.8AAAAABBBAAABBBBC3.6
3.03.3AABBBBBCAABBBBCC3.6
3.61.9AAAAABBBAAAABBBB3.6
3.62.4AAABBBBCAABBBBCC3.6
3.62.8ABBBBBCCABBBBCCC3.6
3.63.3BBBBBCCCBBBCCCCC3.6
Column 12345678910111213141516171819

Legend - Post Sizes: A = 89 mm x 140 mm · B = 140 mm x 140 mm · C = 140 mm x 184 mm

Notes to Table 1.3.2.I.:

  1. Designs are based on load combinations of total roof load, wind load and stored product acting at the same time on a closed building.
  2. All notes following Table 1.3.2.A. apply, with the following conditions/exceptions:
  • 14.6 kN/m loading: Full 4.8 m sidewall hay/straw storage space above. It is supported by beams spaced at 3.6 m o.c. The outside plate carries a 1.8 m floor width. If the loading is greater, refer to a qualified person for design.
  • 7.3 kN/m loading: Full 2.4 m sidewall hay/straw storage space above or a gambrel roof structure > 9.14 m in total width. Floor support beams as above.
  • 3.6 kN/m loading: Small gambrel roof structure or storage space for light storage. Floor support beams as above.

Table 1.3.2.J. Round Posts

Table 1.3.2.J. Round Posts — Forming Part of Sentence 1.3.2.(1)
Ungraded Lumber Full-dimension Size, mmEquivalent Diameter Full Size, mm
50.8 x 101.6101.6
50.8 x 152.4127.0
50.8 x 203.2152.4
50.8 x 254.0177.8
50.8 x 304.8203.2
76.2 x 304.8228.6
76.2 x 355.6254.0
101.6 x 152.4158.8
101.6 x 304.8203.2
101.6 x 355.6279.4
127.0 x 203.2209.6
127.0 x 254.0241.3
152.4 x 152.4190.5
152.4 x 203.2222.3
152.4 x 254.0260.4
203.2 x 203.2247.7
203.2 x 254.0285.8
203.2 x 304.8317.5
254.0 x 304.8342.9
254.0 x 355.6381.0
Column 12

Notes to Table 1.3.2.J.:

  1. When selecting round, ungraded lumber, ensure that the material is of good quality.
  2. Any timber that is in contact with ground shall be chemically treated to resist growth of fungus and decay.
  3. Equivalent diameter indicated in this Table refers to the smallest diameter of a tapering pole.
  4. Used hydro or telephone poles may be used if they are of good quality and are chemically treated to prevent decay.
  5. Indicated equivalent diameter will provide bending, shear and deflection resisting capabilities equal to or better than the rectangular section that it replaces.

Table 1.3.3.K. Common Rafter Sizes for Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.3.(1)

Table 1.3.3.K — Common Rafter Sizes for Farm Buildings of Low Human Occupancy, Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 305 mm Rafter Spacing
Rafter Span, mLive Load, 1.4 kPaLive Load, 1.9 kPaLive Load, 2.4 kPaLive Load, 2.8 kPaLive Load, 3.3 kPa
2.4AABBB
3.0BBBBB
3.6BBCCC
4.2BCCCC
4.8CCDDD
5.4CDDDE
6.0DDDEN/A
Column 123456
Table 1.3.3.K — Common Rafter Sizes for Farm Buildings of Low Human Occupancy, Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 406 mm Rafter Spacing
Rafter Span, mLive Load, 1.4 kPaLive Load, 1.9 kPaLive Load, 2.4 kPaLive Load, 2.8 kPaLive Load, 3.3 kPa
2.4ABBBB
3.0BBBBC
3.6BCCCC
4.2CCCDD
4.8CDDEE
5.4DDEEN/A
6.0DEEN/AN/A
Column 123456
Table 1.3.3.K — Common Rafter Sizes for Farm Buildings of Low Human Occupancy, Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 610 mm Rafter Spacing
Rafter Span, mLive Load, 1.4 kPaLive Load, 1.9 kPaLive Load, 2.4 kPaLive Load, 2.8 kPaLive Load, 3.3 kPa
2.4BBBBB
3.0BBCCD
3.6CCDDD
4.2CDDEE
4.8DEEN/AN/A
5.4EEN/AN/AN/A
6.0EN/AN/AN/AN/A
Column 123456

Legend - Rafter Sizes: A = 38 mm x 89 mm · B = 38 mm x 140 mm · C = 38 mm x 184 mm · D = 38 mm x 235 mm · E = 38 mm x 286 mm

Notes to Table 1.3.3.K.:

  1. The rafter span is the unsupported length of the rafter from plate to plate or from plate to ridge. A dead load of 0.24 kPa is incorporated to allow for weight of the roof sheathing and rafter.

Table 1.3.3.L. Common Rafter Sizes for Farm Buildings of Low Human Occupancy

Forming Part of Sentence 1.3.3.(1)

Table 1.3.3.L — Common Rafter Sizes for Farm Buildings of Low Human Occupancy, Ungraded Lumber, Full-Dimension, 305 mm Rafter Spacing
Rafter Span, mLive Load, 1.4 kPaLive Load, 1.9 kPaLive Load, 2.4 kPaLive Load, 2.8 kPaLive Load, 3.3 kPa
2.4AABBB
3.0BBBCC
3.6BCCDD
4.2CCDDE
4.8CDEEF
5.4DEFFF
6.0EFFFG
Column 123456
Table 1.3.3.L — Common Rafter Sizes for Farm Buildings of Low Human Occupancy, Ungraded Lumber, Full-Dimension, 406 mm Rafter Spacing
Rafter Span, mLive Load, 1.4 kPaLive Load, 1.9 kPaLive Load, 2.4 kPaLive Load, 2.8 kPaLive Load, 3.3 kPa
2.4BBBBC
3.0BCCCD
3.6CCDDE
4.2DDEEF
4.8DEFFF
5.4EFFFG
6.0FFGGI
Column 123456
Table 1.3.3.L — Common Rafter Sizes for Farm Buildings of Low Human Occupancy, Ungraded Lumber, Full-Dimension, 610 mm Rafter Spacing
Rafter Span, mLive Load, 1.4 kPaLive Load, 1.9 kPaLive Load, 2.4 kPaLive Load, 2.8 kPaLive Load, 3.3 kPa
2.4BBCCD
3.0CCDDE
3.6DDEFF
4.2EFFFG
4.8FFFGI
5.4FGHIN/A
6.0FHIN/AN/A
Column 123456

Legend - Rafter Sizes: A = 50.8 mm x 101.6 mm · B = 50.8 mm x 152.4 mm · C = 50.8 mm x 203.2 mm · D = 50.8 mm x 254.0 mm · E = 50.8 mm x 304.8 mm · F = 76.2 mm x 304.8 mm · G = 76.2 mm x 355.6 mm · H = 101.6 mm x 304.8 mm · I = 101.6 mm x 355.6 mm

Notes to Table 1.3.3.L.:

  1. The rafter span is the unsupported length of the rafter from plate to plate or from plate to ridge. A dead load of 0.24 kPa is incorporated to allow for weight of the roof sheathing and rafter.

Table 1.3.3.M. Floor Joists for Farm Buildings of Low Human Occupancy - Intermittent Loads

Forming Part of Sentence 1.3.3.(1)

Table 1.3.3.M — Floor Joists for Farm Buildings of Low Human Occupancy - Intermittent Loads[1], Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 305 mm Joist Spacing
Joist Span, mLive Load, 1.9 kPaLive Load, 2.8 kPaLive Load, 3.8 kPaLive Load, 4.8 kPaLive Load, 6.7 kPaLive Load, 8.6 kPa
2.4ABBBBC
3.0BBBCCD
3.6BCCCDD
4.2CCDDEE
4.8CDDEN/AN/A
Column 1234567
Table 1.3.3.M — Floor Joists for Farm Buildings of Low Human Occupancy - Intermittent Loads[1], Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 406 mm Joist Spacing
Joist Span, mLive Load, 1.9 kPaLive Load, 2.8 kPaLive Load, 3.8 kPaLive Load, 4.8 kPaLive Load, 6.7 kPaLive Load, 8.6 kPa
2.4BBBBCC
3.0BBCCDD
3.6CCCDEE
4.2CDDEN/AN/A
4.8DDEEN/AN/A
Column 1234567
Table 1.3.3.M — Floor Joists for Farm Buildings of Low Human Occupancy - Intermittent Loads[1], Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 610 mm Joist Spacing
Joist Span, mLive Load, 1.9 kPaLive Load, 2.8 kPaLive Load, 3.8 kPaLive Load, 4.8 kPaLive Load, 6.7 kPaLive Load, 8.6 kPa
2.4BBBCDD
3.0BCCDEN/A
3.6CDDEN/AN/A
4.2DDEN/AN/AN/A
4.8DEN/AN/AN/AN/A
Column 1234567

Legend - Joist Sizes: A = 38 mm x 89 mm · B = 38 mm x 140 mm · C = 38 mm x 184 mm · D = 38 mm x 235 mm · E = 38 mm x 286 mm

Notes to Table 1.3.3.M.:

  1. Loads are applied to the floor intermittently. (When loads are applied for extended periods of time, use Table 1.3.3.N. ).
  2. A dead load of 0.48 kPa is incorporated to allow for the dead weight of the floor system.

Table 1.3.3.N. Floor Joists for Farm Buildings of Low Human Occupancy - Continuous Loads

Forming Part of Sentence 1.3.3.(1)

Table 1.3.3.N — Floor Joists for Farm Buildings of Low Human Occupancy - Continuous Loads[1], Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 305 mm Joist Spacing
Joist Span, mLive Load, 1.9 kPaLive Load, 2.8 kPaLive Load, 3.8 kPaLive Load, 4.8 kPaLive Load, 6.7 kPaLive Load, 8.6 kPa
2.4ABBBCC
3.0BBCCDE
3.6BCDDEN/A
4.2CDDEN/AN/A
4.8DDEN/AN/AN/A
Column 1234567
Table 1.3.3.N — Floor Joists for Farm Buildings of Low Human Occupancy - Continuous Loads[1], Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 406 mm Joist Spacing
Joist Span, mLive Load, 1.9 kPaLive Load, 2.8 kPaLive Load, 3.8 kPaLive Load, 4.8 kPaLive Load, 6.7 kPaLive Load, 8.6 kPa
2.4BBBCDE
3.0BCCDEN/A
3.6CDDEN/AN/A
4.2DEEN/AN/AN/A
4.8DEN/AN/AN/AN/A
Column 1234567
Table 1.3.3.N — Floor Joists for Farm Buildings of Low Human Occupancy - Continuous Loads[1], Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 610 mm Joist Spacing
Joist Span, mLive Load, 1.9 kPaLive Load, 2.8 kPaLive Load, 3.8 kPaLive Load, 4.8 kPaLive Load, 6.7 kPaLive Load, 8.6 kPa
2.4BCCDN/AN/A
3.0CDDEN/AN/A
3.6DEN/AN/AN/AN/A
4.2EN/AN/AN/AN/AN/A
4.8N/AN/AN/AN/AN/AN/A
Column 1234567

Legend - Joist Sizes: A = 38 mm x 89 mm · B = 38 mm x 140 mm · C = 38 mm x 184 mm · D = 38 mm x 235 mm · E = 38 mm x 286 mm

Notes to Table 1.3.3.N.:

  1. For use of floors that support hay, straw, grain or other continuous loads.
  2. A dead load of 0.48 kPa is incorporated to allow for the dead weight of the floor system.

Table 1.3.3.O. Built-up Wood Beam Sizes for Farm Buildings of Low Human Occupancy - Intermittent Loads

Forming Part of Sentence 1.3.3.(1)

Table 1.3.3.O — Built-up Wood Beam Sizes for Farm Buildings of Low Human Occupancy - Intermittent Loads[1], Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Beam Span, mTotal Load on Beam, 5.84 kN/mTotal Load on Beam, 8.76 kN/mTotal Load on Beam, 11.67 kN/mTotal Load on Beam, 14.59 kN/mTotal Load on Beam, 17.51 kN/mTotal Load on Beam, 20.43 kN/mTotal Load on Beam, 23.35 kN/mTotal Load on Beam, 26.27 kN/mTotal Load on Beam, 29.19 kN/mTotal Load on Beam, 32.11 kN/mTotal Load on Beam, 35.03 kN/m
1.8AAABBDDGGJL
2.4AABDEHJLN/AN/AN/A
3.0ACEHJKN/AN/AN/AN/AN/A
3.6CHJLN/AN/AN/AN/AN/AN/AN/A
4.2EJLN/AN/AN/AN/AN/AN/AN/AN/A
4.8ILN/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 123456789101112

Legend - Beam Sizes: A = 3 - 38 mm x 184 mm · B = 4 - 38 mm x 184 mm · C = 3 - 38 mm x 235 mm · D = 5 - 38 mm x 184 mm · E = 3 - 38 mm x 286 mm · F = 4 - 38 mm x 235 mm · G = 6 - 38 mm x 184 mm · H = 5 - 38 mm x 235 mm · I = 4 - 38 mm x 286 mm · J = 6 - 38 mm x 235 mm · K = 5 - 38 mm x 286 mm · L = 6 - 38 mm x 286 mm

Notes to Table 1.3.3.O.:

  1. Loads are applied to the beam intermittently.
  2. A dead load of 0.584 kN/m is assumed for all beams.
  3. Floors systems supporting heavy loads over larger spans will require the use of steel beams or other specialized materials.

Table 1.3.3.P. Built-up Wood Beam Sizes for Farm Buildings of Low Human Occupancy - Continuous Loads

Forming Part of Sentence 1.3.3.(1)

Table 1.3.3.P — Built-up Wood Beam Sizes for Farm Buildings of Low Human Occupancy - Continuous Loads[1], Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Beam Span, mTotal Load on Beam, 5.84 kN/mTotal Load on Beam, 8.76 kN/mTotal Load on Beam, 11.67 kN/mTotal Load on Beam, 14.59 kN/mTotal Load on Beam, 17.51 kN/mTotal Load on Beam, 20.43 kN/mTotal Load on Beam, 23.35 kN/m
1.8AABDGJL
2.4ACEJLN/AN/A
3.0DHJLN/AN/AN/A
3.6HKN/AN/AN/AN/AN/A
4.2KN/AN/AN/AN/AN/AN/A
4.8LN/AN/AN/AN/AN/AN/A
Column 12345678

Legend - Beam Sizes: A = 3 - 38 mm x 184 mm · B = 4 - 38 mm x 184 mm · C = 3 - 38 mm x 235 mm · D = 5 - 38 mm x 184 mm · E = 3 - 38 mm x 286 mm · F = 4 - 38 mm x 235 mm · G = 6 - 38 mm x 184 mm · H = 5 - 38 mm x 235 mm · I = 4 - 38 mm x 286 mm · J = 6 - 38 mm x 235 mm · K = 5 - 38 mm x 286 mm · L = 6 - 38 mm x 286 mm

Notes to Table 1.3.3.P.:

  1. For use of floors that support hay, straw, grain or other continuous loads.
  2. A dead load of 0.48 kPa is assumed for all beams.
  3. Floor systems supporting heavy loads over larger spans will require use of steel beams or other specialized materials.

Table 1.3.3.Q. Ungraded Lumber, Full-Dimension Roof Beam Sizes for Farm Buildings of Low Human Occupancy

Table 1.3.3.Q. Ungraded Lumber, Full-Dimension Roof Beam Sizes for Farm Buildings of Low Human Occupancy[1] — Forming Part of Sentence 1.3.3.(1)
Beam Span, mTotal Load on Built-up Wood Beam, 5.84 kN/mTotal Load on Built-up Wood Beam, 8.76 kN/mTotal Load on Built-up Wood Beam, 11.67 kN/mTotal Load on Built-up Wood Beam, 14.59 kN/mTotal Load on Built-up Wood Beam, 17.51 kN/mTotal Load on Built-up Wood Beam, 20.43 kN/mTotal Load on Built-up Wood Beam, 23.35 kN/mTotal Load on Built-up Wood Beam, 26.27 kN/m
1.8AABCDFGH
2.4BDEHIJN/AN/A
3.0DGIN/AN/AN/AN/AN/A
3.6GJN/AN/AN/AN/AN/AN/A
4.2JN/AN/AN/AN/AN/AN/AN/A
Column 123456789

Legend - Built-up Wood Beam Sizes: A = 3 - 50.8 mm x 203.2 mm · B = 4 - 50.8 mm x 203.2 mm · C = 3 - 50.8 mm x 254.0 mm · D = 5 - 50.8 mm x 203.2 mm · E = 6 - 50.8 mm x 203.2 mm · F = 4 - 50.8 mm x 254.0 mm · G = 5 - 50.8 mm x 254.0 mm · H = 4 - 50.8 mm x 304.8 mm · I = 5 - 50.8 mm x 304.8 mm · J = 6 - 50.8 mm x 304.8 mm

Notes to Table 1.3.3.Q.:

  1. Ungraded lumber, full-dimension, built-up wood beam.
  2. A dead load of 0.584 kN/m is assumed.
  3. Beams are sized for roof load only.

Table 1.3.3.R. Ungraded Lumber, Full-Dimension Roof Beam Sizes for Farm Buildings of Low Human Occupancy

Table 1.3.3.R. Ungraded Lumber, Full-Dimension Roof Beam Sizes for Farm Buildings of Low Human Occupancy[1] — Forming Part of Sentence 1.3.3.(1)
Beam Span, mTotal Load on Sawn Beam, 5.84 kN/mTotal Load on Sawn Beam, 8.76 kN/mTotal Load on Sawn Beam, 11.67 kN/mTotal Load on Sawn Beam, 14.59 kN/mTotal Load on Sawn Beam, 17.51 kN/mTotal Load on Sawn Beam, 20.43 kN/mTotal Load on Sawn Beam, 23.35 kN/mTotal Load on Sawn Beam, 26.27 kN/m
1.8AABCDEFG
2.4ABDDFGN/AN/A
3.0CDEFN/AN/AN/AN/A
3.6DFGN/AN/AN/AN/AN/A
4.2EGN/AN/AN/AN/AN/AN/A
Column 123456789

Legend - Sawn Beam Sizes: A = 127.0 mm x 203.2 mm · B = 127.0 mm x 254.0 mm · C = 152.4 mm x 254.0 mm · D = 203.2 mm x 254.0 mm · E = 203.2 mm x 304.8 mm · F = 254.0 mm x 304.8 mm · G = 254.0 mm x 355.6 mm

Notes to Table 1.3.3.R.:

  1. Ungraded lumber, full-dimension, sawn wood beam.
  2. A dead load of 0.584 kN/m is assumed.
  3. Beams are sized for roof load only.

Table 1.3.3.S. Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy

Table 1.3.3.S — Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy, Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 2.4 m Post Spacing
Building Width, mTotal Roof Load, kPa, ATotal Roof Load, kPa, BTotal Roof Load, kPa, CTotal Roof Load, kPa, DTotal Roof Load, kPa, ETotal Roof Load, kPa, FTotal Roof Load, kPa, GTotal Roof Load, kPa, HTotal Roof Load, kPa, I
7.31.672.773.682.494.115.503.355.557.42
8.51.432.343.162.153.544.742.874.746.36
9.71.242.052.771.863.114.112.534.165.55
10.9N/A1.812.441.672.723.682.253.684.93
12.1N/A1.622.201.482.493.302.013.304.45
13.4N/A1.482.011.342.253.011.813.014.02
14.6N/A1.381.811.242.052.721.672.773.68
15.8N/A1.241.67N/A1.912.531.532.533.40
17.0N/AN/A1.58N/A1.772.341.432.393.16
18.2N/AN/A1.48N/A1.622.201.342.202.96
Column 12345678910
Table 1.3.3.S (continued) — Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy, Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 3.0 m Post Spacing
Building Width, mTotal Roof Load, kPa, ATotal Roof Load, kPa, BTotal Roof Load, kPa, CTotal Roof Load, kPa, DTotal Roof Load, kPa, ETotal Roof Load, kPa, FTotal Roof Load, kPa, GTotal Roof Load, kPa, HTotal Roof Load, kPa, I
7.3N/A1.722.291.532.583.442.103.444.64
8.5N/A1.481.961.342.202.961.772.963.97
9.7N/A1.291.72N/A1.912.581.582.583.44
10.9N/AN/A1.53N/A1.722.291.382.293.06
12.1N/AN/A1.38N/A1.532.051.242.052.77
13.4N/AN/A1.24N/A1.381.86N/A1.862.53
14.6N/AN/AN/AN/A1.291.72N/A1.722.29
15.8N/AN/AN/AN/AN/A1.58N/A1.582.10
17.0N/AN/AN/AN/AN/A1.48N/A1.481.96
18.2N/AN/AN/AN/AN/A1.38N/A1.381.81
Column 12345678910
Table 1.3.3.S (continued) — Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy, Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), 3.6 m Post Spacing
Building Width, mTotal Roof Load, kPa, ATotal Roof Load, kPa, BTotal Roof Load, kPa, CTotal Roof Load, kPa, DTotal Roof Load, kPa, ETotal Roof Load, kPa, FTotal Roof Load, kPa, GTotal Roof Load, kPa, HTotal Roof Load, kPa, I
7.3N/A1.381.811.242.052.721.672.773.68
8.5N/AN/A1.58N/A1.772.341.432.393.16
9.7N/AN/A1.38N/A1.532.051.242.052.77
10.9N/AN/A1.19N/A1.381.81N/A1.812.44
12.1N/AN/AN/AN/A1.241.67N/A1.672.20
13.4N/AN/AN/AN/AN/A1.48N/A1.482.01
14.6N/AN/AN/AN/AN/A1.38N/A1.381.81
15.8N/AN/AN/AN/AN/A1.24N/A1.291.67
17.0N/AN/AN/AN/AN/AN/AN/AN/A1.58
18.2N/AN/AN/AN/AN/AN/AN/AN/A1.48
Column 12345678910

Legend - Roof Plate-Beam and Lintel Sizes: A = 2 - 38 mm x 184 mm · B = 3 - 38 mm x 184 mm · C = 4 - 38 mm x 184 mm · D = 2 - 38 mm x 235 mm · E = 3 - 38 mm x 235 mm · F = 4 - 38 mm x 235 mm · G = 2 - 38 mm x 286 mm · H = 3 - 38 mm x 286 mm · I = 4 - 38 mm x 286 mm

Notes to Table 1.3.3.S.:

  1. Trusses are at 1.2 m on centres.
  2. Plate-beam/lintel loading can be very significant.
  3. Specifications for anchorage at supporting posts must be specified by a competent designer.

Table 1.3.3.T. Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy

Table 1.3.3.T — Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy, Ungraded Lumber-Full Dimension, 2.4 m Post Spacing
Building Width, mTotal Roof Load, kPa, ATotal Roof Load, kPa, BTotal Roof Load, kPa, CTotal Roof Load, kPa, DTotal Roof Load, kPa, ETotal Roof Load, kPa, FTotal Roof Load, kPa, GTotal Roof Load, kPa, HTotal Roof Load, kPa, I
7.3N/A1.722.291.482.443.251.913.204.26
8.5N/A1.431.961.242.102.771.672.723.68
9.7N/A1.291.72N/A1.812.441.432.393.20
10.9N/AN/A1.53N/A1.622.151.292.152.87
12.1N/AN/A1.34N/A1.481.96N/A1.912.58
13.4N/AN/A1.24N/A1.341.77N/A1.722.34
14.6N/AN/AN/AN/A1.191.62N/A1.582.15
15.8N/AN/AN/AN/AN/A1.48N/A1.481.96
17.0N/AN/AN/AN/AN/A1.38N/A1.381.81
18.2N/AN/AN/AN/AN/A1.29N/A1.291.72
Column 12345678910
Table 1.3.3.T (continued) — Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy, Ungraded Lumber-Full Dimension, 3.0 m Post Spacing
Building Width, mTotal Roof Load, kPa, ATotal Roof Load, kPa, BTotal Roof Load, kPa, CTotal Roof Load, kPa, DTotal Roof Load, kPa, ETotal Roof Load, kPa, FTotal Roof Load, kPa, GTotal Roof Load, kPa, HTotal Roof Load, kPa, I
7.3N/AN/A1.43N/A1.532.051.192.012.68
8.5N/AN/A1.19N/A1.291.72N/A1.722.29
9.7N/AN/AN/AN/AN/A1.53N/A1.482.01
10.9N/AN/AN/AN/AN/A1.34N/A1.341.77
12.1N/AN/AN/AN/AN/A1.19N/AN/A1.58
13.4N/AN/AN/AN/AN/AN/AN/AN/A1.43
14.6N/AN/AN/AN/AN/AN/AN/AN/A1.34
15.8N/AN/AN/AN/AN/AN/AN/AN/A1.24
17.0N/AN/AN/AN/AN/AN/AN/AN/AN/A
18.2N/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 12345678910
Table 1.3.3.T (continued) — Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy, Ungraded Lumber-Full Dimension, 3.6 m Post Spacing
Building Width, mTotal Roof Load, kPa, ATotal Roof Load, kPa, BTotal Roof Load, kPa, CTotal Roof Load, kPa, DTotal Roof Load, kPa, ETotal Roof Load, kPa, FTotal Roof Load, kPa, GTotal Roof Load, kPa, HTotal Roof Load, kPa, I
7.3N/AN/AN/AN/A1.191.62N/A1.582.15
8.5N/AN/AN/AN/AN/A1.38N/A1.381.81
9.7N/AN/AN/AN/AN/A1.19N/AN/A1.58
10.9N/AN/AN/AN/AN/AN/AN/AN/A1.43
12.1N/AN/AN/AN/AN/AN/AN/AN/A1.29
13.4N/AN/AN/AN/AN/AN/AN/AN/AN/A
14.6N/AN/AN/AN/AN/AN/AN/AN/AN/A
15.8N/AN/AN/AN/AN/AN/AN/AN/AN/A
17.0N/AN/AN/AN/AN/AN/AN/AN/AN/A
18.2N/AN/AN/AN/AN/AN/AN/AN/AN/A
Column 12345678910

Legend - Roof Plate-Beam and Lintel Sizes: A = 2 - 50.8 mm x 203.2 mm · B = 3 - 50.8 mm x 203.2 mm · C = 4 - 50.8 mm x 203.2 mm · D = 2 - 50.8 mm x 254.0 mm · E = 3 - 50.8 mm x 254.0 mm · F = 4 - 50.8 mm x 254.0 mm · G = 2 - 50.8 mm x 304.8 mm · H = 3 - 50.8 mm x 304.8 mm · I = 4 - 50.8 mm x 304.8 mm

Notes to Table 1.3.3.T.:

  1. Trusses are at 1.2 m on centres.
  2. Plate-beam/lintel loading can be very significant.
  3. Specifications for anchorage at supporting posts must be specified by a competent designer.

Table 1.3.4.U. Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey)

Forming Part of Sentence 1.3.4.(1)

Table 1.3.4.U — Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey), Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), Wind Load: q10 ≤ 0.30 kPa
Sidewall Height, mTotal Roof Load, kPa406 mm o.c. Building Width, 9.14 m406 mm o.c. Building Width, 12.2 m406 mm o.c. Building Width, 15.2 m406 mm o.c. Building Width, 18.3 m
3.01.9AAAA
3.02.4AABB
3.02.8ABBB
3.03.3BBBB
3.61.9ABBB
3.62.4BBBB
3.62.8BBBB
3.63.3BBBB
4.21.9BBBB
4.22.4BBBB
4.22.8BBBB
4.23.3BBBB
4.81.9BBBB
4.82.4BBBB
4.82.8BBBB
4.83.3BBCC
Column 123456
Table 1.3.4.U (continued) — Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey), Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), Wind Load: q10 ≤ 0.30 kPa
Sidewall Height, mTotal Roof Load, kPa610 mm o.c. Building Width, 9.14 m610 mm o.c. Building Width, 12.2 m610 mm o.c. Building Width, 15.2 m610 mm o.c. Building Width, 18.3 m
3.01.9AAAA
3.02.4ABBB
3.02.8BBBB
3.03.3BBBB
3.61.9BBBB
3.62.4BBBB
3.62.8BBBB
3.63.3BBBB
4.21.9BBBB
4.22.4BBBB
4.22.8BBBB
4.23.3BBBB
4.81.9BBBB
4.82.4BBBC
4.82.8BCCC
4.83.3BCCC
Column 123456
Table 1.3.4.U (continued) — Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey), Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), Wind Load: q10 ≤ 0.45 kPa
Sidewall Height, mTotal Roof Load, kPa406 mm o.c. Building Width, 9.14 m406 mm o.c. Building Width, 12.2 m406 mm o.c. Building Width, 15.2 m406 mm o.c. Building Width, 18.3 m
3.01.9AAAA
3.02.4AAAB
3.02.8AABB
3.03.3BBBB
3.61.9BBBB
3.62.4BBBB
3.62.8BBBB
3.63.3BBBB
4.21.9BBBB
4.22.4BBBB
4.22.8BBBB
4.23.3BBBB
4.81.9BBBB
4.82.4BBBB
4.82.8BBBB
4.83.3CCCC
Column 123456
Table 1.3.4.U (continued) — Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey), Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), Wind Load: q10 ≤ 0.45 kPa
Sidewall Height, mTotal Roof Load, kPa610 mm o.c. Building Width, 9.14 m610 mm o.c. Building Width, 12.2 m610 mm o.c. Building Width, 15.2 m610 mm o.c. Building Width, 18.3 m
3.01.9AAAB
3.02.4AABB
3.02.8BBBB
3.03.3BBBB
3.61.9BBBB
3.62.4BBBB
3.62.8BBBB
3.63.3BBBB
4.21.9BBBB
4.22.4BBBB
4.22.8BBBB
4.23.3BBBB
4.81.9BBBB
4.82.4BBBB
4.82.8BBCC
4.83.3CCCC
Column 123456

Legend - Stud Sizes: A = 38 mm x 89 mm · B = 38 mm x 140 mm · C = 38 mm x 184 mm or double 38 mm x 140 mm under the trusses, with an intermediate 38 mm x 140 mm stud at 610 mm.

Notes to Table 1.3.4.U.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. It is assumed that the double top plate is rigid enough to cause load sharing amongst all studs regardless of the spacing 406 mm or 610 mm.
  3. Solid bridging shall be used on all walls as follows: ≤ 3.0 m: 1 row at mid-height. 3.6 m - 4.2 m: 2 rows at third-points. 4.8 m: 3 rows at quarter-points.
  4. Wind bracing shall not impose additional bending forces onto the stud.

Table 1.3.4.V. Stud Sizes for Farm Buildings of Low Human Occupancy (With Second Storey Loading)

Forming Part of Sentence 1.3.4.(1)

Table 1.3.4.V — Stud Sizes for Farm Buildings of Low Human Occupancy (With Second Storey Loading), Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), Wind Load: q10 ≤ 0.30 kPa
Sidewall Height, mTotal Roof Load, kPa406 mm o.c. Building Width, 9.14 m406 mm o.c. Building Width, 12.2 m406 mm o.c. Building Width, 15.2 m406 mm o.c. Building Width, 18.3 mSecond Storey Plate, kN/m
3.01.9BBBB14.6
3.02.4BBBB14.6
3.02.8BBBB14.6
3.03.3BBBB14.6
3.61.9BBBB14.6
3.62.4BBBB14.6
3.62.8BBBB14.6
3.63.3BBBB14.6
3.01.9AABB7.3
3.02.4ABBB7.3
3.02.8ABBB7.3
3.03.3BBBB7.3
3.61.9BBBB7.3
3.62.4BBBB7.3
3.62.8BBBB7.3
3.63.3BBBB7.3
3.01.9AAAA3.6
3.02.4AAAB3.6
3.02.8AABB3.6
3.03.3ABBB3.6
3.61.9ABBB3.6
3.62.4BBBB3.6
3.62.8BBBB3.6
3.63.3BBBB3.6
Column 1234567
Table 1.3.4.V (continued) — Stud Sizes for Farm Buildings of Low Human Occupancy (With Second Storey Loading), Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), Wind Load: q10 ≤ 0.30 kPa
Sidewall Height, mTotal Roof Load, kPa610 mm o.c. Building Width, 9.14 m610 mm o.c. Building Width, 12.2 m610 mm o.c. Building Width, 15.2 m610 mm o.c. Building Width, 18.3 mSecond Storey Plate, kN/m
3.01.9BBBB14.6
3.02.4BBBB14.6
3.02.8BBBB14.6
3.03.3BBBB14.6
3.61.9BBBC14.6
3.62.4BBCC14.6
3.62.8BBCC14.6
3.63.3BCCC14.6
3.01.9BBBB7.3
3.02.4BBBB7.3
3.02.8BBBB7.3
3.03.3BBBB7.3
3.61.9BBBB7.3
3.62.4BBBB7.3
3.62.8BBBB7.3
3.63.3BBBB7.3
3.01.9AAAA3.6
3.02.4AABB3.6
3.02.8ABBB3.6
3.03.3BBBC3.6
3.61.9BBBB3.6
3.62.4BBBB3.6
3.62.8BBBB3.6
3.63.3BBBB3.6
Column 1234567
Table 1.3.4.V (continued) — Stud Sizes for Farm Buildings of Low Human Occupancy (With Second Storey Loading), Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), Wind Load: q10 ≤ 0.45 kPa
Sidewall Height, mTotal Roof Load, kPa406 mm o.c. Building Width, 9.14 m406 mm o.c. Building Width, 12.2 m406 mm o.c. Building Width, 15.2 m406 mm o.c. Building Width, 18.3 mSecond Storey Plate, kN/m
3.01.9BBBB14.6
3.02.4BBBB14.6
3.02.8BBBB14.6
3.03.3BBBB14.6
3.61.9BBBB14.6
3.62.4BBBB14.6
3.62.8BBBB14.6
3.63.3BBBB14.6
3.01.9BBBB7.3
3.02.4BBBB7.3
3.02.8BBBB7.3
3.03.3BBBB7.3
3.61.9BBBB7.3
3.62.4BBBB7.3
3.62.8BBBB7.3
3.63.3BBBB7.3
3.01.9AAAA3.6
3.02.4AAAA3.6
3.02.8AABB3.6
3.03.3AABB3.6
3.61.9BBBB3.6
3.62.4BBBB3.6
3.62.8BBBB3.6
3.63.3BBBB3.6
Column 1234567
Table 1.3.4.V (continued) — Stud Sizes for Farm Buildings of Low Human Occupancy (With Second Storey Loading), Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber), Wind Load: q10 ≤ 0.45 kPa
Sidewall Height, mTotal Roof Load, kPa610 mm o.c. Building Width, 9.14 m610 mm o.c. Building Width, 12.2 m610 mm o.c. Building Width, 15.2 m610 mm o.c. Building Width, 18.3 mSecond Storey Plate, kN/m
3.01.9BBBB14.6
3.02.4BBBB14.6
3.02.8BBBB14.6
3.03.3BBBB14.6
3.61.9BBCC14.6
3.62.4BCCC14.6
3.62.8BCCC14.6
3.63.3CCCC14.6
3.01.9BBBB7.3
3.02.4BBBB7.3
3.02.8BBBB7.3
3.03.3BBBC7.3
3.61.9BBBB7.3
3.62.4BBBB7.3
3.62.8BBBB7.3
3.63.3BBBC7.3
3.01.9AABB3.6
3.02.4ABBB3.6
3.02.8BBBB3.6
3.03.3BBBC3.6
3.61.9BBBB3.6
3.62.4BBBB3.6
3.62.8BBBB3.6
3.63.3BBBB3.6
Column 1234567

Legend - Stud Sizes: A = 38 mm x 89 mm · B = 38 mm x 140 mm · C = 38 mm x 184 mm or double 38 mm x 140 mm

Notes to Table 1.3.4.V.:

  1. Design is based on load combinations of total roof load, wind load and stored product acting at the same time on a closed building.
  2. All notes following Table 1.3.4.U. apply, with the following conditions/exceptions:
  • 14.6 kN/m loading: Full 4.8 m sidewall hay/straw storage space above. It is supported by beams spaced at 3.6 m o.c. The outside plate carries a 1.8 m floor width. If the loading is greater, refer to a qualified person for design.
  • 7.3 kN/m loading: Full 2.4 m sidewall hay/straw storage space above or a gambrel roof structure >9.14 m in total width. Floor support beams as above.
  • 3.6 kN/m loading: Small gambrel roof structure or storage space for light storage. Floor support beams as above.

Table 1.3.4.W. Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey)

Forming Part of Sentence 1.3.4.(1)

Table 1.3.4.W — Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey), Ungraded Lumber, Full-Dimensioned, Wind Load: q10 ≤ 0.30 kPa
Sidewall Height, mTotal Roof Load, kPa406 mm o.c. Building Width, 9.14 m406 mm o.c. Building Width, 12.2 m406 mm o.c. Building Width, 15.2 m406 mm o.c. Building Width, 18.3 m
3.01.9AAAA
3.02.4AAAB
3.02.8AABB
3.03.3ABBB
3.61.9AABB
3.62.4ABBB
3.62.8BBBB
3.63.3BBBB
4.21.9ABBB
4.22.4BBBB
4.22.8BBBC
4.23.3BBCC
4.81.9BBBB
4.82.4BBBC
4.82.8BBCC
4.83.3BCCC
Column 123456
Table 1.3.4.W (continued) — Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey), Ungraded Lumber, Full-Dimensioned, Wind Load: q10 ≤ 0.30 kPa
Sidewall Height, mTotal Roof Load, kPa610 mm o.c. Building Width, 9.14 m610 mm o.c. Building Width, 12.2 m610 mm o.c. Building Width, 15.2 m610 mm o.c. Building Width, 18.3 m
3.01.9AAAB
3.02.4ABBB
3.02.8BBBB
3.03.3BBBC
3.61.9BBBB
3.62.4BBBC
3.62.8BBCC
3.63.3BCCC
4.21.9BBBC
4.22.4BBCC
4.22.8BCCC
4.23.3CCCC
4.81.9BBCC
4.82.4BCCC
4.82.8CCCC
4.83.3CCCC
Column 123456
Table 1.3.4.W (continued) — Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey), Ungraded Lumber, Full-Dimensioned, Wind Load: q10 ≤ 0.45 kPa
Sidewall Height, mTotal Roof Load, kPa406 mm o.c. Building Width, 9.14 m406 mm o.c. Building Width, 12.2 m406 mm o.c. Building Width, 15.2 m406 mm o.c. Building Width, 18.3 m
3.01.9AAAA
3.02.4AABB
3.02.8ABBB
3.03.3BBBB
3.61.9ABBB
3.62.4BBBB
3.62.8BBBC
3.63.3BBCC
4.21.9BBBB
4.22.4BBBC
4.22.8BBCC
4.23.3BCCC
4.81.9BBBC
4.82.4BBCC
4.82.8BCCC
4.83.3CCCC
Column 123456
Table 1.3.4.W (continued) — Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey), Ungraded Lumber, Full-Dimensioned, Wind Load: q10 ≤ 0.45 kPa
Sidewall Height, mTotal Roof Load, kPa610 mm o.c. Building Width, 9.14 m610 mm o.c. Building Width, 12.2 m610 mm o.c. Building Width, 15.2 m610 mm o.c. Building Width, 18.3 m
3.01.9AABB
3.02.4ABBB
3.02.8BBBC
3.03.3BBCC
3.61.9BBBC
3.62.4BCCC
3.62.8BCCC
3.63.3CCCC
4.21.9BBCC
4.22.4BCCC
4.22.8CCCC
4.23.3CCCC
4.81.9BCCC
4.82.4CCCC
4.82.8CCCC
4.83.3CCCC
Column 123456

Legend - Stud Sizes: A = 50.8 mm x 101.6 mm · B = 50.8 mm x 152.4 mm · C = 50.8 mm x 203.2 mm or double 50.8 mm x 152.4 mm under the trusses, with an intermediate 50.8 mm x 152.4 mm stud at 610 mm

Notes to Table 1.3.4.W.:

  1. Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
  2. It is assumed that the double top plate is rigid enough to cause load sharing amongst all studs regardless of the spacing 406 mm or 610 mm.
  3. Solid bridging shall be used on all walls as follows: ≤ 3.0 m: 1 row at mid-height. 3.6 m to 4.2 m: 2 rows at third-points. 4.8 m: 3 rows at quarter-points.
  4. Wind bracing shall not impose additional bending forces onto the stud.